58
inVENTer Connect controller platform | Installation instructions
TECHNICAL DATA
6
Technical data
1.1 Easy Connect e16 controller
Feature
Value
Protection class (EN 61140)
II
Type of protection (DIN EN 60529)
IP31
Input voltage mains voltage [V AC] [Hz]
230 / 50
Operating voltage [V DC]
5
Power consumption [W]
0.6
Power consumption in standby [W]
0.4
Radio frequency [MHz]
868
Radio network range [m]
Free field: 100
Bluetooth radio frequency [GHz]
2.4
Bluetooth range [m]
5
Temperature measuring range [°C]
0 – 60
Air humidity measuring range [%]
20 – 90
Dimensions [H x W x D in mm]
90 x 90 x 17
Conformity
Table 6: Technical data - controller
1.2 Connect inner cover
Feature
Value
Protection class (DIN EN 61140)
II
Type of protection (DIN EN 60529)
IP21
Input voltage mains voltage [V AC] [Hz]
230 / 50
Operating voltage [V DC]
18 – 24
Fan voltage [V DC]
6 – 16
Power consumption [W]
5
Power consumption in standby [W]
0.8
Radio frequency [MHz]
868
Radio network range [m]
Free field: 100
Extract air/outdoor air
Free from aggressive gases, dust and oils
Housing dimensions [H x W x D in mm]
Flush-mounted: 258 x 258 x 41
Surface-mounted: 271 x 271 x 41
Installation depth, flush [mm]
+ 38
Standard filter filter class (DIN EN ISO 16890)
ISO Coarse 45 %
(G3 according to EN779)
Conformity
Table 7: Technical data - inner cover