background image

 

           

         

 

  

 

 

 

                         
 
                                      

 

 

Interfaz DK-RC-MBS-1 

 

          

FW:1.6

 

 

Interface DK-RC-MBS-1

                       

FW:1.6 

                                

                  1 / 2

 

© Intesis Software S.L.U. - Todos los derechos reservados/ All rights reserved  

 

IntesisBox es una marca registrada de / is a registred trademark of

 

Intesis Software SLU

 

 

La información en este documento puede variar sin previo aviso. / This information is subject to change without notice.

 

 

Doc. Rev 3.5 

 

URL 

email 

Phone 

 

http://www.intesisbox.com                                          
[email protected] 
+34 938047134 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 

 
 

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

Esta  interfaz  debe  ser  instalada  por  personal  técnico 
acreditado  (electricista,  instalador  o  personal  técnico 
cualificado)  y  siguiendo  todas  las  instrucciones  de 
seguridad. 

 

La interfaz debe ser instalada en una ubicación con acceso 
restringido. 

 

Antes  de  manipular  en  el  interior  del  aire  acondicionado, 
asegúrese de que está completamente desconectado  de  la 
red eléctrica.  

 

En caso de instalación mural de la interfaz junto a la unidad 
interior  de  aire  acondicionado,  fije  la  interfaz  de  forma 
segura siguiendo las instrucciones del diagrama de abajo. 

 

This  interface  must  be  installed  by  accredited  technical 
personnel  (electrician,  installer  or  qualified  technical 
personnel) and they must follow all the safety instructions. 
 

 

This  interface  must  be  installed  in  an  acces  restricted 
location 

 

Before  manipulating  the  AC  indoor  unit,  make  sure  it  is 
completely disconnected from Mains Power. 
 

 

In  case  of  wall  mounting  of  the  interface  next  to  the  AC 
indoor  unit,  attach  the  interface  safely  following  the 
instructions of the diagram below. 

 

 

Desconecte el aire acondicionado de la red eléctrica. 

 

Fije la interfaz a la pared junto a la unidad interior del aire 
acondicionado  siguiendo  las  instrucciones  del  diagrama  de 
abajo o dentro de la unidad interior del aire acondicionado 
(respete las instrucciones de seguridad anteriores). 

 

Conecte  el  interfaz  al  bus  P1P2  en  cualquier  punto  del 
mismo. El bus P1P2 es el bus que conecta la unidad interior 

de  aire  acondicionado  y  el  Control  Remoto  por  cable.  Son 
un par de hilos que se conectan a los terminales P1P2. Este 
bus no tiene polaridad. 

 

Conecte  el  bus  EIA-485  al  conector 

EIA485

  de  la  interfaz. 

Respete la polaridad. 

 

Tape  la  unidad  interior  del  aire  acondicionado  y  vuelva  a 
conectarla a la red eléctrica. 

 

Siga  las  instrucciones  del  Manual  de  Usuario  para  la 
configuración y puesta en servicio de la interfaz. 

 

Siga  las  instrucciones  de  la  página  siguiente  para 
configurar la interfaz a través de los micro interruptores. 

 

Disconnect the air conditioning from the Mains Power. 

 

Attach  the  interface  next  to  the  AC  indoor  unit  (wall 
mounting) following the instructions of the diagram below or 
install  it  inside  the  AC  indoor  unit  (respect  the  safety 

instructions given above). 

 

Connect  the  interface  to  the  P1P2  bus  in  any  point  of  the 
bus. The  P1 P2 bus  is the  bus that connects the AC  indoor 
unit  and  the  wired  Remote  Controller.  It  is  a  two-wire  bus 
connecting  terminals  P1P2.  This  P1P2  connection  has  no 
specific polarity. 

 

Connect  the  EIA-485  bus  to  the  connector 

EIA485

  of  the 

interface. 

 

Close the AC indoor unit and reconnect it to Mains Power. 
 

 

Follow  the  instructions  on  the  User

’s

  Manual  to  configure 

and commission the interface. 

 

Follow  the  instructions  of  the  next  page  to  configure  the 
interface through on-board DIP-switches. 

 

  

WARNING 

  

ATENCIÓN 

Siga  atentamente  estas  instrucciones  de  seguridad  e 
instalación.  Un  manejo  inadecuado  puede  ocasionar  daños 
graves  para  su  salud  y  daños  irreparables  en  la  interfaz  y/o 
en la unidad interior del aire acondicionado. 

Follow  carefully  this  safety  and  installation  instructions.  Not 
proper work may lead to a serious damage for your health and 
may harm seriously the interface and/or the AC indoor unit. 

IMPORTANTE:

  El  cable  a  usar  para  la  conexión  de  DK-

RC-MBS-1 al bus P1P2 puede ser cualquier cable de dos hilos 
de  0.75mm2  hasta  1.25mm2.  La  distancia  máxima  para  el 
bus  P1P2  es  de  500  metros  (1640.42  pies).  Consulte  el 
Manual de la unidad de aire acondicionado para más detalles. 

Mantenga  este  cable  de  comunicación  lo  más  alejado  posible 
del  cableado  eléctrico  y  del  cable  de  tierra.  No  los  enrolle 
juntos. 
 

 
 

IMPORTANT:

  The  cable  used  for  connection  of  DK-RC-

MBS-1 to P1P2 bus can  be any two-wire  cable  of 0.75mm2 to 
1.25mm2. The maximum distance used to install the bus P1P2 
is 500 meters (1640.42 ft). Check the Manual of the AC indoor 
unit for more details. 

Keep  this  communication  cable  far  away  from  electrical  wires 
and ground wire. Do not bundle them together. 
 
 

 

El Manual de Usuario está disponible en: 
 

https://www.intesisbox.com/en/daikin-modbus-vrv-dk-rc-mbs-1/gateway/ 

 

The 

User’s Manual

 is available at:  

 

https://www.intesisbox.com/en/daikin-modbus-vrv-dk-rc-mbs-1/gateway/ 

 

Instrucciones de seguridad 

 

Safety intructions 

 

Instrucciones de instalación 

 

Installation instructions 

 

     P1  
     P2 

90 mm 

/ 3.5”

 

IntesisBox

®

 

DK-RC-MBS-1 

MODBUS RTU 

EIA-485 

Bus

 

EIA485 

 A+  B- 

P1 P2 

AC Unit 

53 mm 

/ 2.1”

 

Para fijación mural 
extraiga hacia fuera 
las grapas superior 

e inferior hasta oir 
el "click". 

 
For wall mounting, 
extract the upper 

and down staples 
until you hear the 
"click".

 

P1 P2 

DAIKIN 

Unidad interior de A.A. 
AC Indoor Unit 

(No es obligatorio tenerlo en la red) 

(It is not mandatory to have it in the network) 

 

Internal electronic 
control board 

Tarjeta de control 
Electrónico interno 

Conexión al bus P1P2. 
Cable de dos hilos. 

 

Connection to P1P2 
bus. Two wire cable. 

Remote Controller 

Control Remoto 

Max. 500m /1640.42 ft  