IntesisBox
®
ASCII Server - LON
Doc. Rev. 2
Installation Manual
URL
tel
http://www.intesis.com
[email protected]
+34 938047134
3 / 5
This information is subject to change without notice.
Connections
________________________________________________________________________________________
Notes:
1.
Must use NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply.
If using DC power supply:
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (9 to 30 Vdc).
The power supply can be connected to earth but only through the negative terminal, never through the positive terminal.
If using AC power supply:
Make sure the voltage applied is of the value admitted (24 Vac). Do not connect any of the terminals of the AC power
supply to earth, and make sure the same power supply is not supplying any other device.
2.
ASCII EIA232 connection: Connect the cable coming from the programmable controller to the connector ASCII EIA232 of IntesisBox,
this is a standard EIA232 DB9 male connector (DTE) in which only lines TX, RX and GND are used, see user's manual for details.
Respect the maximum distance of 15 meters for this cable.
3.
Use the software LinkBoxASCII to configure IntesisBox. Consult the user's manual for details.
Console wire 1.8 m long.
DB9 Female - DB9 Male
standard. It is supplied.
LinkBoxASCII
Only needed for
configuration
See Note 3
Power
See Note 1
LON
TP/FT-10
PC Console
- +
IntesisBox
®
www.intesis.com
EIA232
B A
LON TP/FT-10
ASCII
ASCII
EIA232
See Note 2
CMN 24Vac
9 - 30Vdc
Max.125 mA
24Vac
Max.127mA
50-60Hz
ASCII TCP
+ LinkBoxASCII
Ethernet
RJ45
Ethernet