Error Code
Modbus
Error in
Remote
Controller
System
Error Description
282
C6
PCB 4 error
283
C7
PCB 5 error
284
C8
Peripheral unit input device error
285
C9
Display device error
286
CA
EEPROM error
287
CC
Peripheral unit sensor error
288
CF
Peripheral unit external connector error (USB memory)
289
CJ
Other parts error
293
F1
RAC
System tool software error
294
F2
Inverter
System tool adaptor error
295
F3
Models G
System tool interface error
296
F4
series
System tool environment error
309
J1
RB unit error
310
J2
Branch boxes error
311
J3
VRF
Total heat exchanging, ventilation unit error
312
J4
J-II/V-II/VR-II Domestic hot water unit error
313
J5
Series
Zone control interface error
VRF V / S / J Series
Error Code
Modbus
Error in
Remote
Controller
System
Error Description
0
00
No Error
2
02
Model information Error
4
04
Power frequency Error
6
06
VRF
EEPROM access Error
7
07
V / S / J
EEPROM deletion Error
9
09
Series
Room sensor Error
10
0A
Heat Ex. Middle Sensor Error
11
0b
Heat Ex. Inlet sensor Error
12
0C
Heat Ex. Outlet sensor Error
13
0d
Blower temperature thermistor Error
17
11
Drain Error
18
12
Room temperature Error
19
13
Indoor fan motor Error
20
18
VRF
Standard wired remote Error
V / S / J
Standard wired token Error
31
1F
Series
Network communication Error
32
20
Node setting error
33
21
Communication Error between Main PCB & Transmission PCB
34
32
Outdoor unit Error
In case you detect an error code not listed, contact your nearest Fujitsu technical support service for more information
on the error meaning.