© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL http://www.intesis.com
Rev.1.5
2 / 2
Enclosure
Plastic, type PC (UL 94 V-0)
Net dimensions (d
x
w
x
h): 90x88x56 mm
Recommended space for installation (d
x
w
x
h): 130x100x100mm
Color: Light Grey. RAL 7035
Battery
Size: Coin 20mm x 3.2mm
Capacity: 3V / 225mAh
Type: Manganese Dioxide Lithium
Mounting
Wall.
DIN rail EN60715 TH35.
Console
Port
Mini Type-B USB 2.0 compliant
1500VDC isolation
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
USB port
Type-A USB 2.0 compliant
Only for USB flash storage device (USB pen
drive)
Power consumption limited to 150mA (HDD
connection not allowed)
Power
1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
24VDC +/-10%
Push Button
Button A: Check the user manual
Button B: Check the user manual
Operation
Temperature
0°C to +60°C
Ethernet
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Operational
Humidity
5 to 95%, no condensation
Port A
1 x DALI port (Plug-in screw terminal block orange 2 poles)
1500VDC isolation from other ports
DALI power consumption: 240mA
Voltage rating: 16VDC
1 x Plug-in screw terminal block green (2 poles)
Reserved for future use
Protection
IP20 (IEC60529)
LED
Indicators
10 x On board LED indicators
2 x Error (red) / Power LED
2 x Ethernet Link / Speed
2 x Port A TX/RX
2 x Port B TX/RX
1 x Button A indicator
1 x Button B indicator
Switch A
(SWA)
1 x DIP-Switch for PORT A configuration:
Reserved for future use
PORT B
1 x DALI port (Plug-in screw terminal block green 2 poles)
1500VDC isolation from other ports
DALI power consumption: 240mA
Voltage rating: 16VDC
Switch B
(SWB)
1 x DIP-Switch for PORT B configuration:
Reserved for future use
CONNECTIONS
ELECTRICAL & MECHANICAL FEATURES
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply.
Respect polarity
applied of terminals (+) and (-). Be sure the voltage applied is within the range admitted (check table
below). The power supply can be connected to earth but only through the negative terminal, never
through the positive terminal.
Ethernet / Modbus TCP / Console (UDP & TCP)
Connect the cable coming from the IP network to the connector ETH of the gateway. Use an Ethernet
CAT5 cable. If communicating through the LAN of the building, contact the network administrator and
make sure traffic on the port used is allowed through all the LAN path (check the gateway user manual
for more information). With factory settings, after powering up the gateway, DHCP will be enabled for 30
seconds. After that time, if no IP is provided by a DHCP server, the default IP 192.168.100.246 will be
set.
PortA / DALI #0
Connect the DALI bus to connectors A4 (+), A3 (-) of
gateway’s PortA. The Intesis gateway provides
16VDC (+/-2%) DALI voltage to the bus.
PortB / DALI #1
Connect the DALI bus to connectors B2 (+), B1 (-) of
gateway’s PortB. The Intesis gateway provides
16VDC (+/-2%) DALI voltage to the bus.
Console Port
Connect a mini-type B USB cable from your computer to the gateway to allow communication between
the Configuration Software and the gateway. Remember that Ethernet connection is also allowed. Check
the user manual for more information.
USB
Connect a USB storage device (not a HDD) if required. Check the user manual for more information.
Port B
USB
EIA 232
B1 B2 B3
SW B
SW A Ethernet Port
Port A
A1 A2
A3 A4
Power
zzzzz
Run / Error
Eth.
Link/Spd
PortA
TX/RX
PortB
TX/RX
Button A
Button B
Console
- +
Power Supply
DALI #0
Ethernet
Modbus TCP
USB
storage
(not used)
DALI #1
Console
Port
100 mm (h)
100 mm (w)
130 mm (d)
This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic
parts and they must be properly disposed of by following the instructions at
https://intesis.com/weee-regulation