background image

www.intertec.info

Operating Instructions CP MICROTHERM DENA

HOM180473483Ien-3

Page 5 / 7

INTERTEC-Hess GmbH · Raffineriestr. 8 · 93333 Neustadt/Donau · Germany · 

 +49 9445 9532-0 ·   [email protected]

Illustration 1: 

Installation example MICROTHERM with TAE or

TS and clearance

Additional  installation  material,  such  as  rails  or  panels
and also junction boxes, are not included in the standard
scope of delivery (see 

Installation accessories [

}

Page 4]

)

and must be ordered additionally.

8

Connection

 INFO

The device may only be connected up and secured by a
trained person, taking into account the "rated voltage"
and "rated current" specified on the nameplate.

Where  operating  voltage  =  measured  voltage  (rated
voltage),  then  the  heater  is  at  its  rated  output.  Mains
voltage fluctuations up to 10 % are then permissible.

Each heater with integrated TS thermostat must be pre-
ceded  by  a  10  A  fuse  or  a  motor  protection  switch  with
short-circuit  and  thermal  quick  release  (set  to  10  A)  as
short-circuit  protection.  When  using  a  heater  without  in-
tegrated thermostat, the fuse protection can be selected
according to the cross-section of the supply cable.

Additional  equipotential  bonding  is  required.  The  ter-
minal  block  designated  for  this  purpose  has  the  ground
sign.

ATTENTION:

Never remove the

adapter/ cable gland!

Illustration 2: 

Example heater with KLE connection

 CAUTION

NOTICE: Do not remove adapter/ cable connec-
tion to connect up the heater!

This would cause irreversible damage to the heater and
this would mean that the explosion protection can no
longer be warranted.

The illustration may deviate from the heater.

1

2

J

L
N
PE

J

J

J

Junction box

TAE

TS

Heater

Option AM

bn=brown bl=blue ye/gn=yellow/green bk=black gy=grey

bn

bl

ye/gn

bk

gy

Illustration 3: 

CP ..THERM with TAE

Summary of Contents for CP MICROTHERM DENA

Page 1: ...Operating Instructions CP MICROTHERM DENA HOM180473483Ien 3 11 02 2020 ...

Page 2: ... of contents 1 General 3 2 Use 3 3 Explanation of symbols for warnings and signal words 3 4 Safety information 3 5 Installation accessories 4 6 Technical Data 4 7 Installation 4 8 Connection 5 9 Commissioning 6 10 Maintenance 6 11 Troubleshooting 6 12 Deinstallation 6 13 Disposal 6 14 Declaration of Conformity 7 15 Further information and service 7 ...

Page 3: ... cable for frost protection applications or a safety thermostat for maintaining temperature If a TAE is used the respective operating instructions must be complied with Product approval 18 KA4BO 0090X and 18 KA4BO 0089X with appendices and supplements as well as IEC Scheme Certificate IECEx PTB 07 0052X See http www intertec info 3 Explanation of symbols for warnings and signal words The safety in...

Page 4: ... 275 V AC Connecting cable Silicone hose cable notch and oil resistant 3 x 1 5 mm Ø8 8 mm Connecting cable AM Silicone hose cable notch and oil resistant 3 x 1 0 mm Ø8 5 mm Material Seawater proof alu minium black anodized Mean Time Before Failure 50 000 h Storage temperature 60 to 80 C Special voltages with corresponding power adjustment and component selection are possible Profile type N Height ...

Page 5: ...then permissible Each heater with integrated TS thermostat must be pre ceded by a 10 A fuse or a motor protection switch with short circuit and thermal quick release set to 10 A as short circuit protection When using a heater without in tegrated thermostat the fuse protection can be selected according to the cross section of the supply cable Additional equipotential bonding is required The ter min...

Page 6: ...clean and free of dust and harmful substances that could lead to excessive temperature rise In the dust Ex area the applicable requirements of KS C IEC 60079 17 must be complied with 11 Troubleshooting If the heater fails check the installation Carry out a con tinuity test on the heating circuit Pay attention to the connection diagram and switching point of the thermo stat In the case of overheati...

Page 7: ...otific ation 2016 54 Ministry of Employment and Labor appendix 7 of notific ation 2016 54 Ministry of Employment and Labor appendix 15 of noti fication 2016 54 KS C IEC 61000 6 4 2014 KS C IEC 60529 Marking 18 KA4BO 0090X 18 KA4BO 0089X Ex d IIC T6 T3 Ex tb IIIC T85 C T100 C T135 C T200 C Neustadt May 14th 2018 Dipl Ing Martin Hess Managing Director 15 Further information and service If the inform...