Operating Instructions CP MICROTHERM DC.A
Page 6 / 12
HOM225729419Ien-3
INTERTEC-Hess GmbH · Raffineriestr. 8 · 93333 Neustadt/Donau · Germany ·
+49 9445 9532-0 · [email protected]
ATTENTION:
Never remove the
adapter/ cable gland!
Illustration 3:
Example heater with KLE connection
CAUTION
NOTICE: Do not remove adapter/ cable connec-
tion to connect up the heater!
This would cause irreversible damage to the heater and
this would mean that the explosion protection can no
longer be warranted.
The illustration may deviate from the heater.
1
2
J
L
N
PE
J
J
J
Junction box
TAE
TS
Heater
Option AM
bn=brown bl=blue ye/gn=yellow/green bk=black gy=grey
bn
bl
ye/gn
bk
gy
Illustration 4:
CP ..THERM with TAE
1
2
J
L
N
PE
J
Terminal box
TS
Heating
Option: FA
br=brown bl=blue ye/gn=yellow/green bk=black gr=grey
br
bl
ye/gn
bk
gr
Illustration 5:
CP ..THERM with TS
10
Commissioning
If the heater is installed in accordance with the notes in
the
Page 5]
sections, then the radiator may be commis-
sioned.
CAUTION
Sufficient heat dissipation must be ensured.
Unauthorized covers must be removed as otherwise
there is the risk of the heater overheating.
The heating circuit is permanently disconnected by a
temperature melt fuse which can't be reset if these in-
stallation instructions are not adhered to.
11
Maintenance
The design of the device does not require any mainten-
ance.
Functional and safety test intervals can be freely selec-
ted by the operator in accordance with the applicable
regulations.