background image

www.intertec.info

Operating Instructions CP MICROTHERM DBNA

HOM146708235Ien-4

Page 7 / 8

INTERTEC-Hess GmbH · Raffineriestr. 8 · 93333 Neustadt/Donau · Germany · 

 +49 9445 9532-0 ·   [email protected]

1

2

J

L
N
PE

J

Terminal box

TS

Heating

Option: FA

br=brown bl=blue ye/gn=yellow/green bk=black gr=grey

br

bl

ye/gn

bk

gr

Illustration 5: 

CP ..THERM with TS

10

Commissioning

If the heater is installed in accordance with the notes in
the 

Installation  [

}

Page  5]

  section  and 

Connection  [

}

Page  5]

  sections,  then  the  radiator  may  be  commis-

sioned.

 CAUTION

Sufficient heat dissipation must be ensured.

Unauthorized covers must be removed as otherwise
there is the risk of the heater overheating.

The heating circuit is permanently disconnected by a
temperature melt fuse which can't be reset if these in-
stallation instructions are not adhered to.

11

Maintenance

The design of the device does not require any mainten-
ance.

Functional  and  safety  test  intervals  can  be  freely  selec-
ted  by  the  operator  in  accordance  with  the  applicable
regulations.

Repairs  may  only  be  carried  out  by  the  manufacturer  in
the factory.

All  components  have  to  be  kept  clean  and  free  of  dust
and  harmful  substances  that  could  lead  to  excessive
temperature rise.

In  the  dust  Ex  area,  the  applicable  requirements  of
ABNT  NBR  IEC  60079-17  and  ABNT  NBR  IEC
60079-19 must be complied with.

12

Troubleshooting

If the heater fails, check the installation. Carry out a con-
tinuity  test  on  the  heating  circuit.  Pay  attention  to  the
connection  diagram  and  switching  point  of  the  thermo-
stat!

In the case of overheating, the thermal indicator (see fig-
ure) indicates a discoloration. If more than four fields are
blackened,  the  heater  must  be  uninstalled  and  returned
to the manufacturer for inspection.

Illustration 6: 

Temperature indicator

13

Deinstallation

Disassembly  may  only  be  carried  out  by  a  trained  per-
son.

 DANGER

Risk of fatal injury from electric current!

If contact is made with live components, there is the risk
of fatal injury.

For this reason, switch off the voltage supply, secure
against being switched on again and check that no more
voltage is present.

Disconnect connection line from the clamps and from the
connection  socket,  disconnect  device  from  bracket  and
remove it.

14

Disposal

Disassemble  the  components  of  the  product,  taking  the
applicable local labour protection and environmental reg-
ulations into consideration and make sure that the com-
ponents are recycled:

• Scrap metal

• Send plastic elements to recycling

Summary of Contents for CP MICROTHERM DBNA

Page 1: ...Operating Instructions CP MICROTHERM DBNA HOM146708235Ien 4 05 02 2020...

Page 2: ...al 3 2 Use 3 3 Special conditions for safe use 3 4 Explanation of symbols for warnings and signal words 3 5 Safety information 4 6 Installation accessories 4 7 Technical Data 4 8 Installation 5 9 Conn...

Page 3: ...must be protected mechanically 2 If connection is made in the potentially explosive area the connecting lead shall be connected by means of an enclosure that meets the requirements of a type of protec...

Page 4: ...e of flat steel 1 Packet of screws containing the following 2 Hexagon bolts M 6x12 1 T head bolt type 28 15 M 6x15 2 M6 flat square nut 1 Washer shape A 6 4 2 Lock washers shape J 6 4 1 M6 hex nut If...

Page 5: ...be permanently installed up to the inlet into the on site junction box taking the per missible bending radius 5 x outer diameter into consid eration In the dust Ex area the applicable requirements of...

Page 6: ...sed which switches off the supply as soon as the insulation resistance is no greater than 50 per Volt of the rated voltage refer also to ABNT NBR IEC 60079 14 2009 ATTENTION Never remove the adapter c...

Page 7: ...f dust and harmful substances that could lead to excessive temperature rise In the dust Ex area the applicable requirements of ABNT NBR IEC 60079 17 and ABNT NBR IEC 60079 19 must be complied with 12...

Page 8: ...79 0 2013 Vers o Corrigida 2 2016 ABNT NBR IEC 60079 1 2016 ABNT NBR IEC 60079 31 2014 ABNT NBR IEC 60529 2005 Vers o Corrigida 2 2011 IEC 61000 6 4 2007 A1 2011 Designation NCC 17 0136 X Ex tb IIIC T...

Reviews: