background image

440 04 6001 00

7

Specifications  subject to change without notice.

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal

injury or death.
Disconnect 115vac electrical power before changing

speed tap.

!

WARNING

(Read following caution before changing taps).

UNIT DAMAGE HAZARD

To avoid operating outside the rise range and avoid

component damage:
Refer to the Air Delivery Tables to determine which

airflows and settings are allowed for proper heating

airflow.  DO NOT use the highlighted settings for

Heating airflow. The highlighted settings are to be used

for Cooling and Continuous Fan ONLY.

CAUTION

!

Change the blower speed taps as required to maintain

proper temperature rise for Heating and Cooling as

described above. To change blower motor speed selections

for heating mode, remove blower motor lead from control

HEAT terminal(s). (See Figure 2) Select desired blower

motor speed lead(s) from the other motor leads and relocate

it/them to HEAT (heating blower tap) terminal(s). Reconnect

original lead on SPARE terminal.

Adjust Blower Off Delay (Heat Mode)

If desired, the main blower off time delay period may be

lengthened or shortened when operating in the heating

mode to provide greater comfort. For position and location

of jumpers on control center. (See Figure 2 and Figure 16)

The blower off-delay has four adjustable settings from 90

sec to 180 sec. (See Table 1) To change the blower off

delay setting, move the jumper from one set of pins on the

control to the pins used for the desired blower off delay.

Factory blower off-delay setting is 120 sec.

Table 1 – Blower Off Delay Jumper Positions

PINS

1 AND 2

2 AND 3

3 AND 4

4 AND 5

Time (in sec.)

90

120

150

180

Adjust Cooling Airflow

The cooling airflow can be set from the remaining blower

speed taps. Refer to the Air Delivery Table (see Table 5) in

these instructions.

FURNACE OVERHEATING HAZARD

Failure to follow this caution may result in reduced

furnace life.
Recheck temperature rise. It must be within limits

specified on the rating plate. Recommended operation

is at the mid--point of rise range or slightly above.

CAUTION

!

Adjust Thermostat Heat Anticipator

Mechanical thermostat:

 Set thermostat heat anticipator to

match the amp. draw of the electrical components in the

R-W circuit. Accurate amp. draw readings can be obtained

at the wires normally connected to thermostat sub-base

terminals, R and W. The thermostat anticipator should NOT

be in the circuit while measuring current.

1. Remove thermostat from sub-base or from wall.

2. Connect an amp. meter across the R and W

sub-base terminals or R and W wires at wall.

3. Record amp. draw across terminals when furnace is

in low heat and after blower starts.

4. Set heat anticipator on thermostat per thermostat

instructions and install on sub-base or wall.

5. Install blower access door.

Electronic thermostat:

 Set cycle rate for 3 cycles per hr.

Check Safety Controls

The flame sensor, gas valve, and pressure switch were all

checked in the Start

up procedure section as part of normal

operation.

1. Check Main Limit Switch 

This control shuts off combustion system and

energizes air

circulating blower motor, if furnace

overheats. By using this method to check the temper-

ature limit control, it can be established that the limit is

functioning properly and that the limit will operate if

there is a restricted return

air supply or motor failure.

If the limit control does not function during this test,

the cause must be determined and corrected.
a. Run furnace for at least 5 minutes.
b. Gradually block off return air with a piece of

cardboard or sheet metal until the limit trips.

c. Unblock return air to permit normal circulation.

d.  Burners will re

light when furnace cools down.

2. Check Pressure Switch(es) 

This control proves operation of the draft inducer

blower.
a. Turn off 115

v power to furnace.

b. Disconnect inducer motor lead wires from wire

harness.

c. Turn on 115

v power to furnace.

d. Set thermostat to “call for heat” and wait 1 minute.

When low pressure switch is functioning properly, hot

surface  igniter should 

NOT 

glow and control

diagnostic light flashes a status code 31. If hot

surface igniter glows when inducer motor is

disconnected, shut down furnace immediately.

e. Determine reason low pressure switch did not

function properly and correct condition.

f. Turn off 115

v power to furnace.

g. Reconnect inducer motor wires, replace  door, and

turn on 115

v power.

h. Blower will run for 90 sec  before beginning the call

for heat again.

i. Furnace should ignite normally.

Checklist

1. Put away tools and instruments. Clean up debris.
2. Verify that the jumper is removed from the TEST/

TWIN terminal. Verify that there is nothing plugged in-

to the PLT connector.

NOTE

:  If there is a jumper connector plugged into PLT,

remove it and discard. (See  Figure 2)

3. Verify that the Blower/Heat Off Delay jumpers are set

as desired. (See Figure 2 and Figure 16)

4. Verify that the blower (lower door in upflow position)

and control (“Main” or upper door in upflow position)

doors are properly installed.

5. Verify that the Status LED glows. If not, check that the

power supply is energized and that the blower door is
secure. See Figure 5 to interpret diagnostic codes

.

6. Cycle test furnace with room thermostat to be sure

that it operates properly with the room thermostat.

Check all modes including Heat, Cool and Fan.

7. Check operation of accessories per manufacturer’s

instructions.

8. Review Owner’s Manual with owner.
9. Attach literature packet to furnace.

Summary of Contents for R9MSB0601716B

Page 1: ...in the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used throughout this man...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...115vac terminal is energized whenever blower operates HUM 24vac terminal is only energized when the low pressure switch LPS is closed on a call for heat Prime Condensate Trap with Water CARBON MONOXID...

Page 4: ...ions to match the required orifice to the manifold pressure to the heat content and specific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas s...

Page 5: ...hould be clear blue almost transparent See Figure 12 i Remove jumper R to W j Reinstall manifold pressure tap plug from gas valve 2 Verify natural gas input rate by clocking meter NOTE Contact your HV...

Page 6: ...exchangers or condensing flue gases in heat exchanger areas not designed for condensate S Shortened furnace life S Component damage Temperature rise must be within limits specified on furnace rating p...

Page 7: ...nals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat instructions and install on sub base or wall 5 Install blower access door Electronic thermo...

Page 8: ...743 3048 18 20 0 81 Derate multiplier factors are based on midpoint altitude for altitude range ON OFF Switch Regulator Seal Cap Regulator Adjustment Regulator Seal Cap under Cap 1 2 NPT Outlet 1 8 NP...

Page 9: ...290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 9...

Page 10: ...10 440 04 6001 00 Specifications subject to change without notice 338309 201 Rev E A11602 Figure 5 Service Label Information...

Page 11: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Page 12: ...5 1075 1015 950 885 Red 3 2 5 394 1030 1025 1030 1010 985 940 905 855 805 735 0801716B SIDE BOTTOM Black 4 0 389 1650 1620 1640 1605 1555 1495 1425 1345 1255 1165 Yellow 3 5 381 1420 1425 1400 1370 13...

Page 13: ...switch is 0 73 in W C The maximum make point of the switch is 0 83 in W C ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death There may be more than one el...

Page 14: ...ND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE BLOWER DOOR SWITCH WHT BLK WHT BLK NOTES Connect Y term...

Page 15: ...e sure that it operates properly with the room thermostat Check all modes including Heat Cool and Fan 7 Check operation of accessories per manufacturer s instructions 8 Review Owner s Manual with owne...

Page 16: ...8 Turn on electrical supply to furnace Blower Motor and Wheel Maintenance To ensure long life economy and high efficiency clean accumulated dirt and grease from blower wheel and motor annually The in...

Page 17: ...aning Burners and Flame Sensor The following items must be performed by a qualified service technician If the burners develop an accumulation of light dirt or dust they may be cleaned by using the fol...

Page 18: ...burner assembly without striking the igniter on surrounding parts c Inspect igniter for signs of damage or failure d If replacement is required remove the screw that secures the igniter on igniter bra...

Page 19: ...supply circuit is on Cleaning Heat Exchangers The following items must be performed by a qualified service technician Primary Heat Exchangers If the heat exchangers get an accumulation of light dirt o...

Page 20: ...ed Follow these procedures to winterize your furnace UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the furnace and other property damage Do not use ethylene glyco...

Page 21: ...ner Manifold A11461 Figure 12 Burner Flame SET SCREW MOTOR WHEEL HUB MOTOR SHAFT FLAT SCREW MOTOR ARM GROMMET SCREW LOCATION BLO HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHO...

Page 22: ...22 440 04 6001 00 Specifications subject to change without notice FLAME SENSOR BELOW BURNER FLAME ROLLOUT SWITCH BRACKET IGNITER IGNITER BURNER SUPT ASSY BURNER ASSY A11403 Figure 14 Burner Assembly...

Page 23: ...y If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains...

Page 24: ...flash the status code of the previous fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief com...

Page 25: ...control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check t...

Page 26: ...26 440 04 6001 00 Specifications subject to change without notice 339236 2 Rev A Figure 16 Wiring Diagram...

Page 27: ...can cause personal injury property damage or death Consult a qualified installer service agency or your local gas supplier for information or assistance The qualified installer or service agency must...

Reviews: