International comfort products H2A336G D200 series Technical Support Manual Download Page 4

TECHNICAL 

SUPPORT 

MANUAL

Split System Air Conditioner: H2A3, 3−Phase

4

501 04 2502 00

CFM

72

67

63††

62

57

72

67

63††

62

57

72

67

63††

62

57

72

67

63††

62

57

72

67

63††

62

57

MBh†

39.31 35.87 33.37 32.92 32.17 37.99 34.65 32.22 31.82 31.27 36.55 33.31 30.95 30.63 30.27 34.98 31.84 29.55 29.32 29.15 33.27 30.24 28.01 27.93 27.91

S/T‡

0.52

0.70

0.72

0.90

1.00

0.52

0.71

0.74

0.92

1.00

0.53

0.72

0.75

0.93

1.00

0.54

0.73

0.76

0.95

1.00

0.54

0.75

0.78

0.99

1.00

*

AMPS

11.56 11.44 11.30 11.28 11.23 12.51 12.40 12.26 12.24 12.21 13.59 13.48 13.35 13.33 13.31 14.83 14.74 14.61 14.60 14.59 16.29 16.21 16.09 16.09 16.09

HI PR

164

162

161

161

160

194

191

189

189

189

226

223

221

220

220

260

257

254

254

254

297

294

291

291

291

LO PR

86

78

72

71

69

87

79

73

72

71

89

80

74

74

73

90

82

76

75

75

92

83

77

77

77

MBh†

39.89 36.44 33.93 33.69 33.42 38.52 35.18 32.75 32.58 32.46 37.03 33.80 31.44 31.35 31.40 35.42 32.30 30.00 30.22 30.22 33.66 30.65 28.42 28.91 28.92

S/T‡

0.53

0.73

0.76

0.94

1.00

0.54

0.74

0.77

0.96

1.00

0.55

0.75

0.78

1.00

1.00

0.55

0.77

0.80

1.00

1.00

0.57

0.79

0.82

1.00

1.00

*

AMPS

11.82 11.72 11.59 11.58 11.56 12.76 12.67 12.55 12.54 12.54 13.84 13.75 13.63 13.63 13.64 15.08 15.01 14.89 14.91 14.91 16.53 16.48 16.37 16.40 16.40

HI PR

165

163

161

161

161

194

192

190

190

190

226

223

221

221

221

261

258

255

256

256

298

295

292

293

293

LO PR

88

80

74

73

73

89

81

75

75

74

91

82

76

76

76

92

84

77

78

78

93

85

79

80

80

MBh†

40.31 36.89 34.38 34.40 34.45 38.90 35.58 33.16 33.43 33.43 37.37 34.17 31.82 32.31 32.32 35.72 32.63 30.35 31.08 31.08 33.92 30.95 28.74 29.72 29.72

S/T‡

0.55

0.76

0.79

1.00

1.00

0.56

0.77

0.80

1.00

1.00

0.56

0.79

0.81

1.00

1.00

0.57

0.81

0.83

1.00

1.00

0.59

0.83

0.86

1.00

1.00

*

AMPS

12.07 11.99 11.87 11.87 11.88 13.01 12.94 12.83 12.85 12.85 14.08 14.02 13.91 13.94 13.94 15.32 15.27 15.17 15.21 15.21 16.77 16.74 16.64 16.69 16.69

HI PR

165

163

162

162

162

195

192

190

191

191

227

224

222

222

222

261

258

256

257

257

299

295

292

294

294

LO PR

90

82

75

76

76

91

83

76

77

77

92

84

77

79

79

93

85

79

81

81

95

86

80

83

83

1050

COOLING

36 Size Outdoor With EB*2X36F** Indoor Cooling

Outdoor Ambient Temperature − Degrees F, Dry Bulb

75

Entering Indoor Temperature − Degrees F, Wet Bulb

5

1

1

5

0

1

5

9

5

8

1200

1350

Total capacities are net (I.D. blower heat subtracted) system capacities based on 25’ line set.  
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

†† At TVA rating indoor condition (75 

°F 

db, 63 

°F 

wb), all other indoor air temperatures are at 80 

°

F db  

If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

^

System amps are total of indoor and outdoor amps.

Chart data is for 80

°

 

F indoor dry bulb. For indoor db temperatures other than 80

°

 F, measure Indoor db and Indoor CFM, and plug these into the

     formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T, and plug these into the formula below.
     (Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)

Sensible Capacity at Indoor db LOWER than 80 

°

F  =  ( MBh  x  S/T )   −

( 80  −  Indoor db )  x  835  x  Indoor CFM

1000

(

)

Sensible Capacity at Indoor db HIGHER than 80 

°

F  =  ( MBh  x  S/T )   +

( Indoor db  −  80 )  x  835  x  Indoor CFM

1000

(

)

Summary of Contents for H2A336G D200 series

Page 1: ...word CAUTION is used throughout this manual in the following manner Signal Words on Product Labeling Signal words are used in combination with colors and or pictures on product labels WARNING Safety...

Page 2: ...former with a grounded secondary connect the grounded side to the BRN YEL lead 8 When start capacitor and relay are installed start thermistor is not used 9 CH not used on all units 10 If any of the o...

Page 3: ...8 78 26 73 23 68 20 171 86 30 81 27 76 24 71 22 179 89 32 84 29 79 26 74 23 187 92 33 87 31 82 28 77 25 196 95 35 90 32 85 29 80 27 205 98 37 93 34 88 31 83 28 214 101 38 96 36 91 33 86 30 223 104 40...

Page 4: ...0 35 31 08 31 08 33 92 30 95 28 74 29 72 29 72 S T 0 55 0 76 0 79 1 00 1 00 0 56 0 77 0 80 1 00 1 00 0 56 0 79 0 81 1 00 1 00 0 57 0 81 0 83 1 00 1 00 0 59 0 83 0 86 1 00 1 00 AMPS 12 07 11 99 11 87 1...

Page 5: ...35 37 27 37 27 41 10 37 34 34 60 35 78 35 79 S T 0 56 0 78 0 81 1 00 1 00 0 57 0 79 0 82 1 00 1 00 0 58 0 81 0 84 1 00 1 00 0 59 0 83 0 86 1 00 1 00 0 60 0 85 0 88 1 00 1 00 AMPS 13 55 13 42 13 32 13...

Page 6: ...79 1 00 1 00 0 58 0 81 1 00 1 00 0 59 0 83 1 00 1 00 AMPS 15 58 15 41 15 27 15 26 16 86 16 66 16 51 16 51 18 30 18 07 17 91 17 91 19 91 19 65 19 49 19 49 21 69 21 39 21 22 21 22 HI PR 169 167 165 165...

Page 7: ...00 0 57 0 79 1 00 1 00 0 58 0 81 1 00 1 00 0 59 0 83 1 00 1 00 AMPS 19 81 19 53 19 27 19 27 21 41 21 16 20 95 20 95 23 31 23 08 22 90 22 90 25 56 25 34 25 18 25 18 28 23 27 99 27 86 27 86 HI PR 182 17...

Page 8: ...G 48 00 46 00 44 00 41 90 39 70 37 40 34 90 32 30 SDT 84 10 92 10 100 40 108 80 117 40 126 10 134 70 143 40 KW 1 82 1 99 2 18 2 38 2 61 2 87 3 18 3 55 H2A342 30 TCG 34 10 32 70 31 10 29 60 28 80 26 30...

Page 9: ...4 26 4 67 55 TCG 71 00 67 30 63 80 60 20 56 80 53 40 50 10 46 70 SDT 83 00 91 30 99 60 108 10 116 80 125 60 134 60 143 50 KW 2 51 2 73 2 99 3 27 3 59 3 95 4 34 4 77 H2A360 30 TCG 52 00 49 50 47 10 44...

Page 10: ...00 1 02 0 95 ED 2X36J 1 00 1 00 EHD2X42A 8MPV100 1 02 0 96 EB 2X36J 8MPV125 1 02 0 95 ED 2X42F 8MPV075 1 01 0 97 EHD2X42A 8MPV125 1 02 0 96 EB 2X36J 9MPV100 1 01 0 94 ED 2X42F 9MPV050 1 00 0 97 EHD2X4...

Page 11: ...95 FVM2X24 1 00 0 96 ED 2X36B 0 99 0 99 EHD2X36A 9MPV100 1 01 0 94 FVM2X36 1 01 0 94 ED 2X36F 8MPV075 1 00 0 96 EHD2X36A 9MPV125 1 01 0 94 FVM2X48 1 05 0 96 ED 2X36F 9MPV050 0 99 0 99 EHD2X36A 9MVX040...

Page 12: ...X48A MV20L24 B 0 99 0 89 EB 2X48J 9MVX080 1 01 0 95 ED 2X48J 1 01 1 01 EHD2X48A 0 99 0 99 EB 2X48J MV16J22 B 1 01 0 91 ED 2X48L 9MPV125 1 00 0 92 EMA2X48D 0 99 0 99 EB 2X48J 1 01 1 01 ED 2X48L 9MVX100...

Page 13: ...X60A 1 03 0 99 EB 2X60J MV16J22 B 1 02 0 94 ED 2X60L 9MPV125 1 03 1 01 EMA2X48D 0 98 0 98 EB 2X60J 1 03 0 99 ED 2X60L 9MVX100 1 02 0 96 FEM2X48 1 03 0 97 EB 2X60L 9MPV125 1 03 1 01 ED 2X60L 1 03 0 99...

Page 14: ...5 tons NOMINAL CAPACITY A Standard Grille G Coil Guard Grille C Coastal FEATURES H 208 230 3 60 L 460 3 60 VOLTAGE Sales Code Engineering Revision Extra Digit Extra Digit ACCESSORIES PART NUMBER IDEN...