508 01 1603 01
Specifications subject to change without notice.
41
LEGEND
Bold
indicates field-supplied drive is required.
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to
fan motor and drive tables to complete selection.
NOTES:
Maximum allowable fan speed is 1100 rpm for unit sizes 300 and 336;
1200 rpm for all other sizes. Fan performance is based on deductions
for wet coil, clean 2-in. filters, and unit casing. See table on page 42 for
factory-supplied filter pressure drop. For 60 Hz units, the medium-static
drive and standard motor combination is not available for size 300.
Table 40 — Fan Performance Data — 1.4-2.4 in. wg External Static Pressure
UNIT
AIRFLOW
(CFM)
EXTERNAL STATIC PRESSURE (in. w
g
)
1.4
1.6
1.8
2.0
2.2
2.4
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
FAS072
FHS072
1,800
921
1.07
975
1.23
1026
1.39
1074
1.55
1120
1.72
1164
1.90
2,100
942
1.26
997
1.43
1048
1.61
1097
1.79
1143
1.97
1186
2.16
2,400
963
1.47
1017
1.66
1069
1.85
1118
2.05
1164
2.25
—
—
2,700
987
1.71
1039
1.91
1090
2.12
1138
2.33
1185
2.55
—
—
3,000
1015
1.99
1065
2.20
1113
2.42
1161
2.65
—
—
—
—
FAS091
FHS091
2,250
930
1.29
986
1.47
1039
1.65
1089
1.84
1136
2.03
1181
2.22
2,600
950
1.53
1005
1.72
1057
1.92
1107
2.13
1154
2.33
—
—
3,000
980
1.86
1031
2.06
1081
2.27
1129
2.49
1175
2.72
—
—
3,400
1018
2.26
1065
2.48
1111
2.70
1156
2.93
—
—
—
—
3,750
1057
2.69
1101
2.92
1144
3.15
1186
3.39
—
—
—
—
FAS120
FHS120
3,000
961
1.78
1012
1.98
1062
2.19
1111
2.41
1158
2.64
—
—
3,500
1005
2.27
1052
2.49
1098
2.71
1142
2.94
1186
3.18
—
—
4,000
1058
2.90
1101
3.13
1143
3.36
1184
3.60
—
—
—
—
4,500
1116
3.66
1157
3.91
1196
4.16
—
—
—
—
—
—
5,000
1176
4.56
—
—
—
—
—
—
—
—
—
—
FAS150
3,750
912
2.39
971
2.76
1028
3.14
1083
3.54
1135
3.95
1185
4.36
4,300
928
2.75
982
3.13
1036
3.53
1087
3.94
1138
4.37
1187
4.81
5,000
956
3.30
1007
3.71
1056
4.13
1104
4.56
1151
5.00
1196
5.46
5,700
990
3.96
1039
4.40
1086
4.85
1130
5.31
1174
5.78
—
—
6,250
1019
4.54
1067
5.02
1112
5.50
1156
5.99
1198
6.49
—
—
FAS180
FHS180
4,500
912
2.75
967
3.12
1019
3.52
1070
3.92
1120
4.35
1168
4.79
5,300
942
3.34
992
3.76
1041
4.18
1088
4.61
1134
5.06
1179
5.52
6,000
971
3.95
1020
4.40
1067
4.86
1112
5.33
1156
5.81
1198
6.29
6,800
1005
4.72
1054
5.23
1101
5.75
1145
6.27
1187
6.79
—
—
7,500
1036
5.48
1084
6.04
1131
6.61
1174
7.17
—
—
—
—
FAS240
FHS240
6,000
961
3.86
1011
4.31
1058
4.77
1104
5.24
1147
5.71
—
—
7,000
1000
4.79
1050
5.32
1097
5.85
1142
6.38
1184
6.91
—
—
8,000
1041
5.88
1090
6.47
1137
7.07
1181
7.67
—
—
—
—
9,000
1086
7.21
1133
7.82
1178
8.47
—
—
—
—
—
—
10,000
1138
8.83
1180
9.46
—
—
—
—
—
—
—
—
FAS300
7,500
874
5.33
897
5.91
940
6.80
990
7.50
—
—
—
—
8,750
886
5.36
930
6.13
982
7.32
1020
8.10
—
—
—
—
10,000
930
6.60
969
7.20
1007
7.89
1045
8.71
—
—
—
—
11,250
976
8.25
1014
8.86
1051
9.49
1086
10.17
—
—
—
—
12,500
1023
10.20
1061
10.88
1097
11.56
—
—
—
—
—
—
FAS336
9,000
881
5.37
923
6.03
967
6.89
1020
8.25
—
—
—
—
10,500
930
6.97
970
7.55
1008
8.17
1045
8.86
—
—
—
—
12,000
981
9.02
1021
9.67
—
—
—
—
—
—
—
—
13,500
1035
11.45
—
—
—
—
—
—
—
—
—
—
15,000
—
—
—
—
—
—
—
—
—
—
—
—
Bhp
—
Brake Horsepower Input to Fan
ESP
—
External
S
tatic Pressure