INSTALLATION INSTRUCTIONS
Gas Furnace: (F/G)9MVE
24
440 01 4401 02
Specifications subject to change without notice.
Figure 26
Suspended Furnace Installation
2
−
in.
(51 mm)
A11155
COMBUSTION
−
AIR PIPE
(SEE VENTING SECTION)
NOTE: Local codes may require a drain pan and condensate trap when a condensing furnace is installed over a finished
ceiling.
Figure 27
Working Platform for Attic Installation
2
−
in.
(51 mm)
L14F019
ROLLOUT PROTECTION REQUIRED
Install 12” x 22” (305 x 559 mm) sheet
metal in front of burner compartment
area.
COMBUSTION
−
AIR PIPE
(SEE VENTING SECTION)
NOTE: Local codes may require a drain pan and condensate trap when a condensing furnace is installed over a finished
ceiling.