International comfort products ENH4X Installation Instructions Manual Download Page 5

484 01 3700 01

5

REFRIGERANT LINES

Refrigerant lines must be configured per local building

codes and the guidelines outlined in the OD units

installation instructions.

NOTE

: The filter dryer should be placed just before the

indoor unit.

Connect Refrigerant Liquid and Suction Lines

For matched and mismatched systems, use line sizes

recommended in outdoor unit Installation Instructions.
The coil can be connected to outdoor units using accessory

refrigerant line sets or field--supplied lines of refrigerant

grade.
See Table 1 for coil connection tube size.

Table 1

COIL CONNECTION TUBE SIZE

inches (mm)

MODEL NUMBER

Liquid

Suction

ENH4X24(C,T)17A

3/8 (10)

5/8 (16)

ENH4X30(C,T)17A

3/8 (10)

3/4 (19)

ENH4X31(C,T)17A

3/8 (10)

3/4 (19)

ENH4X36(C,T)17A

3/8 (10)

3/4 (19)

ENH4X42(C,T)21A

3/8 (10)

7/8 (22)

ENH4X43(C,T)21A

3/8 (10)

7/8 (22)

ENH4X48(C,T)21A

3/8 (10)

7/8 (22)

ENH4X60(C,T)24A

3/8 (10)

7/8 (22)

ENH4X61(C,T)24A

3/8 (10)

7/8 (22)

UNIT DAMAGE HAZARD

Failure to follow this caution may result in product

damage.
To avoid valve damage to the refrigerant control device

while brazing, valves must be wrapped with a

heat--sinking material such as a wet cloth.

CAUTION

!

1. Remove cabinet access door.
2. Remove rubber plugs from coil stubs using a pulling

and twisting motion. Hold coil stubs steady to avoid

bending or distorting.

3. Wrap TXV and nearby tubing with a heat--sinking

material such as a wet cloth.

4. Fit refrigerant lines into coil stubs. Wrap a heat sinking

material such as a wet cloth behind braze joints.

5. Use 1/2 psig Nitrogen purge in the suction and out the

liquid line.

6. Braze using a Sil--Fos or Phos--copper alloy. Do not use

soft solder.

7. After brazing, allow joints to cool. Slide rubber grommets

over joints. Position tubing at center of each grommet to

ensure an air seal around the tube.

8. Always evacuate lines and reclaim refrigerant when

making connections or flaring refrigerant lines. Leak

check connections before insulating entire suction line.

9. If outdoor equipment will not be installed until a later

date, braze liquid and suction lines closed outside. Add

a Schraeder port test fitting to the suction line outside.

CONDENSATE DRAIN LINE CONNECTION

PROPERTY DAMAGE HAZARD

Failure to follow this caution may result in property

damage.
When installing over a finished ceiling and/or living area,

install a field--fabricated secondary condensate pan

under the entire unit.

CAUTION

!

The coil is designed to dispose of accumulated water

through built--in condensate drain fittings. It is recommended

that PVC fittings be used on the condensate pan. Do not

over--tighten. Finger tighten plus 1--1/2 turns. Be sure to

install plastic plug in unused condensate drain fitting. Two

3/4 inch female threaded pipe connections are provided in

each coil condensate pan.
A trap is not necessary on the condensate line. Consult

local codes for additional restrictions or precautions. If local

codes require a trap then the following guidelines are

suggested to assure proper drainage. Install a trap in

condensate line of coil as close to the coil as possible. Make

trap at least 3 inches (76 mm) deep and no higher than the

bottom of unit condensate drain opening (See Figure 9).

Pitch condensate line 1 inch (25.4 mm) for every 10 feet

(3m) of length to an open drain or sump. Make sure that the

outlet of each trap is below its connection to condensate

pan to prevent condensate from overflowing the drain pan.

Prime all traps, test for leaks, and insulate traps and lines if

located above a living area.

3” / 76mm

A08067

Figure 9 -- Condensate Trap

NOTE

: If unit is located in or above a living space, where

damage may result from condensate overflow, a
field--supplied, external condensate pan should be installed
underneath the entire unit, and a secondary condensate line
(with appropriate trap) should be run from the unit into the
pan. Any condensate in this external condensate pan
should be drained to a noticeable place. As an alternative to
using an external condensate pan, some localities may
allow the running of a separate 3/4 inch (19 mm)
condensate line (with appropriate trap) per local code to a
place where the condensate will be noticeable. The owner
of the structure must be informed that when condensate
flows from secondary drain or external condensate pan, the
unit requires servicing or water damage will occur. To further
protect against water damage, install a float switch to shut
the unit off if the water in the secondary pan gets too high.

NOTE

: To avoid drainage problems, test the primary drain

line by slowly pouring water into the pan. Check piping for

Summary of Contents for ENH4X

Page 1: ...itions of the Canadian Electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe ...

Page 2: ...ler Plate A08065 Figure 2 Horizontal Left Installation with Filler Plate Coil Ductwork Airflow Furnace Furnace Coil Ductwork Airflow Filler Plate Coil Ductwork Airflow Furnace Filler Plate Filler Plate A08066 Figure 3 Horizontal Right Installation with Filler Plate Airflow Airflow amount and distribution are vital to adequate system performance In addition heat pump applications require airflow in...

Page 3: ...e application There should not be any gaps between the plastic condensate pan and the pan extension All condensate should flow from the pan extension to the plastic condensate pan and not leak into the coil cabinet or duct NOTE Discard the pan not used along with both shipping brackets 2 For horizontal left installation install pan extension onto left end of horizontal condensate pan Pan extension...

Page 4: ... to four corners of coil casing see Figure 8 3 Use a minimum of two screws per corner to attach plumbers strap to casing 4 Position and secure coil in front of furnace discharge end 5 Make sure coil is level for proper condensate drainage 6 Using appropriate fasteners for duct type connect supply air duct to coil HORIZONTAL CRAWL SPACE INSTALLATION As an alternate to horizontal attic installation ...

Page 5: ...D Failure to follow this caution may result in property damage When installing over a finished ceiling and or living area install a field fabricated secondary condensate pan under the entire unit CAUTION The coil is designed to dispose of accumulated water through built in condensate drain fittings It is recommended that PVC fittings be used on the condensate pan Do not over tighten Finger tighten...

Page 6: ...nged period of time condensation can form on the bottom of pan and drip WASTE LINE CONNECTION If the condensate line is to be connected to a waste sewer line an open trap must be installed ahead of the waste line to prevent escape of sewer gases See Fig 10 A10216 Figure 10 Condensate Drain to Waste Line EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death Provid...

Page 7: ... P Piston X TXV METERING DEVICE 18 18 000 BTUH 1 tons 19 18 000 BTUH 1 tons 24 24 000 BTUH 2 tons 30 30 000 BTUH 2 tons 31 30 000 BTUH 2 tons 36 36 000 BTUH 3 tons 37 36 000 BTUH 3 tons 42 42 000 BTUH 3 tons 43 42 000 BTUH 3 tons 48 48 000 BTUH 4 tons 60 60 000 BTUH 5 tons 61 60 000 BTUH 5 tons NOMINAL CAPACITY C Plain Copper L Aluminum T Tin Coated Copper HAIRPIN MATERIAL 14 14 3 16 17 17 1 2 21 ...

Reviews: