ELECTRICAL CONNECTIONS
1. Remove the installation bearer of the sensing device (see Fig. 25).
Installation bearer
of sensing device
A150713
Fig. 25
-
Remove installation bearer
2. Remove the Electrical Cover.
3. Connect wiring from the outdoor unit per the connection
diagram (see Fig. 27).
4. Reinstall the Electrical Cover and sensing device bearer.
CONDENSATE DRAIN CONNECTION
The unit is supplied with a drain connection to connect the drain piping.
When installing condensate piping, follow these recommendations:
S
Condensate piping should slope downward in the direction of
the condensate flow, with a minimum gradient of 1 in. per 100
inches.
S
When multiple units are connected to a common condensate
drain, ensure the drain is large enough to accommodate the
volume of condensate from all units. It is also recommended to
place an air vent in the condensate piping to prevent any air
locks.
S
Condensate piping must not be installed where it may be
exposed to freezing temperatures.
1.5m~2m
Insulating
material
Downward declivity
lower than 1
/
100
Bend
S shape
VP30
Downward angle
lower than 1
/
100
Put as deep as possible
(about 10cm)
Fig. 26
-
Condensate Flow