International comfort products DLFLFA Installation Instructions Manual Download Page 10

10

 32801000401

Specifications  subject to change without notice.

Fig. 19

 - 

Wall mount installation

Interconnecting Piping

Flare Connection

1.  Cut the pipe with a pipe cutter at 90 degrees.

90

Slanted   crude     burr

Fig. 20

 - 

Cut the pipe

2. Remove all the burrs from the cut cross section of the pipe

avoiding any burrs inside the tubes.

3. Remove the flare nuts attached to the indoor and outdoor units.

4. Insert a flare nut into a pipe and flare the pipe. Refer to Table 4

for specifications.

Table 4—Specifications

OUTER DIAM. IN. (MM)

A Dimension IN.(MM)

MAX.

MIN.

Ø

1

/4” 

(6.35)

0.05 (1.3)

0.03 (0.7)

Ø

3

/

8

” 

(9.52)

0.06 (1.6)

0.04 (1.0)

Ø

1

/

2

” 

(12.7)

0.07 (1.8)

0.04 (1.0)

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

Fig. 21

 - 

Clamp Handle

5. Apply a small amount of refrigerant oil to the flare connection

on the tubing.

6. Align the center of the pipes.

Indoor unit tubing

Flare nut

Pipings

Fig. 22

 - 

Align the pipe center

7. Connect both liquid and gas pipings to the indoor unit.

8. Tighten the flare nut using a Torque wrench as specified in the

Table 5.

Table 5—Tightening

PIPE DIAMETER INCH (mm)

TIGHTENING TORQUE

Ft-lb

N - m

1/4 (6.35)

10 to 13

13.6 to 17.6

3/8 (9.52)

24 to 31

32.5 to 42.0

1/2 (12.7)

37 to 46

50.1 to 62.3

5/8 (15.88)

50 to 60

67.7 to 81.3

A150712

Fig. 23

 - 

Tighten

Fig. 24

 - 

Flare nut and copper tube

Summary of Contents for DLFLFA

Page 1: ...stallation TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST CONSOLE 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 CLEARANCES 7 INSTALLATION LOCATION REQUIREMENTS 8 INDOOR UNIT INSTALLATION CO...

Page 2: ...ntifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practi...

Page 3: ...louver at air outlet Air inlet with air filter inside INDOOR UNIT 6 Drain pipe Fig 2 Parts List Console Sizes 18 58 Note If the outdoor unit is higher than the indoor unit prevent rain from flowing i...

Page 4: ...insulation rating power communication wiring from the outdoor unit to indoor unit consists of four 4 wires and provides the power for the indoor unit Two wires are line voltage AC power one is communi...

Page 5: ...ice DIMENSIONS 0 63 16 Drain pipe 7 68 195 Hanging arm Unit in mm 27 56 700 23 62 600 8 27 210 Fig 3 Dimensions Table 2 Indoor Unit Console Dimensions UNIT SIZE 12 Depth in mm 8 27 210 Width in mm 27...

Page 6: ...204mm 8 7in 222mm 8 6in 220mm Fig 4 Dimensions Table 3 Indoor Unit Floor Ceiling Dimensions UNIT SIZE 18K 24K 36K 48K 60K Height in mm 9 25 235 9 25 235 9 25 235 9 25 235 9 25 235 Width in mm 42 05 1...

Page 7: ...32801000401 7 Specifications subject to change without notice CLEARANCES Fig 5 Indoor Unit Clearance Console...

Page 8: ...ft the unit and mount it on the hooks Be sure the hooks are on the correct mounting locations on the back of the unit see Fig 7 Washer Tapping screw Hook 6mm Fig 7 Hang the indoor unit DRILL A HOLE IN...

Page 9: ...e the roof beam to avoid any vibration DRILL A HOLE IN THE WALL FOR THE INTERCONNECTING PIPING DRAIN AND WIRING 1 For maximum serviceability it is recommended that you have the refrigerant line flare...

Page 10: ...MAX MIN 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 Bar Copper pipe Clamp handle Red arrow mark Cone Yoke Handle Bar Fig 21 Clamp Handle 5 Apply a small amount of...

Page 11: ...hen installing condensate piping follow these recommendations S Condensate piping should slope downward in the direction of the condensate flow with a minimum gradient of 1 in per 100 inches S When mu...

Page 12: ...Load Amps CONNECTION DIAGRAM Fig 27 Connection Diagram Notes 1 Do not use thermostat wire for any connection between indoor and outdoor units 2 All connections between indoor and outdoor units must b...

Page 13: ...itioner from being activated for approximately 3 to 4 minutes 2 Press MODE and select COOLING HEATING FAN mode to check if all functions work correctly 3 To run the test using the manual button in the...

Page 14: ...short circuit 7 times X EC Refrigerant leakage detection 8 times X EE Water level alarm malfunction 1 time O F0 Current overload protection 2 times O F1 Open circuit or short circuit of outdoor ambien...

Reviews: