Circulation Air Blower Data - *9MVX100
Cooling Adjustment
Heating Rise Adjustment
DIP Switch
(OFF = 0
ON = 1)
High Cool @ .50
in wc(125 Pa)
Low Cool (80%
of High Cool)
** Adjust
Jumper
Setting
DIP Switch
(OFF = 0
ON = 1)
High Heat
Rise
Change @
0.20 in wc
(50 Pa)
Low Heat
Rise
Change at
Resultant
Static
5 & 6
CFM
L/s
CFM
L/s
3 & 4
00
2108
995
1686
995
+
00
--3
--3
*00
1974
932
1579
932
*NOM
*00
0
0
00
1812
855
1450
855
--
00
4
5
01
1712
808
1370
808
+
01
1
1
01
1587
749
1270
749
NOM
01
4
5
01
1422
671
1138
671
--
01
9
10
10
1312
619
1050
619
+
10
--2
--1
10
1197
565
958
565
NOM
10
1
2
10
1056
498
845
498
--
10
5
7
11
919
434
735
434
+
11
--5
--6
11
797
376
638
376
NOM
11
--3
--3
11
641
303
513
303
--
11
2
2
Airflow performance includes 1” washable filter media.
*Factory Setting
**Adjust Jumper Setting (+, NOM, --) is applied to both Cooling and Heating
Note 1: HP Mode Jumper provides a 10% reduction in airflow when in Comfort position and a call for low or high cooling is
present with the ”O” line off. This feature is to provide lower airflow for running in HP Heating Mode if desirable.
Note 2: DEHUM mode (24VAC on DEHUM terminal) provides a 20% airflow reduction during cooling calls.
Note 3: Low Heat ESP is a result of High Heat ESP (-- is decrease in rise).
Note 4: High and low heat rise values are approximate air temperature change from return air temperature when at factory
default settings.
Table 2
Airflow
DIP Switch
(OFF = 0 / ON = 1)
Continuous Fan @
0.10 in wc (25 Pa) ESP
1 & 2
CFM
L/s
*00
1032
487
01
1778
839
10
2178
1028
11
2178
1028
* Factory Setting
Table 3
SW2 DIP Assignments
DIP Switch
Blower Parameter
1 & 2
Cont Fan Adj
3 & 4
Heat Speed Adj
5 & 6
Cool Speed Adj
7 & 8
Cool On/Off Delay
Table 4
Cooling Delay Options (SW2 -- 7, 8)
ON DELAY
OFF DELAY
DIP SW2 -- 7/8
(OFF = 0 / ON = 1)
Timed ON (sec)
Airflow during on
delay
Timer OFF (sec)
Airflow during off
delay
*00
5
OFF
90
100%
01
5
OFF
0
OFF
10
30
50%
30
100%
11
30
50%
180
50%
Airflow % is of High Cool airflow demand determined from SW2--5/6 Table 1
Airflow resumes to 100% after on delay time is completed
Airflow stops (or switches to continuous fan speed) after off delay time is completed
* Factory Setting
MAX CFM (L/s) for Factory Washable Fil-
ters
Filter Size (in/mm)
CFM
L/s
14
″
X 25
″
(356 x 635)
1400
661
16
″
X 25
″
(406 x 635)
1600
755
20
″
X 25
″
(508 x 635)
2000
944
24
″
X 25
″
(610 x 635)
2500
1180
Max CFM (L/s) based on 600 FPM (3.0 m/s)
NOTE: Disposable filters are typically rated at 300 FPM (1.5 m/s).
These filters only allow half the airflow when compared to 600 FPM
(3.0 m/s) filters.