International comfort products *9MPD User Manual Download Page 5

User’s Information Manual

5

441 02 2001 06

Thermostat

There are many types and styles of thermostats. Most thermostats

control both heating and cooling functions and have a Fan Switch

with

AUTO

and

ON

settings. On

AUTO

, the Circulating Air Blower

will cycle on/off with the unit, on the heating speed unless a call for

cooling is initiated. Blower speed will correspond to the mode of

operation of the unit. If the Fan Switch is positioned to

ON

the blow-

er will run continuously.

In addition some thermostats are programmable with multiple set

backs. The set backs can be pre--programmed to lower or raise the

temperature automatically.

Be sure to become familiar with your thermostat.

Rating Plate

The rating plate contains important information for the service

technician and lists the complete model, manufacturing and serial

numbers. You should always provide all these numbers when re-

questing parts or if you need service. See

Figure 2 or Figure 3

for

rating plate location.

Door Interlock Switch

All the electrical power for the unit goes through the door interlock

switch. The interlock switch interrupts electrical power to the unit

when the blower door is removed. The unit will not operate until the

blower door is reinstalled.

Fan Control

The fan/delay control provides power to the circulating air blower

to keep it on until the unit cools down.

The fan off setting can be adjusted if the fan remains on long

enough that cool drafts are felt in the room after the furnace shuts

off.

The delay is set by moving a set of switches on the control. The

Wiring Diagram located on the inside of the blower door shows the

various delay combinations. Refer to

Figure 2 or Figure 3

for

location of the control.

If you are unsure how to set the Fan Control, contact a Qualified

Service Technician.

Electronic Ignition Module/Gas Valve

When the thermostat calls for heat it completes a circuit to the elec-

tronic ignition module. The module sends an electrical signal

which ignites the pilot, then opens the gas valve.

When the flame is firmly established the ignitor goes off. If there is

a malfunction, the gas valve automatically shuts off the gas.

Pressure Switches

The unit is equipped with one or two pressure switches that shut

down the unit under various flue conditions. The switches are con-

nected to the furnace by factory supplied tubing.

Circulating Air Blower

Rating Plate

Gas Valve/Ignition
Module

D

oor Interlock Switch

Pressure Switches

(some models have one)

Component Locations for Four Position Furnaces 90+ Furnaces

Fan/Delay Control

Furnace Vent Pipe

(Vent Pipe Connection through

Side Panel on Some Models)

Combustion Air Blower

Vent Pipe Grommet

Primary Heat Exchanger

Secondary Heat

Exchanger

Figure 2

dwg 25--23--9a

Diagnostic Light

Manual Gas Valve

Vent Drain Fitting

3

/

4

²²²²

OD Transition Box Drain Hose

5

/

8

²²²²

OD Vent Pipe Drain Hose

Plastic Transition Box

Air Intake Pipe

(Dual Certified or Direct

Vent furnaces)

Condensate Trap

D C Motor Control

(some models)

Representative drawing only, some models may vary in appearance.

Summary of Contents for *9MPD

Page 1: ...you cannot reach your gas supplier call the fire department Installation and service must be per formed by a qualified installer service agency or the gas supplier Printed in U S A LP1 6 1 2002 441 02 2001 07 Fire or explosion hazard Information in this manual MUST be followed exactly Failure to follow the information in this manual exactly could result in death bodily injury and or property damag...

Page 2: ...als The signal word WARNING is used throughout this manual in the following manner WARNING The signal word CAUTION is used throughout this manual in the following manner CAUTION Product Labeling Signal words are used in combination with colors and or pic tures on product labels Following are examples of product la bels with explanations of the colors used Danger Label White lettering on a black ba...

Page 3: ...the sig nals are noticed perform a combustion air check as shown on page 4 or call a service technician If you add weather stripping storm windows insulation an additional fuel burning appliance or remodel the structure a combustion air check MUST be accomplished after the addition 6 Maintain safety and service clearances from the unit These are listed on Unit Clearance Label on the cabinet Keep t...

Page 4: ...ops do not use exhaust fans until you can sup ply fresh air by a permanent duct Circuit breakers for fans should be turned off 4 Spillage means air starvation and a fresh air duct or air in takes must be installed to provide air directly to the area around the unit These MUST comply with local and state building codes or in their absence with the National Fuel Gas Code NFPA 54 ANSI Z223 1 Current ...

Page 5: ...nough that cool drafts are felt in the room after the furnace shuts off The delay is set by moving a set of switches on the control The Wiring Diagram located on the inside of the blower door shows the various delay combinations Refer to Figure 2 or Figure 3 for location of the control If you are unsure how to set the Fan Control contact a Qualified Service Technician Electronic Ignition Module Ga...

Page 6: ...n front of the unit Removing the panel will expose the gas con trol switch 5 Slide the gas control switch to OFF See Figure 4 6 Wait five 5 minutes to clear out any gas If you then smell gas STOP Follow the safety information on the cover of this manual If you do not smell gas go to the next step 7 Slide the control switch to ON 8 Reinstall all access panels 9 Turn ON all electrical power to the u...

Page 7: ...es If your unit remains shut off during cold weather the water pipes could freeze and burst resulting in serious water damage If the structure will be unattended during cold weather you should take these precautions 1 Turn off main supply water into the structure and drain the water lines if possible Open faucets in appropriate areas 2 Have someone check the structure frequently during cold weathe...

Page 8: ...ow and filtering A disposable low velocity filter can be replaced with a washable high velocity type Do not replace a high velocity filter with a disposable low ve locity filter Filter Replacement Optional Filter Rack Upflow The filterrack maybe installedin thebottomofthe blowercompart ment or on the outside on either side of the unit A plastic end cap is inserted in the filter rack after the filt...

Page 9: ...ize Heating Input Nominal Air Flow Cubic Feet Recommended Filter Sizes Sq In Surface Area Nominal Size inches Heating Input 1000 x Btuh Cubic Feet per Minute CFM Disposable Filters Cleanable Filters 40 50 800 900 500 or 20 x 25 350 or 14 x 25 40 50 75 and 100 900 1100 600 or 20 x 30 350 or 14 x 25 40 50 75 and 100 1100 1300 350 or 14 x 25 2Req 350 or 14 x 25 75 80 100 and 125 1300 1500 400 or 16 x...

Page 10: ...visible part of the burners and igniter Check for loose soot and give particular attention to obvious deterioration from corrosion or other sources If soot or deterioration is found inside the unit DO NOT OPERATE UNIT call a qualified service technician Lubrication The blower motor and the combustion air blower are prelubricated by the manufacturer and DO NOT require oiling Service Technician Chec...

Page 11: ...efractory chambers oil nozzles refrigerant refrigerant inspection and refrigerant reclaiming freight and or handling charges associated with any repair or replacement and such charges will be your responsibility To establish the installation date for any purpose under this LimitedWarranty youmust retainthe originalrecords thatcan establishthe installationdate ofyour unit Ifyoudonotprovidesuchdocum...

Page 12: ...odel Units HAC0 HAC2 HAC4 CAC0 CAC2 CAC4 KAC0 TCA0 TCA2 TCA4 HHP0 HHP2 HHP4 CHP0 CHP2 CHP4 TCH0 TCH2 TCH4 PGME PYMC PGK GPK PHAD PGAD PA95 PAPC PAK APK To the original purchaser a replacement for 10 years from original date of installation only if theunit is installed withfactory matchedcoils exceptair conditioner condensing units with anominal SEER of 10may bematchedwithevaporator coils ofthe sam...

Reviews: