OPERATION

TO SET FILTER PUMP TIME SWITCH, follow 

instructions on the right. The length of the daily filtration/ 

heating cycle depends on many variables such as size, shape, 

geographic location of the pool, water chemistry, type of 

pool equipment, usage and season of year. If not sure, 

contact your local pool service professional for advice.

THE FIREMAN SWITCH (Heater Protection Mechanism), 

if required, is factory set and shuts OFF the heater 20 

minutes before the Time Switch turns OFF the filter pump. 

The Fireman Switch requires no setting or service.

3

TIME SWITCH OPERATING 

INSTRUCTIONS

1. TO SET “ON” AND 

“OFF” TIMES: Hold    

TRIPPERS against edge 

of CLOCK-DIAL, 

pointing      to time (AM 

or PM) when ON and 

OFF operations     are 

desired. Tighten tripper 

screws firmly.

2. TO SET TIME-OF-DAY: 

Pull CLOCK-DIAL outward. Turn in either direction 

and align the exact time-of-day on the CLOCK-DIAL 

(the time now, when switch is being put into operation) 

to the pointer.

•  TO OPERATE SWITCH MANUALLY: Move 

  MANUAL LEVER below CLOCK-DIAL left or 

  right as indicated by arrows. This will not affect 

  the next operation.

•  FOR MORE THAN ONE DAILY ON-OFF 

  OPERATION: Place additional tripper pairs on 

  CLOCK-DIAL (order 156T1978A).

•  IN CASE OF POWER FAILURE: Reset CLOCK-

  DIAL to proper time of day. See step 2 above.

TROUBLESHOOTING

SYMPTOM

1. Time Switch will not keep

  time but dial is turning.

2. Time Switch Dial stops

  at ON or OFF tripper.

3. Dial stops after switch 

  turns OFF.

4. Load is ON at all times -

  dial is turning.

5. Dead clock motor. (Clock

  motor gears do not rotate).

CAUSE(S)

1a. Frequent power outages

1b. Wrong voltage/cycle

1c. Loose clock motor connections

2a. Loose tripper

2b. Bent dial

2c. Defective motor

3a. LINE leads are connected 

  to LOAD terminals

4a. Welded contacts

4b. Two ON trippers and 

  no OFF tripper on dial

4c. Defective mechanism

5a. Defective clock motor

 

(open coil due to lightning or surge)

5b. Loose clock motor connections

5c. Wrong voltage

CORRECTIVE ACTION

Reset dial

Change clock motor

Check connections

Check/change tripper

Check/change mechanism

Change clock motor

Reverse LINE and LOAD 

connections

Change mechanism

Change tripper

Change mechanism

Change clock motor

Check connections

Change clock motor

Figure 2