background image

GGEENNEERRAALL

This document provides detailed information on how to install and operate the SG Modular
Series 
of Surge Protective Devices (SPD).

Units should be mounted as close as possible to the AC panel to be protected.  It is recom-
mended that conduit, preferably metallic, be utilized to accomplish this connection.

The SG Modular Series Protectors are installed and connected in parallel ("shunt") across the
AC supply to be protected.  Connecting wires do not carry the supply current, only the short
duration currents associated with the suppression of a transient event.

Identified or indicated terminals must be connected exactly with respect to the AC Power
feeding the SPD.  Failure to do so may result in damage to the device or pose a danger to
personnel.

Incorrect installation may significantly impair the performance of the Surge Protective
Device.  It is particularly  important that all installation procedures and guidelines be followed
exactly.

INSTALLATION OF THIS DEVICE SHOULD ONLY BE PERFORMED BY A
QUALIFIED LICENSED ELECTRICIAN.

Before starting any installation procedures, verify service voltages with an AC Voltmeter to
ensure that the correct SPD Model has been selected.

D

O NOT CONNECT WITHOUT SECURING POWER FROM THE DISTRIBUTION PANEL

.

C

HECK TO ENSURE THAT ALL CONNECTIONS ARE CORRECT AND SECURE BEFORE ENERGIZING

.  D

O

NOT ENERGIZE WITH DOOR OPEN

.

K

EEP THIS MANUAL IN A SAFE DRY PLACE FOR FUTURE REFERENCE

.

A.)

B.)

C.)

D.)

E.)

F.)

G.)

H.)

I.)

J.)

After determining a position to mount the device that
will minimize the length of the connecting  wires,
drill a hole in the cabinet for the conduit to run the
wires from the distribution panel to the connecting
lugs inside the SPD.  Installation is simplified if the
wires enter the enclosure at the top (see figure #2) of
the enclosure.  Securely mount the TVSS unit using
1/4-20 bolts in the four (4) mounting holes provided
in the enclosure's mounting flanges.   

CONSTRUCTION

14 Gauge steel with continuous hinge.
UL 50 Type 12 and Type 13.
NEMA/EEMAC Type 12 and Type 13.
JIC standard #GP-1-1967.
CSA Type 12.
IEC 529, IP65.

[Figure #2:  Cabinet Top View]

[Figure #1:  Cabinet Front View]

10.00"

(254mm)

14.75"

(375mm)

15.50"

(394mm)

12.94"

(329mm)

3.00"

(76mm)

6"

(152mm)

MMOOUUNNTTIINNGG IINNFFOORRMMAATTIIOONN

((AALLLL MMOODDUULLAARR SSGG MMOODDEELLSS))

Page:  2

FINISH

ANSI 61 Gray polyester.
Powder coating inside and
out over phosphatized sufaces.

1.030"

(26.162mm) Dia.

APPLICATION or TECHNICAL ASSISTANCE

Contact Intermatic at 1-800-391-4555 or on the web at www.intermatic.com

Summary of Contents for SG160

Page 1: ...R R LISTED LISTED TRANSIENT SURGE SUPPRESSORS FOR AC POWER PANEL APPLICATIONS USER MANUAL 1449 2nd Edition HARDWIRED SURGE PROTECTION DEVICES SG Modular Series...

Page 2: ...rrect SPD Model has been selected DO NOT CONNECT WITHOUT SECURING POWER FROM THE DISTRIBUTION PANEL CHECK TO ENSURE THAT ALL CONNECTIONS ARE CORRECT AND SECURE BEFORE ENERGIZING DO NOT ENERGIZE WITH D...

Page 3: ...a 2 Pole Breaker Requires a 3 Pole Breaker 120 240Vac Split Phase 3 Wire Ground PHASE A NEUTRAL GND 120 VAC 120 VAC PHASE B 120 or 240 VAC PHASE NEUTRAL GND PHASE A NEUTRAL GND PHASE B PHASE C 120 or...

Page 4: ...FAULT N G VOLTAGES RESET ENABLE TEST EVENT COUNTER TEST DISABLE ENABLE STATUS INDICATORS AUDIO ALARM Figure 10 3 Phase Wye Configuration Shown 1 For Single Phase Models Only 1 Green LED in the Phase...

Page 5: ...suppressor encounters Control of the Surge Counter is managed with a switch located to the left of the count er display The switch has three 3 settings Up momentary only for RESET Center this is the E...

Page 6: ...160kA 240kA 320kA Phase C RPM SURGE RATING 160kA 240kA 320kA Phase B RPM SURGE RATING 160kA 240kA 320kA B SENSOR CABLE Figure 11 Internal Layout INTERNAL LAYOUT 1 Make Sure the power has been turned o...

Page 7: ...ENANCE INSTRUCTIONS At intervals not to exceed two 2 months check and verify 1 Diagnostic and Indication display 2 Alarm Operation 3 Condition of ALL Connection Cables and Terminations ANY ALTERATIONS...

Page 8: ...not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state This warranty service is available by either a returning the product t...