background image

158PG1

1953

ITEM

PT

. NO.

DESC.

QUAN.

DR.:   SRB   1/25/2005      

INTERMA

TIC INCORPORA

TED

CHKD.:  RM 1/25/2005

SCALE:

NAME:     

INST SHT -  PG60-PG80-PG100 SERIES     

APPROVED

MA

TL.:     

WHITE P

APER ST

OCK

2    

REVISE DR

WG TO ALIGN TEXT (NO

ECO)

SRB

3/2/2005

2-RM 3/2/2005

FINISH:    

BLACK PRINTING INK

1      RELEASED  T

O ELEC. DA

T

A

HEA

T TREA

T

:

LET

.    REVISION

SIGN.

MODEL

SUPERSEDES:

NOTES:

ALL

PRINTING T

O BE 

AS PER INTERMA

TIC

APPROVED ARTWORK.

FRA .010 . DECIMALS 

AS SPECIFIED - 

1/2˚

ALL

DIMENSIONS MUST

BE MET

BEFORE PLA

TING.

DIM       

:

TO

L

11

8.

5

SEE B/M FOR 

ALL

P

ART NUMBERS & QUANTITIES

FRONT

BACK

FOLD LINES

INSTALLA

TION INSTRUCTIONS

and

OPERATIONS MANUAL

PanelGuard

®

PG60 - PG80 - PG100 Series

Electrical Panel Extension Hardwired Surge

ALARM

OPERA

TION

PROTECTIO

N MODES

CAUTION

; HIGH V

OLT

AGE INS

IDE

SEVICE BY

 QUALIFIED

 PERSONN

EL ONL

Y

Red ALARM 

light ON or 

Audible Alarm 

ON 

indicate

loss 

of prote

ction. 

 Re

fer to 

the operatio

n manual for

 

troubleshoo

ting help.

Alarm

Neutral

L1

L2

L3

L1

L2

L3

Ground

Green lights

 ON indicat

power prese

nt and prote

c- 

tion circuits

 for each mo

de 

are operatin

g propely

One or more

 Green ligh

ts 

OFF indica

tes loss of 

power 

or protection

. Refer to th

operation m

anual for 

troubleshoo

ting help.

INTRODUCTION

The PG60-80-100 Series is designed to be installed in very close prox-

imity to the power bus of an electric distribution panel or electric panel-

board.   It can be used with most panels or panelboards in distribution

today.  

The PG60-80-100 Series offers peak surge amperage protection

levels of 60 kAto 100 kA

per mode.  It is designed to be easily mounted

above or below the panelboard.  Provisions have been made with a

reversible cover plate to keep the instructions and indicators in a user

friendly position.  Standard features include all mode protection,  multi-

mode LED indicators that show full protection, diminished protection and

lost protection for all phases. A

form C relay for remote alarm indication,

audible trouble alarm with test and silence switch are also standard

equipment. 

The system is comprised of three sections; outer housing, cover plate

and inner module.  Each section is engineered to make the installer/ser-

vice technician's task as easy as possible.  A

description of each section

and the function follows.

Outer Housing - Metal housing measuring 20" wide x 16" high x 6"

deep. The outer housing contains the inner housing. connection lugs for

each phase, neutral and ground, connections for the form C alarm relay

and the audible alarm test and silence switch.  

A5/8" flange on the forward side of the housing has ten (10) threaded

holes that are used to attached the cover plate.  Four (4) mounting holes

are located in the back surface of the housing for mounting.  It is sug-

gested that all four (4) fasteners be used to secure the outer housing.

Cover Plate - Metal plate measuring 19 13/16" wide x 15 13/16" high.

The cover plate contains ten (10) holes located around the edges that

matched the threaded holes in the outer housing and are used to secure

the cover plate to the outer housing.  The cover plate is reversible and

has an identification label on both front and reverse sides. The labels

are mirror images of each other and selection of which side to use

depends upon the placement of the outer housing. (This process will be

explained in the installation section that follows.)

Inner Module - Metal box measuring 13 3/16" wide x 9 3/4" high x 4

15/16" deep including the mounting rails that are part of the module.

The inner module is fastened to the outer housing with four (4) bolts

through the mounting rails.  Module identification and wiring diagram

labels are attached to the inner module.  The inner module contains all

of the surge suppression, noise filtering, fusing, monitoring and reporting

components.  Copper bus bars and terminal lugs extend from the inner

module.  

NEC Section 285 requires that a SPD have a fault current rating equal

to or greater than the point of installation (switchboard or panelboard).

The PG60-80-100 Series is suitable for use on a circuit capable of deliv-

ering not more than 200,000 amperes (120/208-3Y , 120/240-2S,

120/240-3HLD, 277/480-3Ymodels).  480-3D models are rated at

25,000 amperes.  Should you require a 480-3D model with a higher fault

current rating consider Intermatic PG2500/PG3000/PG3500 Series

which are rated at 200 kAIC.

S

UPPLY

V

OLTAGE

AND

 C

ONFIGURATION

240-2S

120/240 Single Phase 

208-3Y

120/208 Three Phase W

ye 

240-3HLD

120/240 Three Phase H. L. Delta 

480-3Y

277/480 Three Phase W

ye 

480-3D

480 Three Phase Delta

P

EAK

 S

URGE

 R

ATING

PG60

60 kA

per Mode

PG80

80 kA

per Mode

PG100

100 kAper Mode

Model #  PG100 - 208 - 3Y

INSTALLA

TION INSTRUCTIONS and OPERATIONS MANUAL

PG60-80-

100 SERIES  -  V .10-03

ALARM

OPERATION

PROTECTION MODES

CAUTION; HIGH VOLT

AGE INSIDE

SEVICE BY QUALIFIED PERSON

NEL ONL

Y

Red ALARM light ON or 

Audible Alarm ON indicates 

loss of protection.  Refer to 

the operation manual for 

troubleshooting help.

Alarm

Neutral

L1

L2

L3

L1

L2

L3

Ground

Green lights ON indicate 

power present and protec- 

tion circuits for each mode 

are operating propely. 

One or more Green lights 

OFF indicates loss of power 

or protection. Refer to the 

operation manual for 

troubleshooting help.

20.0”

6.0”

16.0”

TEN YEAR LIMITED PRODUCT W

ARRANTY

For

Intermatic PG60-80-100 Series

SURGE PROTECTION DEVICES

(1) What Is Covered By This Limited W

arranty

Repair or Replacement of Product

Intermatic Incorporated ("Intermatic") warrants to the original purchaser only, the Intermatic model PG60-240-2S, PG60-208-3Y

,

PG60-240-3HLD, PG60-480-3Y , PG60-480-3DLL, PG80-240-2S, PG80-208-3Y

, PG80-240-3HLD, PG80-480-3Y , PG80-480-3DLL,

PG100-240-2S, PG100-208-3Y , PG100-240-3HLD, PG100-480-3Y

and PG100-480-3DLL,  PanelGuard®

Surge Protection Devices

(each a "Product") shall be free from defects in material or workmanship for a period of ten years (120 months) from date of pur-

chase or 126 months from date of manufacture.  If the purchaser discovers a defect in material or workmanship, the purchaser must

promptly submit a warranty claim.  Upon a determination by Intermatic that the Product is defective, Intermatic shall correct any

defect in material or workmanship by, at Intermatic's option, either repairing or replacing the defective Product.  

Any repair, including

both parts and labor, shall be at Intermatic's expense.  

The foregoing remedies are the purchaser's exclusive remedies for a breach

of warranty.  

For purposes of this Limited Warranty

, a Power T

ransient shall mean over-voltage resulting from momentary voltage spikes or

surges on an AC power line of magnitude that the Product, according to its specifications, is designed to stop before such spikes or

surges affect downstream equipment. 

The Product must be installed in the appropriate application in complete accordance with the installation instructions.  All building

wiring and other connections to the Product must conform to all applicable national, state and local electrical codes; the Product

must not be opened, modified, exposed to extreme heat or cold, submerged or subjected to abnormal use or service.  All products

must be used in accordance with the instructions provided with the Product and the purchaser shall be solely responsible for select-

ing a Product model with specifications appropriate for the equipment to be protected.  Intermatic shall determine, in its sole discre-

tion, whether any Product returned by a purchaser has been used in accordance with its instructions, is an appropriate model for the

purchaser's use thereof, and whether the Product is defective.  

(2) What Is Not Covered By This W

arranty  

Intermatic does not warrant (a) defects in the Product or damage to any equipment caused by the failure to properly install the

Product; (b) damage caused by use of the Product for purposes other than those for which it was designed; (c) damage caused by

disaster such as fire, flood and wind; (d) damage caused by unauthorized attachments or modification of the Product; (e) damage to

the Product occurring during shipment; (f) damage caused by electrical disturbances exceeding published product specifications or

(g) damage to the Product caused by any other abuse or misuse by the purchaser.

(3) Disclaimer of W

arranty

THE FOREGOING WARRANTIES 

ARE IN LIEU OF ALL

OTHER EXPRESSED WARRANTIES.   

TO 

THE EXTENTALLOWED BY

LAW

, ANY

IMPLIED WARRANTIES OF MERCHANT

ABILITYOR FITNESS FOR 

AP

ARTICULAR PURPOSE 

ARE LIMITED IN

DURATION 

TO 

THE DURATION OF 

THIS LIMITED WARRANTY

.

(4) Limitation of Remedies

IN NO CASE SHALLINTERMA

TIC BE LIABLE FOR ANY

SPECIAL, INCIDENTAL, OR CONSEQUENTIAL

DAMAGES BASED

UPON BREACH OF WARRANTY

, BREACH OF CONTRACT , NEGLIGENCE, STRICT T

ORT , OR 

ANYOTHER LEGAL

THEORY

.

SUCH EXCLUDED DAMAGES INCLUDE, BUT ARE NOT LIMITED T

O, DAMAGE TO SOFTW

ARE, LOSS OF DATA, LOSS OF

PROFITS, LOSS OF SAVINGS OR REVENUE, LOSS OF USE OF THE PRODUCT OR 

ANYASSOCIA

TED EQUIPMENT , COST

OF CAPITAL, COST OF 

ANYSUBSTITUTE EQUIPMENT

, FACILITIES OR SER

VICES, DOWNTIME, THE CLAIMS OF THIRD

PARTIES INCLUDING CUST

OMERS, DAMAGE TO PROPERTY

AND PERSONALINJUR

Y .  SOME ST

ATES DO NOT 

ALLOW

LIMITS ON WARRANTIES OR ON REMEDIES FOR BREACH IN CERT

AIN TRANSACTIONS.  IN SUCH STA

TES, THE LIMITS IN

THIS PARAGRAPH 

AND IN PARAGRAPH (3) MA

YNOT 

APPLY.

(5) T

ime Limit for Bringing Suit 

No action arising out of any claimed breach of warranty may be brought more than one year after the cause of action has occurred.

(6) No Other W

arranties  

Unless modified in writing signed by both parties, this agreement is understood to be the complete and exclusive agreement

between the parties, suspending all prior agreements, oral or written, and all other communications between the parties relating to

the subject matter of this aggreement. No employee of Intermatic or any other partyis authorized to make any warranty in addition to

those made in this aggreement.

INTERMATIC INCORPORA

TED

SPRING GROVE, ILLINOIS

http://www.intermatic.com

158PG11953

FINALCHECKOUT PROCEDURE

1.

CHECK all connections for correct location and torque.

2.

Make sure that the electrical panel and the SPD are clear of all tools, metal parts and personnel.

3.

Turn power ON to the electrical panel.

4.

Place Alarm Switch in the NORMAL

position.

5.

Turn the power ON to the SPD.

6.

Check all PROTECTION STA

TUS Line indicator lights for proper illumination.

PROTECTION MODE indicators ON.

ALARM indicator OFF .

7.

Check output continuity for the Alarm Relay if used. 

(a) Common to Normally Open = greater than 10 M ohms, (b) Common to Normally Closed = 0 ohms.

8.

The Audible 

Alarm should be silent.

9.

Place Alarm Switch in SILENCE position: 

Audible alarm should sound. Return Alarm Switch to normal position. 

10.

Place Alarm Switch in 

TESTposition. 

Audible alarm should sound, the Red Alarm Indicator LED should be ON and the alarm relay

outputs should reverse state. Return the switch to the NORMALposition.

OPERATION

1.

The ALARM SWITCH should be in the NORMAL

position for standard operating conditions.

2.

The COVER PLATE must be in position with all bolts secured to prevent access by unauthorized  personnel.

3.

The PROTECTION MODE indicator lights should be ON. 

4.

The ALARM indicator light should be OFF

.

5.

Periodic functional checks of the system as required by local codes or procedures are conducted by performing steps 9 and 10  of

the FINALCHECKOUT

PROCEDURE. 

INSTALLA

TION INSTRUCTIONS and OPERATIONS MANUAL

5

PG60-80-100 SERIES  -  V .10-03

COVER PLATE INST

ALLATION

The cover plate has labels on the front and back.

One side has the labels positioned for use when

the SPD is located at the top of the electrical

panel.  The second side of the cover plate is used

when the SPD is positioned at the bottom of the

electric panel.  MAKE SURE THAT THE PROPER

SIDE IS PLACED FORW

ARD AND 

ALLINDICA

TOR

LIGHTS ARE VISIBLE.

SPD mounted above the Panelboard

1.

Position the cover plate on the face of the outer

housing so that the mounting holes align with the

threaded holes and the indicator light positions in the

label align with the indicator lights in the inner mod-

ule.  

NOTE: In this application, the label with the LED indi-

cators will be at the top of the cover plate.

SPD mounted under the Panelboard

1.

Position the cover plate on the face of the outer

housing so that the mounting holes align with the

threaded holes and the indicator light positions in the

label align with the indicator lights in the inner mod-

ule.  

NOTE: In this application, the label with the LED indi-

cators will be at the bottom of the cover plate.

TECHNICALASSIST

ANCE

For application or technical assistance contact

Intermatic at 1-800-391-4555 or on the web at

www.intermatic.com.

Figure 6

TYPICALINST

ALLATIONS

circuit breaker

Alarm relay

wiring area

Alarm relay

wiring area

Ground bus

Wire pass-

through areas

Wire pass-

through areas

Neutral bus

Neutral bus

Main breaker

Main breaker

INSTALLATION INSTRUCTIONS and OPERATIONS MANUAL

2

PG60-80-

UNPACKING 

Open the carton, remove the PG60 - 100 Series unit and examine the outer housing and cover for shipping damage.  If damage is
observed, notify your supplier.  

Remove the cover plate by removing the ten (10) bolts that secure it and examine the inner housing, bus bars, connecting lugs and
the alarm device for shipping damage.  If damage is observed, notify your supplier.

BEFORE INSTALLATION

1.

All electrical wiring and connections should be installed by a

qualified electrician.  All wiring must comply with the National
Electrical Code (NEC) and local codes.

2.

This Surge Protection Device (SPD) incorporates a NEMA 12

enclosure. 

3.

The installation and operation of any Surge Protection Device

(SPD) requires  proper grounding.  A properly sized, insulated
grounding conductor is required.  The grounding conductor should be
the same wire size (gauge) as the phase and neutral conductors
used for the SPD. Refer to Table 2 for recommendations.

4.

The service entrance and panel grounding configurations must

comply with the National Electrical Code and all local codes.

3.

Select a location opposite the incoming feed to the panelboard.

The SPD must be mounted in an area that provides sufficient work-
ing space around the panelboard and SPD cabinet.

5.

The collar and/or conduit used to connect this SPD to the panel-

board must be sized correctly for the gauge and length of wire
required.  The length of conduit should allow no more than 1/16”
between the edge of the SPD cover plate and the panelboard cover. 

6.

TEST and verify system voltage to assure proper selection of

the Surge Protection Device (SPD) in accordance with the wiring dia-
grams shown below and on the labels located on the inner module.
If the voltage or the number of conductors does not agree with the
information supplied with the Surge Protection Device, contact your
supplier.  If you have questions about the proper use of this unit for
your application, contact Intermatic at the numbers listed under
TECHNICAL ASSISTANCE on page 5 of this publication. 

PG60 - PG80 - PG100 Series

with cover plate removed. Unit in position
to be installed at the top of panelboard.

BUS BARS AND TERMINAL LUGS ARE ENERGIZED

DURING NORMAL OPERATING CONDITIONS. ONLY A

QUALIFIED PERSON SHOULD PERFORM SERVICE.

WARNING

Wire  

Pass-

through 

area

Wire Pass-through area

Low voltage alarm
contact wiring area

AC Voltage wiring area

REAR

FRONT

20.0”

6.0”

9.195”

1.980”

3.438”

3.438”

5.75”

Table 1

INSTALLATION (above panelboard)

1.

Turn OFF and LOCK the electric power supply to the panel-

board. 

2.

SELECT the location where the Surge Protection Device

(SPD) will be mounted, above or below the electric panel.
Position the SPD adjacent to the electric panel with the bus bars
pointed toward the panel.  NOTE: If the SPD is mounted below
the electric panel, the labels on the inner housing will be invert-
ed.  Refer to INVERTED INSTALLATION section below for infor-
mation regarding the inverted installation. Align the SPD to allow
1/16” between the SPD cover plate and the cover of the panel-
board.  The SPD should be secured to a flat vertical surface that
can support the weight of the device.  

3.

Temporarily fasten the SPD to the vertical surface and mark

the location where a hole for the collar or conduit will enter.
Refer to Table 1 for acceptable locations on the bottom of the
Outer Housing that can be drilled for wire entry.  Note that wiring
for the remote monitoring relay enters separate from the AC
power leads.  Remove the SPD unit and drill a hole of sufficient
size to accept the collar or conduit connector. Attach the collar or
connector to the SPD outer cabinet and mount the unit with the
collar or connector inserted into the knockout in the panelboard.

4.

Use the proper gauge wire to connect each of the lugs on

the SPD to the appropriate points on the electric panel.  See
Table 2  for recommended wire and breaker sizes. Use of a ded-
icated circuit breaker is optional since the SPD has integral
overcurrent fusing. The SPD can be connected through feed-
thru lugs on a panelboard.  The SPD can be connected through
a breaker or direct tapped for Switchboard installations. Select a
position for the connection that results in the shortest lead
lengths between the SPD and the power bus.  Leads should be
kept as short as possible to insure optimum operation.  Measure
and cut all leads to proper length. Strip the ends of each lead
9/16" for the SPD terminal lugs and to proper length for the
breaker used. Connect the wire leads to the lugs on the bus
bars of the SPD.  Torque the lugs 35 to 50 inch pounds per UL
486 torque tightening requirements.

NOTE: For safety, observe proper wire marking 
conventions; BLACK for HOT, RED for HOT HIGH 
LEG, WHITE for NEUTRAL, GREEN for GROUND.

5.

Route the wire lead bundle through the collar or connecter

into the electric panel.  

6.

Connect the GROUND (green) lead to the ground bus in

electric panel. 

7.

If used, connect the NEUTRAL (white) to the neutral bus in

the electric panel. If installing at a main electrical panel, the neu-
tral and ground leads could terminate at a common bus bar in
the panel. 

8.

Connect the phase leads to the appropriate breaker in the

electric panel. 

NOTE: For HIGH LEG DELTA, make certain that the  
high leg is connected to the center bus bar position in 
the SPD. (Refer to Figure 3)

9.

Connect wires to the alarm relay leads if used. Alarm wires

should be routed through a hole in the outer housing that is sep-
arate from the power leads. If the alarm relay is not used, leave
the wires in the low voltage section, they will have no power and
do not need to be capped.  Refer to the alarm wiring drawings
on page 3 or on the wiring label on the inner housing for wire
designation. 

10. CHECK all connections for correct torque.

INSTALLATION INSTRUCTIONS and OPERATIONS MANUAL

3

PG60-80-100 SERIES  -  V.10-03

277/480 VAC Three Phase Wye

Figure 4

PG60-480-3Y
PG80-480-3Y
PG100-480-3Y

L1

L2

L3

N

G

Line to Line: 480v.; Line to Neutral: 277v.; Line to Ground: 277v.

120/240 VAC Three Phase
High Leg Delta

Figure 3

PG60-240-3HLD
PG80-240-3HLD
PG100-240-3HLD

L1

L2

L3

N

G

Line to Line: 240v.; Line to Neutral: 120v.; Line to Ground: 120v. 

** High Line to Neutral: 208v.; High Line to Ground: 208v.

**

120/208 VAC Three Phase Wye

Figure 2

PG60-208-3Y
PG80-208-3Y
PG100-208-3Y

L1

L2

L3

N

G

Line to Line: 208v.; Line to Neutral: 120v.; Line to Ground: 120v.

PG60-240-2S
PG80-240-2S
PG100-240-2S

120/240 VAC Single Phase

L1

L2

N

G

Line to Line: 240v.; Line to Neutral: 120v.; Line to Ground: 120v.

Figure 1

480 VAC Three Phase Delta

Figure 5

PG60-480-3DLL
PG80-480-3DLL
PG100-480-3DLL

L1

L2

L3

G

Line to Line: 480v.;  Line to Ground: 480v.

INSTALLATION INSTRUCTIONS and OPERATIONS MANUAL

4

PG60-80-100 SERIES  -  V.10-03

Brown - c

Brown - c

Violet - n/c

Orange - n/o

Orange - n/o

Violet - n/c

Normal operating condition - relay energized

Alarm condition - relay not energized

Figure 6

ALARM RELAY CONNECTIONS

ALARM CONDITIONS

Alarm sounding and relay in "alarm state"
1.

The audible alarm will sound and the alarm relay output

will reverse state upon the loss of one or more protection com-
ponents. 
2.

CAUTION: The following steps should be performed only

by qualified personnel. Remove the ten (10) bolts holding the
cover plate in place.
3.

Move the Alarm Switch to the SILENCE position. The local

audible alarm should silence but the alarm relay output should
remain in the alarm condition until the unit is returned to normal
operating condition.
4.

Verify that the proper voltage is present at each of the ter-

minal lugs.  CAUTION: LINE VOLTAGE MAY BE PRESENT AT
THE TERMINAL LUGS. 
5.

Turn the breaker OFF and then ON to reset the SPD.

6.

If the alarm condition will not clear upon reset and the line

voltages are present and are of the correct value, contact
Intermatic TECHNICAL ASSISTANCE at the number given on
page 5 of this publication.

Alarm not sounding but relay in "alarm state"
1.

The  alarm relay output will change state but the audible

alarm will not sound under the following conditions:

a) Loss of power to the PG Series unit.
b) The circuit breaker in the electric panel that is feeding  

the SPD is turned to the OFF position or tripped.

c) A fault exists in the remote monitor system.

2.

Check for PROTECTION STATUS indicator light illumina-

tion. If all of the Line indicator lights are ON and the Alarm indi-
cator light is OFF, consult directions for trouble shooting the
remote monitoring system.

ALARM RELAY SPECIFICATIONS 

Relay:

Single pole double throw.

Power Rating: 120 VAC - 500 mA

24 VAC - 1 A.

Operation:

Energized during normal conditions.
De-energized during alarm conditions or loss 
of power.

INVERTED INSTALLATION  (under panelboard)

1.

Turn OFF and LOCK the electric power supply to the panelboard. 

2.

SELECT the location where the Surge Protection Device (SPD) will

be mounted below the electric panel.  Position the SPD adjacent to the
electric panel with the bus bars pointed toward the panel.  NOTE: The
labels on the inner housing will be inverted.  Align the SPD to allow
1/16” between the SPD cover Plate and the cover of the panelboard.
The SPD should be secured to a flat vertical surface that can support
the weight of the device.  

3.

Temporarily fasten the SPD to the vertical surface and mark the

location where a hole for the collar or conduit will enter.  Refer to Table
1 for acceptable locations on the bottom of the Outer Housing that can
be drilled for wire entry.  Note that wiring for the remote monitoring relay
enters separate from the AC power leads.  Remove the SPD unit and
drill a hole of sufficient size to accept the collar or conduit connector.
Refer to Table 2 for suggested collar or conduit sizes.  Attach the collar
or connector to the SPD outer cabinet and mount the unit with the collar
or connector inserted into the knockout in the panelboard.

4.

Use the proper gauge wire to connect each of the lugs on the SPD

to the appropriate points on the electric panel.  See Table 2  for recom-
mended wire and breaker sizes. Use of a dedicated circuit breaker is
optional since the SPD has integral overcurrent fusing. The SPD can
be connected through feed-thru lugs on a panelboard.  The SPD can be
connected through a breaker or direct tapped for Switchboard installa-
tions. Select a position for the connection that results in the shortest
lead lengths between the SPD and the power bus.  Leads should be
kept as short as possible to insure optimum operation.  Measure and cut
all leads to proper length. Strip the ends of each lead 9/16" for the SPD
terminal lugs and to proper length for the breaker used. Connect the
wire leads to the lugs on the bus bars of the SPD.  Torque the lugs 35 to
50 inch pounds per UL 486 torque tightening requirements.

NOTE: For safety, observe proper wire marking conventions;
BLACK for HOT, RED for HOT HIGH LEG, WHITE for NEUTRAL,
GREEN for GROUND.

5.

Route the wire lead bundle through the collar or connecter into the

electric panel.  

6.

Connect the GROUND (green) lead to the ground bus in electric

panel. 

7.

If used, connect the NEUTRAL (white) to the neutral bus in the

electric panel. If installing at a main electrical panel, the neutral and
ground leads could terminate at a common bus bar in the panel. 

8.

Connect the phase leads to the appropriate breaker in the electric

panel. 

NOTE: For HIGH LEG DELTA, make certain that the high leg is con-
nected to the center bus bar position in the SPD. (Refer to Figure
3)

9.

Connect wires to the alarm relay leads if used. Alarm wires should

be routed through a hole in the outer housing that is separate from the
power leads. If the alarm relay is not used, leave the wires in the low
voltage section, they will have no power and do not need to be capped.
Refer to the alarm wiring drawings on page 3 or on the wiring label on
the inner housing for wire designation. 

10. CHECK all connections for correct torque.

SUGGESTED WIRE and BREAKER SIZES 

Use the following table as a guideline for the PG60, PG80 and PG100 Surge Protection Devices.  All models have integral overcurrent fusing and

the use of a dedicated circuit breaker is optional.  Lugs accept wire sizes from 10 AWG to 2 AWG.  Keep all leads as short and straight as possi-

ble, avoiding sharp 90 degree bends.  Increase wire size when lead length is extended.

Table 2

10 AWG       30 AMP

8 AWG       40 AMP

6 AWG        50 AMP

4 AWG       60 AMP

2 AWG       80 AMP

  

  

 

 

 

 

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

  

 

Reviews: