Intermatic IOS-CMP-U Installation And Configuration Instructions Download Page 2

ADJUSTING DIP SWITCH SETTINGS

The occupancy sensor features 2 DIP switch settings. Each setting can be set to an up or down position to 

configure the DIP switch setting. Follow these steps to adjust the DIP switch settings.

1.  Adjust the sensitivity level DIP Switch (1). The Up position sets the sensitivity to 50%, while the down position 

  adjusts the sensitivity level to 100%.

 

DIP SWITCH 1 - SENSITIVITY LEVEL SETTINGS

 

50% 

UP position

 

100% 

Down positions

2.  2. Adjust the Vacancy feature DIP Switch (2). 
NOTE: Turn this DIP switch to ON if you have a momentary switch. This enables overrides.

 

DIP SWITCH 2 - VACANCY LEVEL SETTINGS

 

Enable 

UP position

 

Disable 

Down positions

3.  Install the front on the sensor and secure with the screws.

TESTING THE OCCUPANCY SENSORS

1.  Ensure the PIR Activity is enabled, the Red LED flashes, and the PIR Sensitivity is set to MAX (DIP switch 1 OFF). 

2.  Ensure the Time Delay is set for TEST MODE.

3.  Ensure the Light Level is the default (maximum). 

4.  Remain stationary until the lights turn OFF. The Red LED and Load are ON.

5.  Once the lights turn off, move around the coverage area. The lights will illuminate. 

6.  When testing and adjustment is complete, reset DIP Switches and Light Level to the desired settings and replace the cover on the sensor.

    

 

TROUBLESHOOTING

  

 

The PIR activity LED does not flash properly,

 

The warm-up period has not been completed

    

 

Make sure the circuit breaker is on

   

 

 

Set the PIR sensitivity to Max/Autoset (DIP switch 1 OFF)

   

 

 

Check all sensor connections

  There is improper PIR activity, LED flashes 

Make sure the light level adjustment is set properly by covering the PIR lens and PIR activity LED to verify if 

   

 

 

lights turn on. If lights still turn on, adjust the light level.

  The sensor is activating without detecting 

The PIR sensitivity is set too high. Adjust the PIR sensitivity.

  movement. 

 

The sensor is mounted too close to HVAC or VAV vents with heavy air flow. Relocate the sensor.

   

 

 

Set the DIP switch 1 to ON

  

 

158--01285

1 2

ON

1 2

Sensitivit

y

Up Position

Down Position

DIP SWITCH

DIP Switch 

Settings

Settings Chart

Va

canc

y

LIMITED TWO YEAR WARRANTY

If within the warranty period specified, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, at its sole option, free of charge. This warranty is extended to the original 

purchaser only and is not transferable. This warranty does not apply to: (a) damage to units caused by accident, dropping or abuse in handling, acts of God or any negligent use; (b) units which have been subject to 

unauthorized repair, opened, taken apart or otherwise modified; (c) units not used in accordance with instructions; (d) damages exceeding the cost of the product; (e) sealed lamps and/or lamp bulbs, LED’s and 

batteries; (f) the finish on any portion of the product, such as surface and/or weathering, as this is considered normal wear and tear; (g) transit damage, initial installation costs, removal costs, or reinstallation costs.
INTERMATIC INCORPORATED WILL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR 

CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES. ALL IMPLIED 

WARRANTIES, INCLUDING THE WARRANTY OF MERCHANTABILITY AND THE WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY MODIFIED TO EXIST ONLY AS CONTAINED IN THIS 

LIMITED WARRANTY, AND SHALL BE OF THE SAME DURATION AS THE WARRANTY PERIOD STATED ABOVE. SOME STATES DO NOT ALLOW LIMITATIONS ON THE DURATION OF AN IMPLIED 

WARRANTY, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased, or (b) completing a warranty claim on line at www.intermatic.com. This warranty is made by: 

Intermatic Incorporated, Customer Service 7777 Winn Rd. Spring Grove, Illinois 60081-9698. For warranty service go to: http://www.intermatic.com or call 815-675-7000.

Reviews: