STEP 7
Position the protector
on the
wall next to the electrical panel
and mark the position of the the
cabinet mounting holes on the
wall. Care should be exercised
to position the knockout in the
protector cabinet in line with a
knockout in the electrical panel.
At least 2” should be allowed
between the protector and the
electrical panel to allow the
cover to open. Predrill the holes
and set one screw in the hole
for the top mounting screw.
STEP 8
Remove the appropriate
knockout
from the protector
cabinet. Install a 2-1/2” nipple,
length of seal-tite or conduit
between the protector and electrical cabinets. Hang the protector cabinet on
the screw using the exterior top keyhole of the cabinet. Insert the remaining
two mounting screws through the holes in the protector cabinet and tighten all
of the cabinet mounting screws. Tighten the connectors on the nipple, seal-tite
or conduit between the cabinets.
STEP 9
Make sure that the electric power is OFF
in the electrical panel. Remove
the front cover or trim panel from the panel. Select and remove the desired
knockout through which the protector
wiring will enter the panel.
STEP 10
Twist the four 14 AWG wires
around
each other at a rate of 1-1/2 turns per
foot of length. Wrap a piece of tape on
the ends of the wires and feed them
through the connector and into the
electrical panel.
STEP 11
The IG1300 Series is shipped ready
for installation on the right-hand side
or top positions of the electrical panel.
If the protection panel is mounted on
the left side of the electrical panel,
refer to the
Special Instructions
at
the end of this section to reverse the
wire channel cover and telephone and
coaxial modules.
Figure 3
3
Figure 2