GM40AVE-RD89 Series General Purpose Electronic Commercial Time Switches
Installation Instructions

•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
•  More than one circuit breaker or disconnect switch may be required to de-energize the equipment before 

servicing.

•  Do not use the manual shut-off position of the timer for equipment servicing. Always disconnect the power 

at the circuit breaker(s) or disconnect switch(es).

•  Installation and/or wiring must be in accordance with national and local electrical code requirements.
•  This Time Switch is designed to control one or two single phase loads. Do not use to directly control three 

phase loads. Consult a qualified electrician if you are required to control three phase equipment.

•  Some terminals in the Time Switch may be energized even if the yellow and green LED indicators are OFF.
•  The circuit conductors shall have an ampacity not less than the maximum total load to be controlled.
•  For all connections, use COPPER conductors ONLY – min. #8 AWG wires for 40 A loads, or #10 AWG wires 

for 30 A loads, min. 90°C (194°F) 

•  Over current protection shall have an interrupting rating sufficient for the application control circuit voltage 

and the total load current of the equipment being controlled.

•  A fuse or circuit breaker shall be connected in series with each ungrounded conductor (and shall be able 

to simultaneously open each conductor.

•  Check all terminals and wires with an appropriate voltage meter before touching.
•  This enclosure does not provide grounding between conduit connections. When metallic conduit is used, 

you must also install grounding type bushings and jumper wire, in accordance with the (NEC) National 
Electrical Code requirements.

•  For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the 

UL514B (standard for fitting conduit and outlet boxes) are to be used.

•  Replace plastic insulator covering terminals before powering ON.

APPLICATION

The GM40AVE-R Series Time Controls are universal, electronic time switches designed for general 
purpose commercial applications. The control operates on any AC voltage from 120 VAC to 277 VAC. 
The mechanism is mounted in an indoor/outdoor enclosure to control lighting, heating, air 
conditioning, pumps, motors, or general electrical circuits in residential, commercial, industrial and 
agricultural facilities. 

INSTALLATION INSTRUCTIONS

1.  Open door and remove the interior protective cover by releasing the spring latch (See Figure 1).
2.  Remove the printed circuit board by releasing the spring latch holding the bottom of the board (see 

Figure 1).

3.  Select knockouts to be used. Remove the inner 1/2" knockout by inserting a flathead screwdriver 

in the slot and carefully punch the knockout loose. Remove slug. If 3/4" knockout is required, 
remove the outer ring with pliers after removing the 1/2" knockout. Smooth edge with knife, if 
necessary.

4.  Place the enclosure in the desired mounting location, and mark the three mounting holes (refer to 

Figure 2 for dimensions).

5.  Install the top screw first with one of the supplied spacers, and then hang the enclosure by the 

keyhole. 

6.  Drive the remaining two screws at the bottom of the enclosure through the mounting holes while 

passing each screw through one of the supplied spacers and in to the wall.

7.  Connect conduit hubs to conduit before connecting the hubs to the enclosure. After inserting hubs 

into enclosure, carefully tighten hub lock nut. Do not over-torque. 

8.  Replace printed circuit board making sure to engage spring latch at the bottom of PCB.
9.  Connect wiring in accordance with national and local electrical and safety codes (see wiring 

diagrams).

10.  Grounding: Terminate all ground wires to the ground lug inside the case at the bottom of the 

enclosure.

11.  Replace interior protective cover. 
12.  Close the enclosure door.

PROGRAMMING

The installer should refer to the supplemental instruction manual included with this unit for information 
regarding setting the time, symbols, keys and programming.

•  Rotate timer dial clockwise only.
•  Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
•  Jumper wires are not included.
•  Alterations or modifications to the device will void warranty.

ELECTRICAL RATINGS

Risk of Fire or Electric Shock

WARNING

NOTICE

Read instructions completely before installation and retain this booklet for future reference.

GM40AVE-R SERIES TERMINAL DESIGNATIONS 

NO 2

NC 2

NO

NC

L 2/N

L 1

T

TIMER

L

N

COM

LOAD 

#1  

LOAD 

#2 

COM2

120/277 VAC Application Two Loads

COM2

NO 2

NC 2

NO

NC

L 2/N

L 1

T

TIMER

L1

L2

COM

LOAD 

#1  

208/240 VAC Application One Load

NO Contacts:

40 A Resistive, 120-277 VAC
30 A Ballast, 120 VAC
20 A Ballast, 277 VAC
15 A Tungsten, 120 VAC
300 VA Pilot Duty, 120-240 VAC
1 HP, 16 FLA, 90 LRA @ 120 VAC
2 HP, 12 FLA, 52 LRA @ 208-277VAC

NC Contacts:

30 A Resistive, 120-277 VAC
10 A Ballast, 277 VAC
2 A Tungsten, 120 VAC
1 HP, 12 FLA, 30 LRA @ 120 VAC
2 HP, 10 FLA, 30 LRA @ 240 VAC

WIRING CONNECTIONS:

Screw box lug terminals

ENVIRONMENTAL RATINGS:

Operating Temperature Range:   
-13° F to 131° F (-25° C to 55° C)
Operating Humidity:  
10-95% RH, non-condensing

ENCLOSURE DIMENSIONS:

8.795" H x 6.631" W x 2.935" D

SHIPPING WEIGHT: 

2 lbs.

Figure 2 - Rear View of 

Enclosure with mounting hole 

dimensions

6-1/8”

2-1/2”

GM40AVE-R Digital timer controls

Interior Protective Cover

Figure 1 - Spring Latch

Timer 
Mechanism

Summary of Contents for GM40AVE-RD89 Series

Page 1: ...olding the bottom of the board see Figure 1 3 Select knockouts to be used Remove the inner 1 2 knockout by inserting a flathead screwdriver in the slot and carefully punch the knockout loose Remove slug If 3 4 knockout is required remove the outer ring with pliers after removing the 1 2 knockout Smooth edge with knife if necessary 4 Place the enclosure in the desired mounting location and mark the...

Page 2: ...e mécanisme est monté dans un boîtier d extérieur intérieur conçu pour le contrôle de l éclairage du chauffage de la climatisation des pompes des moteurs ou des circuits électriques généraux de locaux particuliers commerciaux industriels et agricoles DIRECTIVES D INSTALLATION 1 Ouvrez la porte et retirez le cache intérieur de protection en appuyant sur le verrou à ressort voir la figure 1 ci desso...

Page 3: ...enga la parte inferior del tablero vea la Figura 1 de abajo 3 Seleccione los troqueles a utilizar Retire el troquel de 1 2 interior al insertar un destornillador de cabeza plana en la ranura y aflojar el troquel con cuidado Retire el vástago Si se requiere un troquel de 3 4 retire el anillo exterior con unas pinzas después de retirar el troquel de 1 2 Alise la orilla con un cuchillo si es necesari...

Page 4: ...EXCLUIR O LIMITAR LOS DAÑOS INCIDENTALES O CONSECUENCIALES POR LO QUE LA LIMITACIÓN O EXCLUSIÓN ANTERIOR PUDIERA NO SER VÁLIDA EN SU CASO ESTA GARANTÍA SUSTITUYE A CUALQUIER OTRA GARANTÍA EXPRESA O IMPLÍCITA TODAS LAS GARANTÍAS IMPLÍCITAS INCLUIDA LA GARANTÍA DE IDONEIDAD COMERCIAL O DE IDONEIDAD PARA UN DETERMINADO FIN SE MODIFICAN PARA QUEDAR INCLUIDAS ÚNICAMENTE EN LA PRESENTE GARANTÍA LIMITADA...

Reviews: