Intermatic FL250HPS Installation Instructions Download Page 2

277 V

240 V

208 V

120 V

COM

IGN-02

X3

LAMP

X1

X2

COM

CAP

277 V

240 V

208 V

120 V

COM

LAMP

COM

347 V

277 V

120 V

COM

IGN-02

X3

LAMP

X1

X2

COM

CAP

COM

LAMP

COM

347 V

277 V

120 V

High Pressure 
Sodium 250 &  
400 Watt
Figure 3

Metal Halide  
250 & 400 Watt
Figure 4

High Pressure 
Sodium 250 &  
400 Watt w/tri-tap
Figure 4

Metal Halide  
250 & 400 Watt  
w/tri-tap
Figure5

MOUNTING & WIRING (continued)

Select appropriate fixture wire to match incoming voltage. 
Models  FL250HPS,  FL400HPS,  FL250MH  &  FL400MH 
are shipped with 277 V wire ready for connection. Models 
FL250HSPT,  FL400HPST,  FL250MHT  &  FL400MHT  are 
shipped with 347 V wire ready for connection. If supply voltage 
is lower, cap wire marked 277V (or 347 V for tri-tap models) 
with appropriate twist on wire connector and strip fixture wire 
marked with matching voltage (see Figure 3 through Figure 5) 
Using  provided  twist  on  or  other  approved  connectors, 
connect the fixture wires to the 3-wire cord.

Connect the selected voltage fixture wire to the Black 

(hot) cord wire.

Connect  the  white  fixture  wire  marked  “COM”  to  the 

White (neutral) cord wire.

Connect  the  Green  (equipment  ground)  cord  wire  to 

the fixture ground screw.

Confirm all unused fixture wires are capped.
Replace  and  secure  reflector/lampholder  assembly  with 
(4) screws.
Install the fixture to the Trunion Mounting Bracket using the 
(2)  Trunion  Bolts.  On  the  trunion  assembly  there  are  (3) 
position holes in the outer yoke and (5) positioning hoes in 
the inner yoke. Align the positioning holes as desired and 
secure with Positioning Screw.
Using approved twist on wire connector, connect the free 
end of the 4ft cord to the supply wires inside an approved 
outdoor,watertight junction box.

Connect  the  Black  (hot)  cord  wire  to  the  Black  (hot) 

supply wire.

Connect  the  White  (neutral)  cord  wire  to  the  White 

(neutral) supply wire.

6.

7.

a.

b.

c.

8.
9.

10.

11.

a.

b.

Connect the Green (equipment ground) cord wire to the 

Green (equipment ground) supply wire.

Screw lamp into lampholder until finger-tight.
Install,  close,  and  secure  lens  cover  with  (2)  screws.  To 
weatherproof  fixture,  seal  all  holes  in  housing  (mounting 
conduit, plugs, photocontrols, etc.) with silicone sealant.
To operate, restore power to the circuit and switch light on.

c.

12.
13.

14.

LIMITED 1 YEAR WARRANTY

If within one (1) year from the date of purchase, this product fails due to a defect in material or workmanship, Intermatic Incorporated will repair or replace it, at its sole option, 

free of charge. This warranty is extended to the original purchaser only and is not transferable. This warranty does not apply to: (a) damage to units caused by accident, 

dropping or abuse in handling, acts of God or any negligent use; (b) units which have been subject to unauthorized repair, opened, taken apart or otherwise modified; 

(c) units not used in accordance with instructions; (d) damages exceeding the cost of the product; (e) sealed lamps and/or lamp bulbs; (f) the finish on any portion of the 

product, such as surface and/or weathering, as this is considered normal wear and tear; (g) transit damage, initial installation costs, removal costs, or reinstallation costs.

INTERMATIC  INCORPORATED  WILL  NOT  BE  LIABLE  FOR  INCIDENTAL  OR  CONSEQUENTIAL  DAMAGES.  SOME  STATES  DO  NOT  ALLOW  THE  EXCLUSION 

OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. THIS WARRANTY 

IS IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES. ALL IMPLIED WARRANTIES, INCLUDING THE WARRANTY OF MERCHANTABILITY AND THE 

WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE, ARE HEREBY MODIFIED TO EXIST ONLY AS CONTAINED IN THIS LIMITED WARRANTY, AND SHALL 

BE OF THE SAME DURATION AS THE WARRANTY PERIOD STATED ABOVE. SOME STATES DO NOT ALLOW LIMITATIONS ON THE DURATION OF AN IMPLIED 

WARRANTY, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.

This warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased, or (b) mailing the product, along with proof of pur-

chase, postage prepaid to the authorized service center listed below. This warranty is made by: Intermatic Incorporated/After Sales Service/7777 Winn Rd., Spring Grove, 

Illinois 60081-9698/815-675-7000  http://www.intermatic.com  Please be sure to wrap the product securely to avoid shipping damage. 

158--00108

THESE INSTRUCTIONS DO NOT COVER ALL VARIATIONS IN EQUIPMENT, NOR DO THEY PROVIDE FOR ALL SITUATIONS 

RELATED TO FIXTURE INSTALLATION, OPERATION OR MAINTENANCE. FOR FURTHER INFORMATION CONTACT YOUR 

DISTRIBUTOR OR INTERMATIC INCORPORATED - SPRING GROVE, ILLINOIS 60081 (815) 675-7000   www.intermatic.com

    

CAUTION

  (Metal Halide Lamps Only) 

Do not use lamp beyond manufactures rated life to reduce 
chance of lamp rupture.Turn lamp off at least once for 15 
minutes per week to reduce chance of lamp rupture.

LAMP REPLACEMENT

    

CAUTION

 

Use lamp of correct type and wattage as specified on fixture.

1.  Turn off power at circuit breaker or fuse box. Allow fixture and 

lamp to cool.

2.  Loosen (2) screws and swing hinged fixture lens door open. 

Remove old lamp and replace with new lamp of correct type 
and  wattage.  Screw  lamp  into  socket  in  lampholder  until 
finger-tight.

3.  Close  and  secure  lens  door,  making  sure  that  gasket  is 

properly seated, free of debris, and compressed to seal out 
moisture.

4.  Turn power back on.
5.  Properly dispose of lamp per manufacturer’s recommendations.

Alternate wiring: If desired connections may be made inside 

fixture using supply wire rating minimum 125°.

Reviews: