background image

Electronic 4 - Circuit Astronomic 

7 - Day Time Switch

Installation and Setup Instructions

With Supercapacitor Carryover

Federal Communications Commission (FCC) Notice for ET8415 Time Switch

This document explains the setup and configuration of the Intermatic ET8415 4-Circuit Electronic Astronomic 
7-Day Time Switch. The ET8415 time switch automatically switches loads to a preset weekly schedule. The time 
switch can support up to 28 fixed ON and 28 fixed OFF events (56 total) and up to four Astro events. Each event 
can be applied to any combination of circuits and days. 
The  time  switch  features  an  LCD  and  panel-mounted  control  buttons  to  set,  review,  and  monitor  the  time  switch                         
functions,  including  enabling  or  disabling  Daylight  Saving  Time  (DST)  and  configuring  DST  switchover  dates.                            
Follow these instructions to complete the installation and programming for the ET8415 time switch.

Description

This device complies with part 15 of the FCC rules. Operation of this device is subject to the following two conditions: (1) This device may 
not cause harmful interference, and (2) This device must accept any interference, including interference that may cause undesired opera-
tion.  This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. 
These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial 
environment. This equipment generates, uses and radiates radio frequency energy and, if not installed and used in accordance with instruc-
tions, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful 
interference that requires the user to correct at his or her own expense. 

Installation

MODEL ET8415CR

NOTICE

Follow these instructions to install the time switch. 

1.  Open the time switch enclosure door.
2.  Press the catch at the top of the case and pull out the mechanism from the case. 
3.  Choose a knockout to remove from the enclosure.

NOTE:

 

There are five 1/2 inch to 3/4 inch combination knockouts available. There are 

two on the bottom of the enclosure, one on each side, and one on the rear. 

4.  Insert a flathead screwdriver into the slot of a 1/2 inch knockout and punch loose and  

remove.

NOTE:

 If a 3/4 inch knockout is needed, remove the 1/2 inch knockout first, then the 

outer ring. Smooth edge if necessary.

Snap out catch

Tilt top forward

  

Do not touch the circuit board components. Contact with the circuit board components can create static discharge, which can damage the 
microprocessor.

Snap out catch

Tilt top forward

      

WARNING

Risk of Fire or Electric Shock

•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
•  More than one circuit breaker or disconnect switch may be required to de-energize the equipment before servicing.
•  Bonding between conduit connections is not automatic and must be provided as part of the installation.
•  Installation and/or wire must be in accordance with National and Local Electrical Code requirements.
•  Use #14 - #8 AWG wires, rated at least 90°C - COPPER conductors ONLY.
•  If the power disconnect point is out of sight, lock it in the OFF position and tag it to prevent unexpected application power.
•  Make sure there is not wire insulation under the terminal plate on the time switch connector. Firmly tighten terminal screws.
•  Replace plastic insulator covering terminals before powering ON.
•  KEEP DOOR CLOSED AT ALL TIMES when not servicing.

Summary of Contents for ET8415

Page 1: ...quipment in a residential area is likely to cause harmful interference that requires the user to correct at his or her own expense Installation MODEL ET8415CR NOTICE Follow these instructions to install the time switch 1 Open the time switch enclosure door 2 Press the catch at the top of the case and pull out the mechanism from the case 3 Choose a knockout to remove from the enclosure NOTE There a...

Page 2: ...ch AC IN COM1 COM2 COM3 COM4 NO 1 NO 2 NO 3 NO 4 Load 1 Load 2 Load 3 Load 4 L1 120 208 240 277 VAC Input Neutral L2 EXAMPLE 4x SPST Operation Mode set to IND Input and Output voltage are the same NOTE Each relay has isolated contacts Other voltages can be used if dedicated supply voltage is used for COM terminal replacing L1 There are many different ways to set the relays on the ET8415CR Time Swi...

Page 3: ...e time switch will return to manual mode Initial Setup The following sections provide instructions for the initial setup of the time switch Setting Date and Time Follow this procedure below to set the date and time in the time switch NOTE If necessary hold or to scroll through the digits rapidly 1 Press MODE to scroll through the menus until SET and DATE appear at the top of the display The month ...

Page 4: ...ns If Then Latitude needs to be set Press or to select the latitude and press ENTER NEXT The longitude screen appears Go to step 7 Latitude does not need to be set Press ENTER NEXT to scroll past the latitude and longitude screens to the TZCENT screen Go to step 8 NOTE If necessary press or simultaneously to return to the region screen 7 Press or to select the longitude and press ENTER NEXT The TZ...

Page 5: ...tro event for another load Press ENTER NEXT Repeat steps 3 through 6 All the required Astro events are set Press MODE to exit The procedure is complete Users can configure Astro events fixed timed events or a combination of Astro and fixed timed events Perform the applicable instructions below To set Astro events only perform the procedure Setting Astro On Off Events To set fixed timed events only...

Page 6: ...T to save NOTE If you are performing the procedure Setting Astronomic and Fixed Events return to step 4 of that procedure 8 Repeat steps 2 through 7 to set the fixed OFF event After both fixed on and fixed off are set go to step 9 9 Take one of these actions If Then Another fixed timed event needs to be set Repeat steps 2 through 8 All the events are set Press MODE to exit Go to step 10 10 Press M...

Page 7: ...ed in the reset procedure Resetting the Time Switch To perform a reset press the reset button The following occurs All display segments activate for one second then the timer model number appears followed by the firmware revision The current operational mode setting appears for the first two relays followed by the current setting for the last two relays The time switch defaults to Manual Mode The ...

Page 8: ...age initial installation costs removal costs or reinstallation costs INTERMATIC INCORPORATED WILL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS OR IMPLIED WARRANTIES ALL IMPLIED WARRANTIES INCLUDI...