![background image](http://html.mh-extra.com/html/interlogix/iti-superbus-2000/iti-superbus-2000_installation-instructions-manual_2076775004.webp)
4
SuperBus® 2000 Energy Saver Module
Setting the Module Unit Number
Setting the Module Unit Number
Setting the Unit Number On Concord
(software versions 1.0–1.6) and
UltraGard Panels
Module dip switches can be set to any unit number 0–15.
The default setting 0 can be used if no other bus devices are
installed in the system. When using one module per
partition (Concord only), the lower unit number will be
assigned to partition 1, while the higher unit number will be
assigned to partition 2.
Note
Do not use module number 15 if it is installed in a
Concord RF system since the built-in receiver is fac-
tory set to unit number 15 and cannot be changed.
To set the module unit number:
Locate the DIP switches on the ESM circuit board (see
Figure 1) and set them to the desired unit number (0–15)
before applying power (see Figure 6).
CAUTION
Do not change DIP switch settings once the panel is
powered up.
❑
0-15 for Concord
❑
0-7 for UltraGard
Figure 6. ESM Unit Number DIP Switch Settings
Setting the Unit Number on Concord
Panels with Software Version 2.0 or Later
The unit number will be automatically set when powering
up the system. No action is required by the installer. When
using one module per partition, the panel automatically
assigns each module with a partition number.
Power Up and Bus Communication
Use the following procedures for powering up the system
and verifying bus communication.
On Concord Panels (all software versions)
Note
In order to enter panel program mode to verify unit
numbers (optional), an alphanumeric touchpad must
be connected to Concord panels. Refer to the specific
Installation Instructions for more information.
1.
Verify that all wiring at the panel and module is correct.
2.
Connect the panel battery and plug in the panel AC
power transformer. Alphanumeric touchpad displays
should come on.
3.
Verify that the ESM red bus LED is flashing.
4.
If desired, enter panel program mode to verify the unit
number was learned and enrolled into the correct parti-
tion (see panel Installation Instructions for more infor-
mation).
Note
If the ESM red bus LED does not flash, remove AC
panel power, disconnect the battery, and see Table 3
“Troubleshooting.”
On UltraGard Panels
1.
Verify that all wiring at the panel and module are cor-
rect.
2.
Connect the panel battery and plug in the panel AC
power transformer.
3.
Turn the panel power switch to on.
4.
Set the panel RUN/PROGRAM switch to PROGRAM.
If the alphanumeric display reads
1-OFF
and the
1
is flash-
ing, you must enter the installer code to place the panel into
the program mode. Refer to the panel Installation
Instructions for more information.
The ESM red bus LED should be flashing continuously
which indicates successful communication to the panel.
Note
If the ESM red bus LED is not flashing continuously,
set the RUN/PROGRAM switch to RUN, turn off the
panel power switch, unplug the panel AC power trans-
former, disconnect the backup battery, and see
Table 3 “Troubleshooting.”
9712G09A.DSF
UNIT NUMBER 0
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 1
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 2
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 3
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 4
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 5
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 6
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 7
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 8
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 9
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 10
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 11
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 12
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 13
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 14
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8
ON
UNIT NUMBER 15--Do not use in Concord RF systems.
M
A
M
A
M
A
M
A
M
A
M
A
M
A
M
A
M
A
M
A
M
A
M
A
M
A
M
A
M
A
M
A