background image

8841G01A.DS4

1

SuperBus® 2000 Energy Saver Module

Installation Instructions

Product Summary

The SuperBus

 

2000

 

Energy Saver Module (ESM) provides a 

money-saving and convenient way to monitor and control 
temperatures. The ESM uses low- and high-temperature 
limits to save energy by overriding the existing HVAC ther-
mostat. When the ESM is on, temperature limits determine 
when the heat or air-conditioning turns on. When the ESM 
is off, the HVAC thermostat controls heat and air-condition-
ing.

For example, if the thermostat is set for 68°F and the ESM 
high limit is 80°F, the ESM prevents the air-conditioner 
from turning on until the temperature reaches 80°F. The 
ESM limits may be set between 40° and 90°F.

A temperature sensor monitors the temperature and reports 
a freeze alarm to the panel if the temperature drops below 
the set freeze temperature (default = 42°F). A backup freeze 
stat provides additional protection by activating the furnace 
if the temperature drops to 45°F (±6°F).

Note

Depending on where the ESM is located, additional 
freeze sensors may need to be placed throughout the 
residence to provide adequate freeze protection.

This device is backward compatible with Concord

 panels 

with software versions 1.0–1.6 and UltraGard

 panels.

SuperBus 2000 

vs. 

SuperBus

Compatible panels (SuperBus 2000) have the ability to 
auto-address module unit numbers. When the panel is pow-
ered up, the panel automatically reads the unique SuperBus 
2000 device ID number and assigns a unit number to the 
module. This eliminates manually setting DIP switches and 
the chance of identical unit number conflicts. 

Non-Compatible panels (SuperBus) communicate with 
SuperBus 2000 modules but require the module unit num-
ber to first be set manually using DIP switches.

SuperBus 2000 Panels

Concord (software versions 2.0 and later)

SuperBus Panels

UltraGard

Concord (software versions 1.0–1.6)

Figure 1 shows the main ESM components and Table 1 
describes them.

Figure 1. ESM Component Locations

 Table 1: ESM Component Descriptions

ESM Component

Function

Backup Freeze Stat

Activates furnace if temperature drops 
to 45°F (±6°F).

SuperBus 2000 
Device ID Number 
Label

Identifies unique device ID number 
(SuperBus 2000 panels).

ESM Software 
Version Label

Identifies the installed software 
version.

Terminal Strip

Used for panel and HVAC thermostat 
connections.

Temperature Sensor

Monitors the premises temperature.

Bus LED

Flashes constantly to indicate normal 
communication to the panel bus.

Unit Number DIP 
Switches

Used for manually setting unit 
numbers (SuperBus panels).

1

2

3

4

5

6

8557G31C.DS4

BACKUP

FREEZE

STAT

BUS

LED

ESM SOFTWARE
VERSION LABEL

TERMINAL STRIP

UNIT NUMBER

DIP SWITCHES

TEMPERATURE

SENSOR

SUPERBUS 2000

DEVICE ID

NUMBER LABEL

 

ITI Part No. 60-620-01

Document Number: 466-1031-01 Rev. A
August 2000

Summary of Contents for ITI SuperBus 2000

Page 1: ...rBus 2000 have the ability to auto address module unit numbers When the panel is pow ered up the panel automatically reads the unique SuperBus 2000 device ID number and assigns a unit number to the module This eliminates manually setting DIP switches and the chance of identical unit number conflicts Non Compatible panels SuperBus communicate with SuperBus 2000 modules but require the module unit n...

Page 2: ...nterrupting the thermostat main power forcing the thermostat to rely on battery power to save time and programmed set tings As a result the thermostat battery may need to be replaced more often depending on how often and how long the ESM is turned on Refer to the specific panel Installation Instructions for wire length limits Tools and Supplies Screwdrivers Phillips and flat Screws and anchors inc...

Page 3: ...r transformer and disconnect the backup battery 2 Turn off the thermostat and remove its cover 3 Route a 4 conductor 22 gauge or larger stranded wire from the ESM to the panel 4 Connect terminals 3 through 6 to the panel as shown in Figure 5 Figure 5 ESM Wiring Connections to the Thermostat and UltraGard Panel Terminals 5 Route 22 gauge or larger stranded wire from the ESM to the thermostat To con...

Page 4: ...rrect 2 Connect the panel battery and plug in the panel AC power transformer Alphanumeric touchpad displays should come on 3 Verify that the ESM red bus LED is flashing 4 If desired enter panel program mode to verify the unit number was learned and enrolled into the correct parti tion see panel Installation Instructions for more infor mation Note If the ESM red bus LED does not flash remove AC pan...

Page 5: ...d software ver sions 1 0 1 6 panels make sure that all bus devices are set with different unit numbers 3 If the unit number dip switches were changed remove panel power and reapply it for the panel and ESM to communicate successfully You will have to go into panel programming to delete the unit number previ ously assigned to the ESM see panel Installation Instructions 4 If the LED still doesn t fl...

Page 6: ...nd used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one o...

Reviews: