background image

 

P/N 466-

2913 • REV C • ISS 15MAR19 

 

7 / 7 

Wiring configuration for EN version 

Wire(s) 

Type 

Assignment 

Red (RD) 

Supply 

Supply voltage (+) 

Blue (BU) 

Supply 

Ground (-) 

Pink (PK) 

Input 

Command input 

Black (BK), brown (BN) 

Output 

Intrusion 

Yellow (YE), green (GN) 

Output 

Tampering (removal protection) 

White (WH), grey (GY) 

Output 

Fault (external field) 

Note: 

See Figures 8 and 9. 

Distances 

Mounted on non ferromagnetic material 

Approach distance A 

30 

mm ± 10 mm 

Break distance B 

50 

mm ± 10 mm 

Fault trigger distance C 

−4 mm ± 2 mm 

Mounted on ferromagnetic material 

Approach distance A 

28 mm ± 7 mm 

Break distance B 

38 mm ± 5 mm 

Fault trigger distance C 

−4 mm ± 2 mm 

See Figure 7. 

The values refer to the Y-distance relative to the learning position. 
Values along the Z-axis may differ. If required they are to be 
determined separately. The distances may vary depending on the 
installation situation, the magnetic code and the learning distance. 
Before the device is brought into service, they are to be verified. 

These operating distances are reached with a learning distance of 
15 mm (y axis) with a tolerance of 

± 5 mm (x axis) between the 

detector and the magnet housing. 

Specifications 

Operating voltage 

12 to 24 V DC 

Power consumption (monitoring mode) 

Approx. 5  mA (typical) 

Power consumption (learn-in mode, 
LED) 

max. 13 mA 

Permitted installation gap between 
magnet and detector 

10 to 20 mm 

Installation offset on the sides (revolving)  max. 1.5 mm 

Clearance from metal components 

min. 2 mm 

Permitted tolerance after learn-in (radial)  max. 1.5 mm 

Signal output 

Electronic switch 

Transfer resistance (closed) 

approx. 7 

Ω (typical) 

Transfer resistance (open) 

≥10 MΩ 

Electrical isolation between input and 
output 

min. 30 V 

Permitted output current 

max. 50 mA 

Permitted output voltage 

max. 30 V 

Measurement speed 

approx. 100 ms 

Connection cable 

LIYY 9 x 0.14  

mm² copper 

tin

−plated 

Cable conductors 

See Table 1 

Cable diameter 

Ø 5.8 mm 

Cable length 

Up to 10 m 

Contact dimensions 

140 x 62 x 28 mm 

Magnet dimensions 

121.5 x 45 x 25 mm 

Temperature range 

−40°C to +70°C 

Regulatory information 

Manufacturer 

PLACED ON THE MARKET BY: 
UTC Fire & Security Americas Corporation, Inc. 
3211 Progress Drive, Lincolnton, NC, 28092, USA 

AUTHORIZED EU REPRESENTATIVE: 
UTC Fire & Security B.V. 
Kelvinstraat 7, 6003 DH Weert, Netherlands 

Product warnings 
and disclaimers 

 

THESE PRODUCTS ARE INTENDED FOR SALE 
TO AND INSTALLATION BY QUALIFIED 
PROFESSIONALS. UTC FIRE & SECURITY 
CANNOT PROVIDE ANY ASSURANCE THAT 
ANY PERSON OR ENTITY BUYING ITS 
PRODUCTS, INCLUDING ANY “AUTHORIZED 
DEALER” OR “AUTHORIZED RESELLER”, IS 
PROPERLY TRAINED OR EXPERIENCED TO 
CORRECTLY INSTALL FIRE AND SECURITY 
RELATED PRODUCTS. 

For more information on warranty disclaimers and 
product safety information, please check 

https://firesecurityproducts.com/policy/product-
warning/

 or scan the QR code. 

Protection class 

IP67 EN III/A 

Certification 

 

EN 

Grade 4, EN-ST-000222 

European Union 
directives 

UTC Fire & Security hereby declares that this 
device is in compliance with the applicable 
requirements and provisions of the Directive 
2014/30/EU and/or 2014/35/EU. For more 
information see www.utcfireandsecurity.com or 
www.interlogix.com. 

 

2012/19/EU (WEEE directive): Products marked 
with this symbol cannot be disposed of as 
unsorted municipal waste in the European Union. 
For proper recycling, return this product to your 
local supplier upon the purchase of equivalent 
new equipment, or dispose of it at designated 
collection points. For more information see: 
www.recyclethis.info. 

Contact information 

www.utcfireandsecurity.com or www.interlogix.com. 

For customer support, see www.utcfssecurityproducts.eu 

Summary of Contents for DC428

Page 1: ... 2019 UTC Fire Security Americas Corporation Inc 1 of 7 P N 466 2913 REV C ISS 15MAR19 DC428 Magnetic Contact Operation and Installation Manual EN 1 2 Z Y X ...

Page 2: ...2 of 7 P N 466 2913 REV C ISS 15MAR19 3 4 5 ...

Page 3: ...P N 466 2913 REV C ISS 15MAR19 3 of 7 6 7 ...

Page 4: ...K YE GN BN WH GY Intrusion zone Tamper zone Burglar Alarm System y Intrusion internal zone D 418 C Intrusion External Field Fault D 418 C BK YE GN BN WH GY Rx Termination Resistor Intrusion zone Tamper zone Burglar Alarm System y BU PK RD 12 24 V DC Command input Tampering Removal Protection DC428 DC428 ...

Page 5: ... x 24 0 x 20 0 mm C 1 AMK 100 G4 F semi finished 4 0 m D 1 Cover AMK G4 ATS 140 0 x 62 0 x 28 0 mm E 1 Protective Hose Ø 7 Ø 10 mm x 1 m F 1 Seal AMK G4 ATS 10 4 x 13 8 x 11 8 mm G 1 Screw AMK G4 ATS DIN 84 M3 x 8 mm H 2 Countersunk Screw ISO 7050 5 5 x 50 mm Form C Z J 4 Fillister Screw ISO 7049 5 5 x 50 mm Form C Z K 2 Fillister Screw ISO 70491 5 5 x 25 mm Form C Z L 2 Cylinder Screw ISO 1207 M3...

Page 6: ... Afterwards proceed according to the Learning in the unit to the installation environment section Note The magnet must already be correctly installed at this time To improve visibility of the LED while selecting this command you can hold the magnet outside of its closed position open window door In this case be ready to immediately return the magnet to its closed position when required to do so To...

Page 7: ...ax 50 mA Permitted output voltage max 30 V Measurement speed approx 100 ms Connection cable LIYY9x0 14 mm copper tin plated Cable conductors See Table 1 Cable diameter Ø 5 8 mm Cable length Up to 10 m Contact dimensions 140 x 62 x 28 mm Magnet dimensions 121 5 x 45 x 25 mm Temperature range 40 C to 70 C Regulatory information Manufacturer PLACED ON THE MARKET BY UTC Fire Security Americas Corporat...

Reviews: