9   P/N 466-5307 

• REV A • ISS 15MAR17                                              ©2017 United Technologies Corporation   

 

 
Carbon monoxide alarm pattern is four quick beeps repeating every 5 seconds 
 

      WARNING:  CARBON  MONOXIDE  ALARM  ACTIVATION  INDICATES  THE 
PRESENCE  OF  CARBON  MONOXIDE  (CO)  AT  HIGH  CONCENTRATIONS  WHICH 
CAN KILL YOU. 

If the CO condition that caused the alarm in the first place continues, the initiating alarm 
unit  will  reactivate  in  alarm  mode.  If  the  unit  goes  into  alarm  mode  again  within  six 
minutes,  it  is  sensing  high  levels  of  CO  which  can  quickly  become  a  dangerous 
situation. 

If the CO alarm reactivates within a 24 hour period, call a qualified appliance technician 
to  investigate  sources  of  CO  from  fuel  burning  equipment  and  appliances,  and  to 
inspect for proper operation of equipment. 

If  problems  are  identified  during  this  inspection,  have  the  equipment  serviced 
immediately.  Note  any  combustion  equipment  not  inspected  by  the  technician  and 
consult  th

e  manufacturer’s  instructions,  or  contact  the  manufacturer  directly  for  more 

information about CO safety and the equipment. Make sure that motor vehicles are not, 
or have not been, operating in a garage attached or adjacent to the residence. 

 

The detector is operating once it is activated and testing is complete.  When products of 
combustion  (smoke  or  CO)  are  sensed,  the  unit  sounds  a  loud  85dB  alarm.    See 
Detector Visual and Audible Indicators table.  In high levels of CO, the unit will go into 
alarm in a shorter period of time than at low levels of CO. 
 
The CO sensor meets the alarm response time as follows: 
 
At 70 PPM, the unit must alarm within 60-240 minutes. 
At 150 PPM, the unit must alarm within 10-50 minutes. 
At 400 PPM, the unit must alarm within 4-15 minutes. 

 
TESTING (PUSH TO TEST BUTTON) 

Test  your  detector  every  three  months  by  pressing  and  releasing  the  test  button 
quickly. A quick beep will confirm the button has been pushed. 

See Detector Visual and Audible Indicators table. The alarm will sound if the electronic 
circuitry,  horn,  speaker,  and  battery  are  working.  If  the  alarm  does  not  sound,  the 
detector must be replaced. 

 

        WARNING:  DUE  TO  THE  LOUDNESS  (85+  DECIBELS)  OF  THE  ALARM, 
ALWAYS 

STAND  AN  ARM’S  LENGTH  (ABOUT  2.5  FT.  (0.7M)  AWAY  FROM  THE 

UNIT OR USE EAR PROTECTION WHEN TESTING. 

 

Weekly testing is required to ensure proper operation. Erratic or low volume sound (or 
no  sound)  coming  from  your detector may  indicate a  defective  alarm  and  it  should  be 

Summary of Contents for CDX-135Z

Page 1: ...nterconnection 10 yr sealed battery and sensor life built in sounder diagnostic status LED integrated fixed temperature and rate of rise heat sensor and a pre freeze condition sensor The CDX 135Z uses a 319 5MHz transmitter for communication to the control panel and a 915MHz transmitter for interconnection communication between networked detectors Up to 24 detectors can be a part of the same inter...

Page 2: ...alarm Write the Install date in the space provided and then write in the Replace by date 10 years from initial power up in permanent marker on the label prior to installing the unit Two labels have been provided at the back of this installation manual that have important information on what to do in case of a CO alarm Place one label next to the alarm after it is mounted and one near a fresh air s...

Page 3: ... ventilating fans or other high air flow areas Do not install near vents flues chimneys or any forced unforced air ventilation openings Do not install near fans doors windows or areas directly exposed to the weather This model is powered by a non replaceable long life sealed lithium battery system and includes SMART HUSH TM control to temporarily silence nuisance alarms INSTALLATION ACTIVATION ENR...

Page 4: ... approximately 4 seconds and then release the button Network closed sound on each detector confirms network has been closed GREEN LED flashes once every 60 seconds to indicate normal operation NOTE The battery activation is a one time feature After activation the battery cannot be turned off and can only be discharged at the end of unit life If the detector is removed from the mounting plate the b...

Page 5: ...ctor will automatically create a new wireless network A brief series of quick GREEN LED blinks will occur and then the GREEN LED will fade on off every second on the button pushed detector network creator 4 Wait for the other wireless detectors to join the wireless network A brief series of quick GREEN LED blinks will occur and then the GREEN LED will fade on off approximately every 3 seconds NOTE...

Page 6: ...y existing detector until two beeps are heard approximately four seconds and then release the button The button pushed detector will cause the GREEN LED to fade on off on each existing detector to signal that the wireless interconnection network has been opened NOTE From this point you have fifteen 15 minutes to power up the new detector 3 Power up the new wireless unit by twisting the detector on...

Page 7: ...nds on the cover at the designated location per Figure 4 The detector will chirp once when the magnet is detected then the detector will chirp twice and the button will start flashing the RED LED rapidly to indicate the proper mode has been entered to reset the wireless settings Figure 4 2 Press and hold the Test Hush button for approximately eight seconds while the RED LED is rapidly flashing Aft...

Page 8: ...cluded on the outside and inside of the packaging provide these IDs The unique ID is enrolled into the control panel at the time of installation Use these IDs where appropriate in the specific panel being used enrollment instructions Verify programming and unit to panel communication Before mounting verify that the desired unit location provides good RF communication to the panel To verify program...

Page 9: ...or have not been operating in a garage attached or adjacent to the residence The detector is operating once it is activated and testing is complete When products of combustion smoke or CO are sensed the unit sounds a loud 85dB alarm See Detector Visual and Audible Indicators table In high levels of CO the unit will go into alarm in a shorter period of time than at low levels of CO The CO sensor me...

Page 10: ...3 From a distance of 2 4 feet 0 6 1 2m aim spray for 1 2 seconds at the vents or side of the detector 4 The alarm will sound within 1 10 seconds if the detector functions properly 5 Press the Test Hush button to quiet the sounder 6 Contact the central monitoring station to verify they received the alarm report 7 Alert the central monitoring station when you are finished testing NOTE An alternative...

Page 11: ...tton until the unit beeps three times approximately 8 seconds and then release the button The unit will enter the functional CO Gas test mode within 5 seconds The GREEN LED will blink periodically 1 second rate indicating that the alarm is in functional test mode 8 Apply UL approved CO test agent to the testing port Figure 5 When CO is detected the unit will activate a CO alarm Figure 5 9 To exit ...

Page 12: ...etector cannot determine a valid Night Day cycle because the detector is located in either a constantly dark or lighted location Low Battery End of Unit Life and Network Error chirps will not be inhibited If the unit is moved to a location that is not constantly dark or lighted it will determine a Night Day cycle because the unit continuously samples ambient light conditions Detector Visual and Au...

Page 13: ...Condition One RED LED blink every 30 seconds Detector chirps once when tamper condition is first sensed then the detector will chirp every 30 seconds after a 3 minute delay Reattach detector to its trim plate otherwise flashing and chirping will continue while condition exists Fault Mode Fatal Error One AMBER LED blink every 5 seconds Detector chirps every 30 seconds Flashing chirping continues wh...

Page 14: ...ble particles are generated from spills or when broiling Using the fan on a range hood which vents to the outside non recirculating type will also help prevent nuisance alarms from occurring by removing these combustible products from the kitchen If the source of a smoke alarm 3 long beeps is immediately known you can use the Hush feature to silence the alarm for approximately 8 10 minutes If no f...

Page 15: ... WHAT TO DO WHEN THE ALARM SOUNDS CO ALARM ACTIVATION NOTE Hush and Locate features are dependent on the type of models enrolled in the wireless interconnect system Non wireless models cannot be enrolled in the wireless interconnect system and therefore cannot receive the wireless Locate feature they will continue to alarm until the initiating unit is Hushed or the Smoke CO condition clears NOTE T...

Page 16: ...ons Permanently Disable Detector Discharge Battery WARNING DISCHARGING THE DETECTOR BATTERY IS PERMANENT ONCE THE DETECTOR BATTERY HAS BEEN DISCHARGED IT CANNOT BE REACTIVATED ONCE DISCHARGED THE DETECTOR WILL NO LONGER DETECT SMOKE OR CO ONCE THE DETECTOR BATTERY IS DISCHARGED THE BATTERY IS DEPLETED AND THE ALARM WILL NO LONGER FUNCTION ONCE THE DETECTOR BATTERY HAS BEEN DISCHARGED THE DETECTOR ...

Page 17: ... blinks when the Test Hush button is pushed released once Report the number of blinks to Customer Service if needed 2 Clean your detector See Section 12 Cleaning Your Detector for instructions Network Error One AMBER LED blink every 5 seconds Detector chirps every 30 seconds 1 Push the Test Hush button once to silence the audible indication for 24 hours at a time The RED LED will blink out an Erro...

Page 18: ...tton to initiate Hush Sensor Cleanliness Level Clean Me Indication AMBER LED Clean Me blink sequnce after TESTING PUSH TO TEST BUTTON temporal pattern per Section 5 Operation and Testing None 1 Push the Test Hush button to initiate detector test Following the temporal patterns the AMBER LED will blink the cleanliness status of the detector 0 1 Unserviceable fault remove discharge and replace the d...

Page 19: ... the vent pipes cold humid air with extended periods between cycles negative pressure differential resulting from the use of exhaust fans simultaneous operation of several fuel burning appliances competing for limited internal air vent pipe connections vibrating loose from clothes dryers furnaces boilers or water heaters obstructions in or unconventional vent pipe designs which can amplify the abo...

Page 20: ...de can be fatal or cause permanent damage and disabilities Many cases of reported carbon monoxide poisoning indicate that while victims are aware they are not feeling well they become so disoriented they are unable to save themselves by either exiting the building or calling for assistance Also young children and household pets may be the first affected Familiarization with the effects of each lev...

Page 21: ...L FIRE PROTECTION ASSOCIATION The National Fire Protection Association s Standard 72 reads as follows Where required by other governing laws codes or standards for a specific type of occupancy approved single and multiple station smoke alarms shall be installed as follows 1 In all sleeping rooms and guest rooms 2 Outside of each separate dwelling unit sleeping area within 21 ft 6 4 m of any door t...

Page 22: ...ng area in the vicinity but outside the bedrooms heat or smoke detectors in the living rooms dining rooms bedrooms kitchens hallways attics furnace rooms closets utility and storage rooms basements and attached garages WARNING ANY CHANGES OR MODIFICATIONS MADE TO THIS PRODUCT NOT EXPRESSLY AUTHORIZED BY THE MANUFACTURER COULD VOID THE USER S RIGHT TO OPERATE THIS DEVICE CONTACT INFORMATION For con...

Page 23: ...rn Dimensions Ø 5 6 0 01in x 2 3 0 04in Ø142 3 0 3mm x 59 0 1 0mm Smoke Sensitivity 0 97 to 3 67 ft obscuration CO Alarm Response Time 70 PPM 60 240 minutes 150 PPM 10 50 minutes 400 PPM 4 15 minutes Rate of Rise ROR heat detection 15 F min 8 3C min monitoring above 85 F 29 4C Fixed temperature heat detection 135 F 57 2C 5 F 2 8C Freeze warning 41 F 5C 5 F 2 8C Storage temperature 4 to 140o F 20 t...

Page 24: ...All transmitters regulated by IC must comply with RF exposure requirements listed in RSS 102 Radio Frequency RF Exposure Compliance of Radiocommunication Apparatus All Frequency Bands Currently this device is approved for use for when 20 cm can be maintained between the antenna and users Specific Absorption Rate SAR evaluation is required if the separation distance between the user and or bystande...

Page 25: ...ment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Changes or m...

Page 26: ...t Support these are the first questions you will be asked Alarm Model Number located on back of detector Date Code located on back of detector The National Fire Protection Association NFPA and the manufacturer recommend replacing this alarm ten years from the date code Date of Purchase Where Purchased WHAT TO DO WHEN THE ALARM SOUNDS Smoke heat alarm pattern is three long beeps 1 5 second pause th...