32
ATS125x/1260 Four-Door/Four-Lift DGP Programming Guide
The difference between Door Open and Door Unlock is: The Door Open
command only unlocks the door for the Unlock Time, whereas the Door Unlock
command opens the door permanently until a Door Lock command is sent.
Door Lock procedure
The second relay will pulse on for 0.5 s. If according to the zone monitoring
(explained below) the door has not closed, this procedure will continue until it
does. See timing diagram in Figure 2 below.
Figure 2
Zone monitoring
The first zone is the reed switch and the second zone comes from the electronic
lock indicating the door lock position.
• Door Open or Door Unlock: If the second zone is active and the first zone is
normal.
• Door Lock: If the second zone is normal and the first zone is active.
Time & Attendance Reader
XX, NO – Time & Attendance Reader
*-Change
If set to Yes, it will enable the reader to function as a time and attendance reader.
Note:
This function is not currently enabled.
Disable Duress functionality
XX, NO - Disable Duress
*-Change
This option is used to disable duress codes from functioning.
• Yes: No duress function available at this door.
• No: The Duress function is available.