Interlogix 600-6520-95 Manual Download Page 2

• 

Do not install in kitchens, garages, or furnace rooms that 
may expose the sensor to substances that could damage 
or contaminate it. 

2  

600-6520-95 Carbon Monoxide Alarm Manual 

• 

Do not install in areas where the temperature is colder 
than 40

°

F (4.4

°

C) or hotter than 100

°

F (37.8

°

C) such as 

crawl spaces, attics, porches, and garages. 

• 

Do not install within 5 ft. of heating or cooking appliances. 
(We recommend 15 ft. to prevent nuisance alarms.) 

• 

Do not install near vents, flues, chimneys, or any 
forced/unforced air ventilation openings. 

• 

Do not install on metal surfaces. 

• 

Avoid mounting in areas with a large quantity of metal or 
electrical wires. 

• 

Do not install near ceiling fans, doors, windows, or areas 
directly exposed to the weather. 

• 

Do not install in dead air spaces, such as peaks of vaulted 
ceilings or gabled roofs, where CO may not reach the 
sensor in time to provide early warning. 

• 

Do not install near deep-cell large batteries. Large 
batteries have emissions that can cause the alarm to 
perform at less than optimum performance. 

• 

Do not obstruct the vents located on the alarm. Do not 
place the alarm where drapes, furniture, or other objects 
block the flow of air to the vents. 

Battery installation and replacement 

Note: 

Place the control panel into sensor test mode prior to 

replacing the batteries. If the control panel is not in sensor test 
mode during battery replacement, an alarm/tamper condition 
may be indicated. 

To install or replace the batteries in this alarm: 

1.  Slide the alarm body off of the mounting plate. 

2.  If replacing batteries, remove the old batteries and 

properly dispose of them as recommended by the battery 
manufacturer. 

3.  Install the new batteries. Note the polarity illustration in the 

battery compartment (Figure 3). 

Figure 3: Batteries 

W
A

R

N

IN

G

 X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

Battery compartment

_

+

_

 

4.  Slide the alarm body back onto the mounting plate. 

Note:

 The mounting plate will not close if all three 

batteries are not installed. 

Figure 4: Sliding the alarm on the mounting plate 

Alarm mounting guide

Alarm mounting guide

 

5.  Perform a sensor/RF test with the control panel. See “RF 

communication test” on page 3

When replacing the batteries, use one of the following 
approved brands: 

• 

Duracell MN1500 or MX1500 

• Energizer 

E91 

Note:

 For battery replacement information, see interlogix.com. 

Use of a different battery may have a detrimental effect on the 
alarm operation. 

Note: 

Constant exposures to high or low humidity may reduce 

battery life. 

After installing or changing the batteries, reinstall your alarm. 
Test your alarm by using the Test/Hush button and check that 
the green Power LED is on. 

Mounting the alarm 

Note: 

Verify RF performance prior to permanently mounting 

the alarm. See “RF communication test” on page 3. 

The CO alarm can be wall mounted or ceiling mounted. 

To mount the alarm: 

1.  Slide the alarm body off of the mounting plate. Place the 

mounting plate in the desired location, and mark the 
location of the two mounting holes. Orient the mounting 
plate vertically or horizontally as shown in the following 
figures. 

Note:

 The alarm can also be directly mounted to a single 

gang box. 

Figure 5: Vertical mounting 

Mounting hole

Mounting latch

Alarm
procedure
label

Warning

XXXXxx XXX x xxx
XX XXX XXXXxxx
XXXX XXX XXXxx
XXXXXXXX XX xx

XXXXxx XXX x  xx
XX XXX XXXX xx
XXXX XXX XXXxx
XXXXXXXX XX xx
XXXXxx XXX xxx
XX XXX XXXXxx
XXXX XXX XXXx
XXXXXXXX XX
XXXXxx XXX xxx
XX XXX XXXX xx
XXXX XXX X X
XXXXXXXX XXxx
xxxxxxxxxxx
XXXXxxx
xxxxxxxxxxx

Mounting hole

 

Summary of Contents for 600-6520-95

Page 1: ...Yes local at CO Yes local at CO Yes Low Battery Yes local at CO Yes local at CO Yes End Of Life Yes local at CO Yes local at CO No Trouble Service Yes local at CO Yes local at CO No Event Audible Visual Transmission to control panel Error Condition Yes local at CO Yes local at CO No Tamper Yes local at CO Yes local at CO No The 600 6520 95 wireless CO alarm is Listed and compliant with the ANSI UL...

Page 2: ... the polarity illustration in the battery compartment Figure 3 Figure 3 Batteries WARNING XXXXXXXXXXXXX XXXXXX XXXXXXXXXXXXX XXXXXXXXXXXXX X XXXXXXXXXXXX XXXXXXXXXXXXXX X XXXXXXXXXXXX XXXXXXXXXXXXX XX Battery compartment _ _ 4 Slide the alarm body back onto the mounting plate Note The mounting plate will not close if all three batteries are not installed Figure 4 Sliding the alarm on the mounting ...

Page 3: ... into sensor test mode while conducting any tests Placing the control panel into sensor test mode for all testing helps to protect against false alarms and unintentional central station reporting Due to the loudness of the alarm we suggest that you place your fingers over the sounder vent while testing your alarm Caution Continuous exposure to the high sound level of this alarm over an extended pe...

Page 4: ...s Battery type 1 5 VDC alkaline Required batteries Duracell MN 1500 Duracell MX1500 Energizer E91 Sensor Electrochemical Sensor life 7 years Frequency 319 5 MHz Supervisory interval 64 minutes Audible alarm Temporal 4 Alarm response times 70 PPM 60 240 min 150 PPM 10 50 min 400 PPM 4 15 min Dimensions 4 68 x 2 75 x 1 85 in 119 x 70 x 47 mm Storage temperature 4 to 140 F 20 to 60 C Operating enviro...

Page 5: ...ter three days the unit will resume end of life chirps Hush mode will silence the alarm ten times or up to 30 days After 30 days the unit can no longer be hushed Replace the CO alarm immediately The unit will not respond to CO Trouble service alarm Red Alarm LED flashes every 30 seconds One quick beep every 30 seconds Unit is in trouble condition Not applicable Trouble Service events are not commu...

Page 6: ...ld not ordinarily affect a healthy adult Symptoms of CO poisoning The following common symptoms are related to CO poisoning and should be discussed with ALL members of the household Mild exposure Slight headache nausea vomiting fatigue often described as flu like symptoms Medium exposure Severe throbbing headache drowsiness confusion fast heart rate Extreme exposure Unconsciousness convulsions car...

Page 7: ...or use in ordinary indoor locations of family living units It is not designed to measure compliance with Occupational Safety and Health Administration OSHA commercial or industrial standards It is not suitable for installation in hazardous locations as defined in the National Electric Code The installation of this device should not be used as a substitute for proper installation use and maintenanc...

Page 8: ...Alarm procedure 2533 7206 8 600 6520 95 Carbon Monoxide Alarm Manual ...

Reviews: