background image

 

600-6520-95 Carbon Monoxide Alarm Manual 

Figure 1: Alarm features 

Test/Hush button

Alarm sounder

Green Power LED

Red Alarm LED

 

466-2411 REV A  May 2011 

Attention: 

Please take a few minutes to thoroughly read this 

guide which should be saved for future reference and passed 
on to any subsequent owner. 

The 600-6520-95 CO alarm is a replacement for the 60-652-
95. It is compatible with Allegro, Simon 3, Simon XT, Concord 
Express, Concord 3, Concord 4, and NetworX panels. Refer to 
the panel installation instructions for revision verification 
details. Please contact Technical Support for any questions 
regarding compatibility. 

Description 

The 600-6520-95 wireless carbon monoxide (CO) alarm 
monitors the levels of CO gas and gives early warning when 
potentially dangerous levels exist. It does not detect fire, 
smoke, or any other gas. If a dangerous concentration of CO is 
detected by patented and field-proven electrochemical sensor, 
an LED indicator illuminates and an internal siren is activated 
in temporal 4 pattern. The CO alarm also transmits an alarm 
signal to the control panel within 15 seconds of detecting 
dangerous concentration of CO gas. The control panel 
activates its internal siren and reports the alarm condition to 
the central monitoring station (if the system is monitored). The 
CO alarm also detects and locally identifies low battery, wall 
tamper, and sensor end-of-life. Only alarm and low battery are 
transmitted to the control panel. The alarm automatically resets 
when CO is no longer detected. 

Table 1: Event reporting 

Event Audible 

Visual 

Transmission 
to control panel

CO Alarm 

Yes, local at CO 

Yes, local at CO 

Yes 

Low 
Battery 

Yes, local at CO 

Yes, local at CO 

Yes 

End-Of-Life  Yes, local at CO 

Yes, local at CO 

No 

Trouble/ 
Service 

Yes, local at CO 

Yes, local at CO 

No 

Event Audible 

Visual 

Transmission 
to control panel

Error 
Condition 

Yes, local at CO 

Yes, local at CO 

No 

Tamper 

Yes, local at CO 

Yes, local at CO 

No 

 

The 600-6520-95 wireless CO alarm is Listed and compliant 
with the ANSI/UL 2034 standard for CO alarms. It is intended 
for residential indoor dwelling unit applications and other areas 
approved by the authority having jurisdiction (AHJ). It is not 
intended for use in industrial applications. 

WARNING: 

After seven years from initial power up, this alarm 

will beep two times every 30 seconds to indicate that it is time 
to replace the alarm. Replace the alarm immediately! It will not 
detect CO in this condition. 

To help identify the date to replace the alarm, an area has 
been reserved on the side of the alarm. Write the “replace by” 
date (seven years from power up) with a permanent marker in 
the area provided. 

Alarm location 

CO alarms should be mounted in or near bedrooms and living 
areas. We recommend that you install an alarm on each level 
of your home. 

When choosing your installation locations, make sure you can 
hear the alarm from all sleeping areas. If you install only one 
CO alarm in your home, install it near bedrooms, not in the 
basement or furnace room. 

Place the alarm out of reach of children. Under no 
circumstances should children be allowed to handle the CO 
alarm. 

Figure 2: Recommended locations 

Dining

Kitchen

Bedroom

Bedroom

Bedroom

Living room

 

Locations to avoid 

Improper location can affect the sensitive electronic 
components in this alarm. To avoid causing damage to the 
unit, to provide optimum performance, and to prevent 
unnecessary nuisance alarms: 

Summary of Contents for 600-6520-95

Page 1: ...Yes local at CO Yes local at CO Yes Low Battery Yes local at CO Yes local at CO Yes End Of Life Yes local at CO Yes local at CO No Trouble Service Yes local at CO Yes local at CO No Event Audible Visual Transmission to control panel Error Condition Yes local at CO Yes local at CO No Tamper Yes local at CO Yes local at CO No The 600 6520 95 wireless CO alarm is Listed and compliant with the ANSI UL...

Page 2: ... the polarity illustration in the battery compartment Figure 3 Figure 3 Batteries WARNING XXXXXXXXXXXXX XXXXXX XXXXXXXXXXXXX XXXXXXXXXXXXX X XXXXXXXXXXXX XXXXXXXXXXXXXX X XXXXXXXXXXXX XXXXXXXXXXXXX XX Battery compartment _ _ 4 Slide the alarm body back onto the mounting plate Note The mounting plate will not close if all three batteries are not installed Figure 4 Sliding the alarm on the mounting ...

Page 3: ... into sensor test mode while conducting any tests Placing the control panel into sensor test mode for all testing helps to protect against false alarms and unintentional central station reporting Due to the loudness of the alarm we suggest that you place your fingers over the sounder vent while testing your alarm Caution Continuous exposure to the high sound level of this alarm over an extended pe...

Page 4: ...s Battery type 1 5 VDC alkaline Required batteries Duracell MN 1500 Duracell MX1500 Energizer E91 Sensor Electrochemical Sensor life 7 years Frequency 319 5 MHz Supervisory interval 64 minutes Audible alarm Temporal 4 Alarm response times 70 PPM 60 240 min 150 PPM 10 50 min 400 PPM 4 15 min Dimensions 4 68 x 2 75 x 1 85 in 119 x 70 x 47 mm Storage temperature 4 to 140 F 20 to 60 C Operating enviro...

Page 5: ...ter three days the unit will resume end of life chirps Hush mode will silence the alarm ten times or up to 30 days After 30 days the unit can no longer be hushed Replace the CO alarm immediately The unit will not respond to CO Trouble service alarm Red Alarm LED flashes every 30 seconds One quick beep every 30 seconds Unit is in trouble condition Not applicable Trouble Service events are not commu...

Page 6: ...ld not ordinarily affect a healthy adult Symptoms of CO poisoning The following common symptoms are related to CO poisoning and should be discussed with ALL members of the household Mild exposure Slight headache nausea vomiting fatigue often described as flu like symptoms Medium exposure Severe throbbing headache drowsiness confusion fast heart rate Extreme exposure Unconsciousness convulsions car...

Page 7: ...or use in ordinary indoor locations of family living units It is not designed to measure compliance with Occupational Safety and Health Administration OSHA commercial or industrial standards It is not suitable for installation in hazardous locations as defined in the National Electric Code The installation of this device should not be used as a substitute for proper installation use and maintenanc...

Page 8: ...Alarm procedure 2533 7206 8 600 6520 95 Carbon Monoxide Alarm Manual ...

Reviews: