background image

P/N 46-547 • REV   • October 2012 

 

Learn Mode Rate of Rise Heat Sensors 

Installation Instructions 

Introduction 

This is the 

Learn Mode Rate-of-Rise Heat Sensors 

Installation  Instructions. 

The sensors (

Figure 1

) combine a 

Chemetron heat detector and a learn mode wireless 
transmitter in one unit. A built-in thermostat trips the transmitter 
when the temperature at the sensor location reaches about 
135°F (57°C) or 200°F (94°C), depending on the model 
installed. 

135°F models 

60-460-95/NX-495, 60-460-95-LB 

200°F models 

60-460-01-95/NX-496 

Figure 1. Sensor models 

 

Since many fires grow rapidly in intensity causing a rapid 
temperature increase, the thermostat also trips the transmitter 
if the temperature rises 15°F (8°C) or more per minute. 

All models can be powered by one 9-volt alkaline battery that 
can last 12 to 18 months, or by  one 9-volt lithium battery that 
can last up to twice as long. 

Note

: Battery  life depends on how often the sensor transmits 

signals, but is more dependent on the temperature of the 
installation environment. Alkaline batteries self-discharge more 
rapidly when used in high temperature environments. 

When the battery voltage gets low, the sensor transmits a low 
battery signal to the panel. The panel then activates sirens with 
trouble beeps to notify the customer that the sensor battery 
must be replaced 

Caution: 

SX-V  Special panels must have software version 8.0 

or later installed for correct response from the sensors. Do not 
install Learn Mode Rate of Rise Heat sensors if the panel an 
earlier software version. Contact Interlogix technical support at 
888.437.3287 for assistance. 

Installation 

Use the following installation guidelines: 

• 

Heat sensors should be installed to provide property 
protection. Reliance should not be placed on heat 
detectors for life safety. Where life safety is involved, 
smoke sensors must also be installed. 

• 

The sensors allow for normal temperature fluctuations, 
however, ceiling temperatures should not exceed 100°F 
(37°C) when installing 135°F models, or 150°F (66°C) 
when installing 200°F models. 

• 

Mount the sensor in a central location of the area to be 
protected, either on the ceiling or on a wall. 

• 

If mounting on a ceiling, the sensor must be at least 4 in. 
(10 cm) away from any walls. 

• 

If mounting on a wall, the top of the sensor must be within 
4 to 6 in. (10 to 15 cm) of the ceiling. 

• 

The UL maximum spacing allowance of the sensor is 50 x 
50 ft. (15 x 15 m). Refer to the NFPA  Standard 72 for 
application requirements. 

Reviews: