BATTERY CHARGER
BATTERY CHARGER
4
PB-6207
Equipment Setting and Checking
Equipment Setting and Checking
1. Address Setting
1) Set the equipment numbers for each deciding condition using the rear panel DIP switch.
- If the equipment number is not set-up or is incorrect, ‘id err’ is displayed on the LED segment.
- If the number is already in-use, the system will not function properly.
- Please check the equipment number set-up status. (can be expanded up to 20 equipments)
2) Setting should be as table below, and if data number is added to switch which is On, it will be the
equipment number.
(Ex: when number 1 and 3 is ON, 1 and 4 is added, so equipment number will be 5.)
2. TERMINATION Switch (LOAD/OPEN) Setting
1) For the system linked by using RS-485 communication interface, it is necessary to set the termination
switch (LOAD/OPEN) on the rear panel to stabilize data transfer.
2) Set the termination switch to LOAD only for the first and last-numbered equipment units.
All others must be set to OPEN.
※
Caution: Communication error may occur if setting is performed incorrectly.
Equipment 1
S/W: LOAD
OUT
Equipment 2
S/W: OPEN
IN
OUT
Equipment 3
S/W: OPEN
IN
OUT
Equipment N
S/W: LOAD
IN
Pin No.
1
2
3
4
5
Data
1
2
4
8
16
1
ON
2
ON
3
ON
ON
4
ON
Address
5
ON
ON
15
ON
ON
ON
ON
16
ON