2.3.2 Preparation
Mains connection for a PSI 9000 2U series device is done using the included 2-meter 3-pole mains cord. If a dif-
ferent AC wiring is required, make sure that the other cable has a cross section of at least 2.5 mm² (AWG 12).
Dimensioning of the DC wiring to the load/consumer has to reflect the following:
•
The cable cross section should always be specified for at least the maximum current of the
device.
•
Continuous operation at the approved limit generates heat which must be removed, as well as
voltage loss which depends on cable length and heating. To compensate for these the cable
cross section should be increased and the cable length reduced.
2.3.3 Installing the device
•
Select a location for the device that makes the connection to the load as short as possible.
•
Leave a minimum of 30cm space behind the equipment for ventilation.
A device in a 19” housing should be mounted on suitable rails and installed in 19” racks or cabinets. The depth
of the device and its weight must be taken into account. The handles on the front are for sliding in and out of the
cabinet. Slots on the front plate are provided for anchoring the device (screws are not included).
With all models of this series, mounting brackets are included to convert the front plate from a rack to desktop.
To do this the 19” mounting brackets can be removed after loosening the screws on the front grips and replacing
them with included pieces.
Acceptable and unacceptable installation positions:
Standing surface