GENERAL DESCRIPTION
The resettable call point is a device that allows the general user to trigger an alarm in case of a fire emergency occurrence in the protected
site. This particular model can be successively reset and made ready for other activations as needed.
REQUIREMENTS
This device works only with control panels employing the Vega
protocol.
VISUAL INDICATOR LIGHT
This device is equipped with a visual indicator light (picture 1) providing information on its status.
Since this indicator is controlled by the control panel, consult your control panel
’
s documentation
or your system supplier for further specific information.
SHORT CIRCUIT ISOLATORS
This device is equipped with short circuit isolators.
Isolators limit the consequences that can be caused by short circuits on the analogue loop.
Remember that the
“
shorted
“
loop section is switched out by the isolators as long as the short
persists.
INSTALLATION NOTES
This device must be used only with control panels employing Vega protocol.
Follow recognised codes of practice.
This device is intended only for indoor use.
Disconnect the loop before installing the devices.
Wire the loop connectors to the correct device
’
s terminal blocks: follow precisely the instructions given in this manual.
Electrostatic sensitive device: observe precautions when handling.
GIVING THE DEVICE AN ADDRESS
This call point must be given an address; you have two options:
-
Programming the address through a hand
-
held Vega programming tool connected to the call
point
’
s front block
.
Consult the Vega programming tool manual for further instructions on how to operate.
-
Performing automatic addressing from the control panel
.
This can be done if the control panel you are using has this feature and after you have physically
installed all the devices on the loop. Consult your control panel
’
s manual on how to operate.
INSTALLATION
-
POSITIONING
1)
Select the installation position.
2)
The call point
’
s installation base has 3 openings, 2 of them are suitable for conduit adaptor
installation (picture 2).
3)
Introduce the loop cables into the inside of the installation base.
4)
Fix the installation base to the wall; use the supplied screws and anchors (picture 3).
5)
Give a suitable length to the loop
’
s cables inside the base.
TI
-
002226
INTELLIGENT ANALOGUE RE
-
SETTABLE MANUAL CALL POINT
WITH SHORT CIRCUIT ISOLATOR