IntelliSense FlexGuard-Plus FG-930 Installation Instructions Download Page 2

SPECIFICATIONS:

Range:

30' (9 m) maximum

Alarm relay:

Form C

500 mA max

24 VDC max

Voltage  supervision:

Performance remains reliable

even if the voltage decreases.  If

the input voltage drops below

approximately 6.0 VDC, a forced

alarm occurs.

Tamper switch:

Form A (NC)

50 mA, 30 VDC

Power  requirements:

8 - 14 VDC

30 mA typical at 12 VDC

35 mA max (worst case)

Use the FG-700 or FG-701 Glassbreak Simulator from IntelliSense to test the

FG-930 detector.  Point the front of the FG-700/701 directly at the FG-930

sensor when testing.

Activate the simulator in MANual mode at the farthest point of the glass to

be  protected  (30'  maximum).    If  the  green  LED  (DS1)  on  the  detector

flashes, the audio technology will detect breaking glass at that distance.

Test the flex technology by carefully striking the glass with a cushioned tool.

If the yellow LED on the detector flashes, the flex technology will be sensitive

enough to detect a blow to the glass at that distance.

TESTING  THE  FG-930

Switch the FG-700/701 simulator to the FLEX mode, press the red start

button,    and  generate  a  flex  signal  by  carefully  striking  the  glass.    The

simulator will automatically generate a burst of glass-break sound, and the

red LED (DS3) on the FG-930 should light to indicate an alarm condition.

See the FG-700/701 operating instructions for additional testing information.

Important:

  The FG-930 should be tested at least 

once each year

to ensure proper operation.

To ensure maximum protection against false alarms, activate any device in

the  area  that  may  automatically  cycle:  pumps,  generators,  heating/air

conditioning units, etc.  If the cycling devices trigger an alarm, mount the

unit in a different location.

There is no need to relocate the detector if the cycling only briefly triggers

the flex technology (the yellow LED flashes).

FINAL  TESTING

ALARM  MEMORY

The FG-930 is equipped with a

latching circuit for the alarm LED.

When the latching circuit is

activated, an alarm condition will

make the red alarm LED on the

unit latch on.  This feature is

particularly helpful in determining

which unit alarmed in a multiple

detector installation.

To activate the latching circuit,

install a jumper at position 

W2

 on

the printed circuit board (refer to

Figure 3).  To reset the latched

alarm LED, remove then replace

the jumper on 

W2

, or remove

then restore power to the

detector.

Note:

 The latching circuit has

absolutely no effect on the

alarm relay.  The alarm relay

will continue to function as

normal.

Figure 3 Testing the FG-930

RF  immunity:

30 volts per meter

1 MHz - 1000 MHz

Dimensions:

3.9" H x 2.4" W x 0.79" D

(98 mm x 61.5 mm x 20 mm)

Weight:

3 oz (85 g)

Operating  temperature:

32

o

 to 120

o

 F (0

o

 to 49

o

 C)

Glass  types:

1/8", 3/16", and 1/4" plate;

1/4" laminated, wired, and

tempered;  minimum size

10-7/8" x 10-7/8", single pane

Copyright 2001 IntelliSense.

5-051-278-00             Rev E

Accessories:

FG-700 Glassbreak Simulator

FG-701 Glassbreak Simulator

Approvals/Listings:

UL listed

C-Tick

Alarm  duration:

4 seconds

Important:

  The FG-930 must be connected to a UL listed

power supply or control unit capable of providing a 

minimum

of four hours

 of standby power.

IntelliSense and FlexGuard are registered

trademarks of Honeywell, Inc.

All Rights Reserved.

Reviews: