SPECIFICATIONS 

ELECTRICAL & WIRELESS

BATTERY TYPE

Requires one CR123(A) Lithium Battery

BATTERY LIFE

Designed for 10 Year Life  
 (under default settings)
Non-Volatile Memory (saves all 

 settings regardless of battery state)

 

Blink Warning @10% Life

RANGE

80’ line of site w/o obstruction (walls) 

40’ with obstruction (walls/floors)

FREQUENCY

915 MHz ISM Band  

WIRELESS LINKING

Simple 3 sec. Push Button Process

SECURITY

All Wireless Data is Encrypted

ENVIRONMENTAL

OPERATING TEMP

32°F to 122°F (0°C to 50°C)

RELATIVE HUMIDITY

0-95% Non-Condensing, 

Indoor Use Only

CODE COMPLIANCE

These sensors can be used to meet 
ASHRAE 90.1, IECC, & Title 24 energy 
code requirements.

PHYSICAL

SIZE

2.875” H x 2.75” W x 3.25”D 

(7.30 x 6.98 x 8.25 cm)

WEIGHT 

4.75 oz.

COLOR

White

LED INDICATION

Motion Detection (when in Test Mode)

 

Wireless Linking (Pairing)

OPERATION

OPERATING MODES

Occupancy & Vacancy Modes -

Configured on Linked Controller

COMPATIBLE LOAD CONTROLLERS

 

ILC-

SWX-851 Wall Switch 

ILC-

SWX-950 Series Power Packs

WIRELESS TEST MODE

 Button Toggles On/Off

Wirelessly Linked Loads

COVERAGE TEST MODE

White LED Illuminates Upon Detected
 Occupancy 

TIME DELAY OPTIONS

Configured at Load Controller(s)

1, 5, 10, 15, 20, 30 min.

WIRELESS 

WIDEVIEW & HALLWAY 

OCCUPANCY SENSOR

BATTERY POWERED

OVERVIEW 

The 

Intelligent Lighting Controls 

wireless wide view and hallway occupancy 

sensors are a simple, yet reliable battery powered control solution. Preferred by 
contractors for their flexible mounting methods, 

ILC

 wireless sensors greatly 

reduce total installation time and wireless pairing fuss. Requiring just a few 
seconds per device, 

ILC

 wireless sensors can be linked to one or more wireless 

load controllers (such as the 

ILC-

SWX-851

 wireless wall switch, or a 

ILC-

SWX-950 

series wireless power pack). Additionally, these sensors can be 

configured to work in applications with other wireless or wired ceiling, corner, or 
hallway sensors 
to provide extended coverage in large or irregularly shaped spaces. As with all 

ILC 

products, the latest passive infrared technology and digital signal processing 
techniques are used to provide unmatched occupant detection performance and 
energy savings.

BASIC OPERATION 

Sensors detect movement in the infrared energy that radiates from occupants as 
they move within the device’s field-of-view. Once occupancy is detected, the 
sensor immediately signals a wirelessly linked load controller (e.g. power pack) to 
switch on or dim up the connected lighting. At regular intervals, the sensor will 
retransmit its latest occupancy status such that the load controller can keep lights 
on for occupants during brief periods of inactivity, while returning the space to an 
energy saving lights off (or dim) state once no longer occupied.