background image

INST

ALL
ATIONGUIDE

GDMS 2

INTELLIGAS

Gas safety & control systems

Introduction

Thank you for choosing an Intelligas product. Please follow these instructions to ensure a safe, functional and 
long-lasting installation.

This information is important and should be read and understood before attempting installation.   

If you are unsure of the terminations and their design voltages or function then refer to this guide or our technical 
support line, you can call 02381 290444 or you can text 07952269791 and we’ll get back to you as soon as we’re 
available.

Siting the panel

Choose a suitable mounting position for the control unit.  Mount the unit away from sources of extreme heat.  Ensure the panel is 
placed in a position where mechanical damage is unlikely and where it can be easily accessed for use and maintenance.

Fix the panel using the marked enclosure holes only.  Take care not to damage the internal wiring or PCB of the unit when drilling. 

Under no circumstances should wiring be routed behind the PCB of the control panel.  

Control panel supply

All our control panels (except the KVM-SF) should be supplied via a fused spur connection unit.  The fuse should be changed to one 
that’s rated at 5amps.

KVM-SF ONLY

 if the panel is supplying the fans directly from the PCB then it should be supplied via a 16amp single phase isolator.  

If the panel is controlling Inverters and only the output signals are being used then, as above, the panel should be supplied by a 5amp 
fused spur. 

intelligas.co.uk

Reviews: