4.  SETUP MODE 

Note: Configuration must be completed before adjusting Setup parameters. 
First select Setup mode from Select mode (refer to section 2). The Setup LED        
will light while in Setup mode. Press        to scroll through the parameters,  
then press        or        to set the required value. 
To exit from Setup mode, hold down        and press        to return to Select mode. 
Note: Parameters displayed depends on how instrument has been configured. 

 

Parameter 

Lower 

Display 

Upper Display Adjustment 

Range & Description 

Default 

Value 

Limit Setpoint value 

Scaled Range Minimum to 

scaled Range Maximum 

R/max if 

=

  

R/min if 

=

  

Limit Hysteresis 

*

*

*

*

1 LSD to full span in display units, 

on the safe side of the limit SP 

Input Filter Time Constant 

OFF or 0.5 to 100.0 secs 

(see 

CAUTION

 note below

.

High Alarm 1 value 

 

 

 

 

R/max 

Low Alarm 1 value 

Scaled Range Minimum to 

scaled Range Maximum 

R/min 

Deviation Alarm 1 Value 

±

Span from SP in display units 

Band Alarm 1 value 

1 LSD to span from setpoint 

Alarm 1 Hysteresis 

!

!

!

!

1 LSD to full span in display units 

High Alarm 2 value 

 

 

 

 

R/max 

Low Alarm 2 value 

Scaled Range Minimum to 

scaled Range Maximum 

R/min 

Deviation Alarm 2 Value 

±

Span from SP in display units 

Band Alarm 2 value 

1 LSD to span from setpoint 

Alarm 2 Hysteresis 

!

!

!

!

1 LSD to full span in display units 

Setup Lock Code 

)

)

)

)

0 to 9999 

Note: Operator mode screens follow, without exiting from Setup mode

 

CAUTION:

 An excessively large filter time could significantly delay 

detection of a limit condition. Set this value to the minimum required 
to remove noise from the process variable
 

 
 

5.  PRODUCT INFORMATION MODE 

First select Product information mode from Select mode (refer to section 2). 
Press       to view each parameter. To exit from Product Information mode, 
hold down        and press         to return to Select mode. 
Note: These parameters are all read only. 

 

Parameter 

Lower 

Display 

Upper 

Display 

Description 

Input type 

%

%

%

%

#

#

#

#

Universal input 

Option 1 type (fixed) 

*

*

*

*

Latching Limit Relay 

No option fitted 

*

*

*

*

Relay output 

SSR drive output 

Triac output 

Option 2 module type 
fitted 

Linear DC voltage / current output 

No option fitted 

*

*

*

*

Relay output 

SSR drive output 

Linear DC voltage / current output 

Option 3 module type 
fitted 

)

)

)

)

Transmitter power supply 

No option fitted 

&

&&

&

RS485 communications 

Auxiliary Option A 
module type fitted 

Digital Input for remote reset 

Firmware type 

+,

+,

+,

+,

Value displayed is firmware type number 

Firmware issue 

%$$

%$$

%$$

%$$

Value displayed is firmware issue number 

Product Revision Level 

Value displayed is Product Revision level 

Date of manufacture 

Mm

Mm

Mm

Mm

Manufacturing date code (mmyy) 

Serial number 1 

First four digits of serial number 

Serial number 2 

Middle four digits of serial number 

Serial number 3 

Last four digits of serial number 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

6.  ERROR/FAULT INDICATIONS 

 

Parameter 

Upper 

Display 

Lower 

Display 

Description 

Instrument 
parameters are in 
default conditions 

 

Configuration & Setup required. This screen is 

seen at first turn on, or if hardware 

configuration has been changed. Press        to 

enter the Configuration Mode, next press         

or       to enter the unlock code number, 

then press        to proceed 

----

.

..

.

Normal 

Process variable input > 5% over-range 

Input Over Range 

Normal 

----

.

..

.

as above if Display Strategy = 

 

---- .

..

.

Normal 

Process variable input > 5% under-range 

Input Under 
Range 

Normal 

---- .

..

.

as above if Display Strategy = 

 

/

/

/

/

Normal 

Break detected in process variable input 

sensor or wiring 

Input Sensor 
Break 

Normal 

/

/

/

/

as above if Display Strategy = 

 

Option 1 Error 

Option 1 module fault 

Option 2 Error 

Option 2 module fault 

Option 3 Error 

Option 3 module fault 

Option A Error 

 

Option A module fault 

Option B Error 

Option B not used on Limit Controllers 

this error is shown if any module is fitted 

 

7.  OPERATOR MODE 

This mode is entered at power on, or accessed from Select mode (see section 2). 
Note: All Configuration mode and Setup mode parameters must be set as 
required before starting normal operations. 
Press        to scroll through the parameters. 

Upper 
Display 

Lower 

Display 

Display Strategy and 

When Visible 

Description 

PV Value 

Limit SP 

Value 

 

(initial screen) 

PV and Limit Setpoint values 

Read only 

Limit SP 
Value 

(Blank) 

 

(initial screen) 

Limit Setpoint value 

Read only 

 or 

   

(Blank) 

or PV 
Value 

 

(Initial Screen)

Displays 

 and PV if Limit 

Output is active or 

 and blank 

if not active. 

Read only 

High Limit 
Hold 

 

 

 

Highest PV value since this 

parameter was last reset. 

To reset, press        for 5 seconds, 

display = 

0000

  when reset 

Low Limit 
Hold 

 

 

 

Lowest PV value since this 

parameter was last reset. 

To reset, press        for 5 seconds, 

display = 

0000

  when reset 

Exceed Time 
Value 

 

Always available 

Format mm.ss to 99.59 

then mmm.s 

(10 sec increments) 

Shows 

----

.

..

.

 if  999.9 

Accumulated time of Limit SP  

exceed conditions since this 

parameter was last reset. 

To reset, press        for 5 seconds, 

display = 

0000

  when reset 

Active Alarm 
Status 

When one or more 
alarms are active. 

ALM indicator 
will also flash

L

 

     Alarm 2 active 

       Alarm 1 active 

L

    

        Annunciator active 

Exceed Condition 

An Exceed Condition is when the Process Variable exceeds the Limit Setpoint value 
(i.e. PV > SP when set for high limit action, PV < SP for low limit action). The             
LED is on during this condition, and is extinguished once it has passed. 

Limit Output Function

 

 

Limit Output relay(s) de-energise whenever an Exceed condition occurs, causing 
the process to shut down. The       LED is on when the relay is de-energised. 
The relay remains latched off even if the Exceed condition is no longer present. 
Only giving a reset instruction (after the exceed condition has passed) will re-
energise the relay, allowing the process to continue. The       LED then turns off. 

Limit Annunciator Outputs 

 

An Annunciator output will activate when an Exceed condition occurs, and will 
remain active until a reset instruction is received, or the Exceed condition has 
passed. Unlike the Limit Output, an Annunciator can be reset even if the Exceed 
condition is present. When an Annunciator is active, the       LED will flash and the 
Alarm Status screen is available. 

 

Resetting Limit Outputs & Annunciators

 

A reset instruction can be given by pressing the        key, via the Digital Input (if 
fitted) or via a Comms command if an RS485 Communications module is fitted. 
Annunciators will deactivate. Limit Outputs will only re-energise if the Exceed 
condition has passed. 

 

CAUTION:

 Ensure that the cause of the Exceed condition has been 

rectified before resetting the Limit Output

 
 

8.  SERIAL COMMUNICATIONS 

Refer to the full user guide (available from your supplier) for details. 

 
 
 
 
 

9.  SPECIFICATIONS 

UNIVERSAL INPUT 

Thermocouple 
Calibration: 

±

0.1% of full range, 

±

1LSD (

±

1°C for Thermocouple CJC). 

BS4937, NBS125 & IEC584. 

PT100 Calibration: 

±

0.1% of full range, 

±

1LSD. 

BS1904 & DIN43760 (0.00385

/

/°C). 

DC Calibration: 

±

0.1% of full range, 

±

1LSD. 

Sampling Rate: 

4 per second. 

Impedance: 

>10M

 resistive, except DC mA (5

) and V (47k

 ). 

Sensor Break 
Detection: 

Thermocouple, RTD, 4 to 20 mA, 2 to 10V and 1 to 5V ranges 
only. Limit outputs turn off (goes into Exceed condition), high 
alarms activate for thermocouple/RTD sensor break, low 
alarms activate for mA/V DC sensor break.
 

Isolation: 

Isolated from all outputs (except SSR driver). 

 

Universal input must not be connected to operator accessible 
circuits if relay outputs are connected to a hazardous voltage 
source.  Supplementary insulation or input grounding would 
then be required. 

DIGITAL INPUT

 

Volt-free(or TTL): 

Open(2 to 24VDC) =No Reset. 
Closed(<0.8VDC) = Reset (edge triggered). 

Isolation: 

Reinforced safety isolation from inputs and other outputs. 

OUTPUTS 

 

Limit Relay 

 

Contact Type & 
Rating: 

Latching limit control relay. Single pole double throw (SPDT); 
5A resistive at 120/240VAC. Slot 1 position fixed for this 
function, optional function for Slot 2 & 3 relay modules, 

Lifetime: 

>100,000 operations at rated voltage/current. 

Isolation: 

Basic Isolation from universal input and SSR outputs. 

Alarm Relays 

 

Contact Type & 
Rating: 

Slot 2 or 3 position non-latching alarm relay. 
Single pole double throw (SPDT); 2A resistive at 120/240VAC. 

Lifetime: 

>500,000 operations at rated voltage/current. 

Isolation: 

Basic Isolation from universal input and SSR outputs. 

SSR Driver 

 

Drive Capability: 

SSR drive voltage >10V into 500

 min. 

Isolation: 

Not isolated from universal input or other SSR driver outputs. 

Triac 

 

Operating Voltage:  20 to 280Vrms (47 to 63Hz). 

Current Rating: 

0.01 to 1A (full cycle rms on-state @ 25°C); 
derates linearly above 40°C to 0.5A @ 80°C. 

Isolation: 

Reinforced safety isolation from inputs and other outputs. 

DC 

 

Resolution: 

8 bits in 250mS (10 bits in 1s typical, >10 bits in >1s typical). 

Isolation: 

Reinforced safety isolation from inputs and other outputs. 

Transmitter PSU 

 

Power Rating: 

20 to 28V DC (24V nominal) into 910

 minimum resistance. 

Isolation: 

Reinforced safety isolation from inputs and other outputs. 

SERIAL COMMUNICATIONS 

Physical: 

RS485, at 1200, 2400, 4800, 9600 or 19200 bps. 

Protocols: 

Selectable between Modbus and West ASCII. 

Isolation: 

Reinforced safety isolation from all inputs and outputs. 

OPERATING CONDITIONS (FOR INDOOR USE) 

Ambient 
Temperature: 

0°C to 55°C (Operating), –20°C to 80°C  (Storage). 

Relative Humidity: 

20% to 95% non-condensing. 

Supply Voltage and 
Power: 

100 to 240VAC 

±

10%, 50/60Hz, 7.5VA 

(for mains powered versions), or 
20 to 48VAC 50/60Hz 7.5VA or 22 to 65VDC 5W 
(for low voltage versions). 

ENVIRONMENTAL 

Standards: 

CE, UL, ULC & FM 3545, 1998 

EMI: 

Complies with EN61326 (Susceptibility & Emissions). 

Safety 
Considerations: 

Complies with EN61010-1 & UL3121. 
Pollution Degree 2, Installation Category II. 

Front Panel Sealing:  To IP66 (IP20 behind the panel). 

PHYSICAL 

Front Bezel Size: 

1

/

16 

Din = 48 x 48mm, 

1

/

8

 Din = 96 x 48mm, 

1

/

4

 Din = 96 x 96mm. 

Depth Behind Panel: 

1

/

16 

Din = 110mm, , 

1

/

8

 & 

1

/

4

 Din = 100mm. 

Weight: 

0.21kg maximum. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

Reviews: