DIN LIMIT CONTROLLERS
CONCISE PRODUCT MANUAL (59333-2)
CAUTION:
Installation should be only performed by
technically competent personnel. Local Regulations
regarding electrical installation & safety must be observed.
1. INSTALLATION
The models covered by this manual have three different DIN case sizes (refer to
section 9). Some installation details vary between models. These differences have
been clearly shown.
Note: The functions described in sections 2 thru 8 are common to all models.
Installing Option Modules
1
/
16
Din Size Instruments
CPU PCB
Option Module 1
(Fixed Limit Relay)
Option Module 2
Mounting Struts
Option Module A
Option Module 3
PSU PCB
1
/
8
&
1
/
4
Din Size Instruments
CPU PCB
Option Module B
(not used on Limit
Controllers)
Option Module 2
Option Module 1
(Fixed Limit Relay)
Mounting Struts
Option Module A
Option Module 3
PSU PCB
To access module A, first detach the PSU and CPU boards from the front by lifting
first the upper, and then lower mounting struts. Gently separate the boards.
a.
Plug the required option modules into the correct connectors, as shown below.
b.
Locate the module tongues in the corresponding slot on the opposite board.
c.
Hold the main boards together while relocating back on the mounting struts.
d.
Replace the instrument by aligning the CPU and PSU boards with their guides
in the housing, then slowly push the instrument back into position.
Note: Option modules are automatically detected at power up.
Option Module Connectors
1
/
16
Din Size Instruments
Option Slot 1
(Fixed Limit
Relay)
Option Slot 2
Connector
PL4A
Option Slot A
Connectors
PL5 & PL6
Option Slot 3
Connector
PL4B
1
/
8
&
1
/
4
Din Size Instruments
Option Slot B
(not used on
Limit Controllers)
Option Slot 2
Connector
PL4A
Option Slot 1
(Fixed Limit
Relay)
Option Slot A
Connectors
PL5 & PL6
Option Slot 3
Connector
PL4B
Panel-Mounting
The mounting panel must be rigid, and may be up to
6.0mm (0.25inch) thick. Cut-out sizes are:
Cut-Out Dim A
Cut-Out Dim B
1
/
16
&
1
/
8
Din = 45mm
1
/
16
Din = 45mm
1
/
4
Din = 92mm
1
/
8
&
1
/
4
Din = 92mm
For n multiple instruments mounted side-by-side, cut-out
A is 48n-4mm (
1
/
16
&
1
/
8
Din) or 96n-4mm (
1
/
4
Din)
Tol0.5, -0.0mm
Mounting Panel
Instrument
Housing
Ratchets
Gasket
Slide mounting clamp
over the instrument
housing towards rear face
of mounting panel until
the tongues engage in
ratchets and instrument is
clamped in position.
Hold instrument firmly in
position (apply pressure
to bezel only)
CAUTION:
Do not remove the panel gasket; it is a seal against dust and
moisture.
Rear Terminal Wiring
USE COPPER CONDUCTORS (EXCEPT FOR T/C INPUT)
Single Strand wire gauge: Max 1.2mm (18SWG)
1
/
16
Din Size Instruments
1
/
8
&
1
/
4
Din Size Instruments
These diagrams show all possible option combinations. The actual
connections required depends on the exact model and options fitted.
CAUTION:
Check information label on housing for correct operating
voltage before connecting supply to Power Input
Fuse: 100 – 240V ac – 1amp anti-surge
24/48V ac/dc – 315mA anti-surge
Note: At first power-up the message
is displayed, as described in
section 6 of this manual. Access to other menus is denied until configuration
mode is completed
2. SELECT MODE
Select mode is used to access the configuration and operation menu functions.
It can be accessed at any time by holding down and pressing .
In select mode, press or to choose the required mode, press to enter.
An unlock code is required to prevent unauthorised entry to Configuration, & Setup
modes. Press or to enter the unlock code, then press to proceed.
Mode
Upper
Display
Lower
Display
Description
Default
Unlock
Codes
Operator
Normal operation
None
Set Up
Tailor settings to the application
Configuration
Configure the instrument for use
Product Info
Check manufacturing information
None
Note: The instrument will always return automatically to Operator mode if
there is no key activity for 2 minutes.
3. CONFIGURATION MODE
First select Configuration mode from Select mode (refer to section 2).
Press to scroll through the parameters, then press or to set the required
value. Press to accept the change, otherwise parameter will revert to previous
value. To exit from Configuration mode, hold down and press , to return to
Select mode.
Note: Parameters displayed depends on how instrument has been configured.
Refer to user guide (available from your supplier) for further details.
Parameters marked * are repeated in Setup Mode.
Parameter
Lower
Display
Upper
Display
Adjustment range & Description
Default
Value
Input
Range/Type
See following table for possible codes
Code Input Type &
Range
Code
Input Type &
Range
Code Input Type &
Range
bC
bC
bC
bC
B: 100 - 1824 ºC
LLLL
.
C
C
C
C
L: 0.0 - 537.7 ºC
bF
bF
bF
bF
B: 211 - 3315 ºF
LLLL
.
F
F
F
F
L: 32.0 - 999.9 ºF
P24F
P24F
P24F
P24F
PtRh20% vs 40%:
32 - 3362 ºF
CC
CC
CC
CC
C: 0 - 2320 ºC
NC
NC
NC
NC
N: 0 - 1399 ºC
PTC
PTC
PTC
PTC
Pt100: –199 - 800 ºC
CF
CF
CF
CF
C: 32 - 4208 ºF
NF
NF
NF
NF
N: 32 - 2551 ºF
PtF
PtF
PtF
PtF
Pt100: –328 - 1472 ºF
JC
JC
JC
JC
J: –200 - 1200 ºC
rC
rC
rC
rC
R: 0 - 1759 ºC
P
P
P
Pt
tt
t
.
C
C
C
C
Pt100: –128.8 - 537.7 ºC
JF
JF
JF
JF
J: –328 - 2192 ºF
rF
rF
rF
rF
R: 32 - 3198 ºF
Pt
Pt
Pt
Pt
.
F
F
F
F
Pt100: –199.9 - 999.9 ºF
j
j
j
j
.
C
C
C
C
J: –128.8 - 537.7 ºC
SC
SC
SC
SC
S: 0 - 1762 ºC
0 - 20 mA DC
j
j
j
j
.
F
F
F
F
J: –199.9 - 999.9 ºF
SF
SF
SF
SF
S: 32 - 3204 ºF
4 - 20 mA DC
KC
KC
KC
KC
K: –240 - 1373 ºC
tC
tC
tC
tC
T: –240 - 400 ºC
0 - 50 mV DC
KF
KF
KF
KF
K: –400 - 2503 ºF
tF
tF
tF
tF
T: –400 - 752 ºF
.
10 - 50 mV DC
k
k
k
k
.
C
C
C
C
K: –128.8 - 537.7 ºC
t
tt
t
.
C
C
C
C
T: –128.8 - 400.0 ºC
0 - 5 V DC
K
K
K
K
.
F
F
F
F
K: –199.9 - 999.9 ºF
t
tt
t
.
F
F
F
F
T: –199.9 - 752.0 ºF
1 - 5 V DC
LC
LC
LC
LC
L: 0 - 762 ºC
0 - 10 V DC
LF
LF
LF
LF
L: 32 - 1403 ºF
P24C
P24C
P24C
P24C
PtRh20% vs. 40%:
0 - 1850 ºC
2 - 10 V DC
Note: Decimal point shown in table indicates temperature resolution of 0.1°
Parameter
Lower
Display
Upper
Display
Adjustment range & Description
Default
Value
Scale Range
Upper Limit
Scale Range Lower Limit +100
to Range Maximum
Range max
(Lin=1000)
Scale Range
Lower Limit
Range Minimum to
Scale Range Upper Limit -100
Range min
(Linear=0)
Decimal point
position
=XXXX, =XXX.X, =XX.XX, =X.XXX
(non-temperature ranges only)
Process Variable
Offset
±
Span of controller
(see
CAUTION
note at end of section)
High Limit.
Limit relay is energised when
process “safe” (PV < Limit Setpoint)
Limit Action
Low Limit.
Limit relay is energised when
process “safe” (PV > Limit Setpoint)
Setpoint Upper
Limit
Current Setpoint to Scale Range maximum
R/max
Setpoint Lower
Limit
Scale Range minimum to Current Setpoint
R/min
Process High Alarm
Process Low Alarm
Deviation Alarm
Band Alarm
Alarm 1Type
No alarm
High Alarm 1
value*
Range Max
Low Alarm 1
value*
Scaled Range Minimum to
scaled Range Maximum in display units
Range Min
Band Alarm 1
value*
1 LSD to span from setpoint in display units
Dev. Alarm 1
value*
+/- Span from setpoint in display units
Alarm 1
Hysteresis*
!
!
!
!
1 LSD to full span in display units
Parameter
Lower
Display
Upper
Display
Adjustment range & Description
Default
Value
Alarm 2 Type*
High Alarm 2
value*
Range Max
Low Alarm 2
value*
Range Min
Band Alarm 2
value*
Dev. Alarm 2
Value*
Alarm 2
Hysteresis*
!
!
!
!
Options as for alarm 1
Mm
Mm
Mm
Mm
Limit Output Relay
"
"
"
"
Alarm 1, Direct
Alarm 1, Reverse
Alarm 2, Direct
Alarm 2, Reverse
Logical Alarm 1 OR 2, Direct
Logical Alarm 1 OR 2, Reverse
Logical Alarm 1 AND 2, Direct
Logical Alarm 1 AND 2, Reverse
Limit Annunciator, Direct
Limit Annunciator, Reverse
"
"
"
"
Retransmit Limit SP Output
Output 2 Usage
#
#
#
#
Retransmit PV Output
0 to 5 V DC output 1
0 to 10 V DC output
2 to 10 V DC output
0 to 20 mA DC output
Linear Output 2
Range
!
!
!
!
4 to 20 mA DC output
Retransmit
Output 2 Scale
maximum
-1999 to 9999
(display value at which output
will be maximum)
Range max
Retransmit
Output 3 Scale
minimum
-1999 to 9999
(display value at which output
will be minimum)
Range min
Output 3 Usage
#
#
#
#
As for output 2
"
"
"
"
Linear Output 3
Range
!
!
!
!
As for output 2
Retransmit
Output 3 Scale
maximum
-1999 to 9999
(display value at which output
will be maximum)
Range max
Retransmit
Output 3 Scale
minimum
-1999 to 9999
(display value at which output
will be minimum)
Range min
PV is visible in Operator mode
PV not visible in Operator mode
Display Strategy
$
$
$
$
Displays
in Operator mode
when Limit Output is not active
%
%
%
%
ASCII
Mm
Mm
Mm
Mm
Modbus with no parity
Mm
Mm
Mm
Mm
Modbus with Even Parity
Serial
Communications
Protocol
Mm
Mm
Mm
Mm
Modbus with Odd Parity
Mm
Mm
Mm
Mm
.
1.2 kbps
.
2.4 kbps
.
&
&&
&
4.8 kbps
'
''
'
.
((((
9.6 kbps
Serial
Communications
Bit Rate
'
''
'
.
19.2 kbps
.
&
&&
&
Comms Address
1 to 255 (Modbus), 1 to 99 (ASCII)
Ww
Ww
Ww
Ww
Read/Write
Comms Write
Read only
Ww
Ww
Ww
Ww
Configuration
Lock Code
)
)
)
)
0 to 9999
Notes: Output 1 is always a Latching Limit Relay output.
If Option Slot A has the Digital Input module fitted, this always functions as a
Remote Reset, duplicating the function of the Reset) key .
As these functions cannot be changed, no Configuration menus are required.
CAUTION:
Process Variable Offset can be used to modify the
measured value to compensate for probe errors. Positive values
increase the reading, negative values are subtracted. This parameter
is effectively, a calibration adjustment and MUST be used with care.
There is no front panel indication of when this parameter is in use.
A
B