 DIN LIMIT CONTROLLERS 

CONCISE PRODUCT MANUAL (59333-2)

 

 

CAUTION:

 Installation should be only performed by 

technically competent personnel. Local Regulations 
regarding electrical installation & safety must be observed. 

 

1.  INSTALLATION 

The models covered by this manual have three different DIN case sizes (refer to 
section 9).
 Some installation details vary between models. These differences have 
been clearly shown. 
Note: The functions described in sections 2 thru 8 are common to all models.

 

 

Installing Option Modules

 

1

/

16 

Din Size Instruments

 

 

CPU PCB 

 
 

Option Module 1 

(Fixed Limit Relay)

 
 

Option Module 2 

 

 

 

Mounting Struts 

 

 

Option Module A 

 

Option Module 3 
 
 
PSU PCB 

 

1

/

8

 & 

1

/

Din Size Instruments

 

 

 
 
 
 

CPU PCB 

 

Option Module B 

(not used on Limit 

Controllers) 

 

Option Module 2 

 
 

Option Module 1 

(Fixed Limit Relay)

 

 

 
 
 
Mounting Struts 
 
 
Option Module A 
 
 
Option Module 3 
 
 
PSU PCB 

 

To access module A, first detach the PSU and CPU boards from the front by lifting 
first the upper, and then lower mounting struts. Gently separate the boards. 
a. 

Plug the required option modules into the correct connectors, as shown below. 

b. 

Locate the module tongues in the corresponding slot on the opposite board. 

c. 

Hold the main boards together while relocating back on the mounting struts. 

d. 

Replace the instrument by aligning the CPU and PSU boards with their guides 

  

in the housing, then slowly push the instrument back into position. 

Note: Option modules are automatically detected at power up. 

 

Option Module Connectors 

1

/

16 

Din Size Instruments 

Option Slot 1 

(Fixed Limit 

Relay)

 
 

Option Slot 2 

Connector

PL4A

 

 
Option Slot A 
Connectors 
PL5 & PL6 
 
 
Option Slot 3 
Connector 
PL4B 

1

/

8

 & 

1

/

Din Size Instruments 

Option Slot B 

(not used on 

Limit Controllers)

Option Slot 2 

Connector

PL4A

Option Slot 1 

(Fixed Limit 

Relay)

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Option Slot A 
Connectors 
PL5 & PL6 
 
 
Option Slot 3 
Connector 
PL4B 

 

Panel-Mounting 

The mounting panel must be rigid, and may be up to 
6.0mm (0.25inch) thick. Cut-out sizes are: 
          Cut-Out Dim A 

      Cut-Out Dim B

 

     

1

/

16 

1

/

8

 Din = 45mm 

      

1

/

16 

Din = 45mm 

               1

/

4

 Din = 92mm                  

1

/

8

 & 

1

/

4

 Din = 92mm 

 

For n multiple instruments mounted side-by-side, cut-out 
A is 48n-4mm (

1

/

16 

 & 

1

/

8

 Din) or  96n-4mm (

1

/

4

 Din)

 

Tol0.5, -0.0mm 

 

 

 
 

Mounting Panel 

 

Instrument 

Housing 

 

Ratchets 

 

Gasket 

 

Slide mounting clamp 
over the instrument 
housing towards rear face 
of mounting panel until 
the tongues engage in 
ratchets and instrument is 
clamped in position. 
 
 
Hold instrument firmly in 
position (apply pressure 
to bezel only) 

 

CAUTION:

 Do not remove the panel gasket; it is a seal against dust and 

moisture. 

 

Rear Terminal Wiring 

 

USE COPPER CONDUCTORS (EXCEPT FOR T/C INPUT) 

Single Strand wire gauge:  Max 1.2mm (18SWG)

 

1

/

16 

Din Size Instruments

 

 

1

/

8

 & 

1

/

Din Size Instruments

 

 

These diagrams show all possible option combinations. The actual 

connections required depends on the exact model and options fitted. 

 

CAUTION:

 Check information label on housing for correct operating 

voltage before connecting supply to Power Input 
Fuse:  100 – 240V ac – 1amp anti-surge 
           24/48V ac/dc – 315mA anti-surge 

 

Note: At first power-up the message 

 

 is displayed, as described in 

section 6 of this manual. Access to other menus is denied until configuration 
mode is completed

 

 

 
 
 
 
 
 

2.  SELECT MODE 

Select mode is used to access the configuration and operation menu functions. 
It can be accessed at any time by holding down        and pressing       . 
In select mode, press        or        to choose the required mode, press        to enter. 
An unlock code is required to prevent unauthorised entry to Configuration, & Setup 
modes. Press        or        to enter the unlock code, then press        to proceed. 

Mode 

Upper 

Display 

Lower 

Display 

Description 

Default 
Unlock 

Codes 

Operator 

Normal operation 

None 

Set Up 

Tailor settings to the application 

Configuration 

Configure the instrument for use 

Product Info 

Check manufacturing information 

None 

Note: The instrument will always return automatically to Operator mode if 
there is no key activity for 2 minutes. 

 
 

3.  CONFIGURATION MODE 

First select Configuration mode from Select mode (refer to section 2). 
Press       to scroll through the parameters, then press        or        to set the required 
value. Press         to accept the change, otherwise parameter will revert to previous 
value. To exit from Configuration mode, hold down        and press       , to return to 
Select mode. 
Note: Parameters displayed depends on how instrument has been configured.  
Refer to user guide (available from your supplier) for further details. 
Parameters marked * are repeated in Setup Mode. 

 

Parameter 

Lower 

Display 

Upper 

Display 

Adjustment range & Description 

Default 

Value 

Input 
Range/Type 

See following table for possible codes 

Code  Input Type & 

Range 

Code 

Input Type & 
Range 

Code  Input Type & 

Range 

bC

bC

bC

bC 

 

 

 

B: 100 - 1824 ºC 

LLLL

.

C

C

C

 

 

 

L: 0.0 - 537.7 ºC 

bF

bF

bF

bF 

 

 

 

B: 211 - 3315 ºF 

LLLL

.

F

F

F

 

 

 

L: 32.0 - 999.9 ºF 

P24F

P24F

P24F

P24F 

 

 

 

PtRh20% vs 40%: 
32 - 3362 ºF 

CC

CC

CC

CC 

 

 

 

C: 0 - 2320 ºC 

NC

NC

NC

NC 

 

 

 

N: 0 - 1399 ºC 

PTC

PTC

PTC

PTC 

 

 

 

Pt100: –199 - 800 ºC 

CF

CF

CF

CF 

 

 

 

C: 32 - 4208 ºF 

NF

NF

NF

NF 

 

 

 

N: 32 - 2551 ºF 

PtF

PtF

PtF

PtF 

 

 

 

Pt100: –328 - 1472 ºF 

JC

JC

JC

JC 

 

 

 

J:  –200 - 1200 ºC 

rC

rC

rC

rC 

 

 

 

R: 0 - 1759 ºC 

P

P

P

Pt

tt

t

.

C

C

C

 

 

 

Pt100: –128.8 - 537.7 ºC 

JF

JF

JF

JF 

 

 

 

J:  –328 - 2192 ºF 

rF

rF

rF

rF 

 

 

 

R: 32 - 3198 ºF 

Pt

Pt

Pt

Pt

.

F

F

F

 

 

 

Pt100: –199.9 - 999.9 ºF 

j

j

j

j

.

C

C

C

 

 

 

J:  –128.8 - 537.7 ºC 

SC

SC

SC

SC 

 

 

 

S: 0 - 1762 ºC 

0 - 20 mA DC 

j

j

j

j

.

F

F

F

 

 

 

J:  –199.9 - 999.9 ºF 

SF

SF

SF

SF 

 

 

 

S: 32 - 3204 ºF 

4 - 20 mA DC 

KC

KC

KC

KC 

 

 

 

K: –240 - 1373 ºC 

tC

tC

tC

tC 

 

 

 

T: –240 - 400 ºC 

0 - 50 mV DC 

KF

KF

KF

KF 

 

 

 

K:  –400 - 2503 ºF 

tF

tF

tF

tF 

 

 

 

T: –400 - 752 ºF 

.

10 - 50 mV DC 

k

k

k

k

.

C

C

C

 

 

 

K: –128.8 - 537.7 ºC 

t

tt

t

.

C

C

C

 

 

 

T: –128.8 - 400.0 ºC 

0 - 5 V DC 

K

K

K

K

.

F

F

F

 

 

 

K: –199.9 - 999.9 ºF 

t

tt

t

.

F

F

F

 

 

 

T: –199.9 - 752.0 ºF 

1 - 5 V DC 

LC

LC

LC

LC 

 

 

 

L: 0 - 762 ºC 

0 - 10 V DC 

LF

LF

LF

LF 

 

 

 

L: 32 - 1403 ºF 

P24C

P24C

P24C

P24C 

 

 

 

PtRh20% vs. 40%:  
0 - 1850 ºC 

2 - 10 V DC 

Note: Decimal point shown in table indicates temperature resolution of 0.1° 
Parameter 

Lower 

Display 

Upper 

Display 

Adjustment range & Description 

Default 

Value 

Scale Range 
Upper Limit 

Scale Range Lower Limit +100 

to Range Maximum 

Range max 

(Lin=1000) 

Scale Range 
Lower Limit 

Range Minimum to 

Scale Range Upper Limit -100 

Range min 

(Linear=0) 

Decimal point 
position 

=XXXX,  =XXX.X,  =XX.XX,  =X.XXX 

(non-temperature ranges only) 

Process Variable 
Offset 

±

Span of controller 

(see 

CAUTION

 note at end of section

High Limit. 

Limit relay is energised when 

process “safe” (PV < Limit Setpoint) 

Limit Action 
 

Low Limit. 

Limit relay is energised when 

process “safe” (PV > Limit Setpoint) 

Setpoint Upper 
Limit 

Current Setpoint to Scale Range maximum 

R/max 

Setpoint Lower 
Limit 

Scale Range minimum to Current Setpoint 

R/min 

Process High Alarm  

Process Low Alarm 

Deviation Alarm 

Band Alarm 

Alarm 1Type 

No alarm 

High Alarm 1 
value* 

 

 

 

 

Range Max 

Low Alarm 1 
value* 

Scaled Range Minimum to 

scaled Range Maximum in display units 

Range Min 

Band Alarm 1 
value* 

1 LSD to span from setpoint in display units 

Dev. Alarm 1 
value* 

+/- Span from setpoint in display units 

Alarm 1 
Hysteresis* 

!

!

!

!

1 LSD to full span in display units 

 
 
 
 
 
 

Parameter 

Lower 

Display 

Upper 

Display 

Adjustment range & Description 

Default 

Value 

Alarm 2 Type* 
High Alarm 2 
value* 

 

 

 

 

Range Max 

Low Alarm 2 
value* 

Range Min 

Band Alarm 2 
value* 
Dev. Alarm 2 
Value* 
Alarm 2 
Hysteresis* 

!

!

!

!

Options as for alarm 1 

Mm

Mm

Mm

Mm

Limit Output Relay 

"

"

"

"

Alarm 1, Direct 

Alarm 1, Reverse 

Alarm 2, Direct 

Alarm 2, Reverse 

Logical Alarm 1 OR 2, Direct 

Logical Alarm 1 OR 2, Reverse 

Logical Alarm 1 AND 2, Direct 

Logical Alarm 1 AND 2, Reverse 

Limit Annunciator, Direct 

Limit Annunciator, Reverse 

"

"

"

"

Retransmit Limit SP Output 

Output 2 Usage 

#

#

#

#

Retransmit PV Output 

 

0 to 5 V DC output 1 

0 to 10 V DC output 

2 to 10 V DC output 

0 to 20 mA DC output 

Linear Output 2 
Range 

!

!

!

!

4 to 20 mA DC output 

Retransmit 
Output 2 Scale 
maximum 

-1999 to 9999 

(display value at which output 

will be maximum) 

Range max 

Retransmit 
Output 3 Scale 
minimum 

-1999 to 9999 

(display value at which output 

will be minimum) 

Range min 

Output 3 Usage 

#

#

#

#

As for output 2 

"

"

"

"

Linear Output 3 
Range 

!

!

!

!

As for output 2 

Retransmit 
Output 3 Scale 
maximum 

-1999 to 9999 

(display value at which output 

will be maximum) 

Range max 

Retransmit 
Output 3 Scale 
minimum 

-1999 to 9999 

(display value at which output 

will be minimum) 

Range min 

PV is visible in Operator mode 

PV not visible in Operator mode 

Display Strategy 

$

$

$

$

Displays 

 in Operator mode 

when Limit Output is not active 

 

 

 

 

%

%

%

%

ASCII 

Mm

Mm

Mm

Mm

Modbus with no parity 

Mm

Mm

Mm

Mm

Modbus with Even Parity 

Serial 
Communications 
Protocol 

Mm

Mm

Mm

Mm

Modbus with Odd Parity 

Mm

Mm

Mm

Mm

.

1.2 kbps 

.

2.4 kbps 

.

&

&&

&

4.8 kbps 

'

''

'

.

((((

9.6 kbps 

Serial 
Communications 
Bit Rate 
 

'

''

'

.

19.2 kbps 

.

&

&&

&

Comms Address 

1 to 255 (Modbus), 1 to 99 (ASCII) 

Ww

Ww

Ww

Ww

Read/Write 

Comms Write 

Read only 

Ww

Ww

Ww

Ww

Configuration 
Lock Code 

)

)

)

)

0 to 9999 

 
 

Notes: Output 1 is always a Latching Limit Relay output.  
If Option Slot A has the Digital Input module fitted, this always functions as a 
Remote Reset, duplicating the function of the Reset) key       .

 

 

As these functions cannot be changed, no Configuration menus are required. 
 

 

CAUTION:

 Process Variable Offset can be used to modify the 

measured value to compensate for probe errors. Positive values 
increase the reading, negative values are subtracted. This parameter 
is effectively, a calibration adjustment and MUST be used with care.
 
There is no front panel indication of when this parameter is in use. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 