VER-1705.02-OPT-31 10K/20K/30K (ENGLISH) - 41
16: Output voltage calibration
Interface
Setting
Parameter 2:
it always shows
OP.V
as output voltage.
Parameter 3:
it shows the internal measurement value of the output A voltage, and you
can calibrate it by pressing
Up
or
Down
according to the measurement from an external
voltage meter. The calibration result will be effective by pressing
Enter
. The calibration
range is limited /-9V. This function is normally used for parallel operation.
17: Phase auto adapt enable / disable
Interface
Setting
Parameter 2:
it always shows
PH.A
as PHASE AUTO ADAPT.
Parameter 3:
it allows enable or disable this function:
DIS:
Disables this function. If disable UPS only accepts 120º difference between input
lines.
ENA:
Enables this function. If enable, UPS will accept input lines with same phase or a
difference of 240ºC between them.
OPTIMA 30K
Since 30K model does not have programmable output 2, configurable functions 10 and 11 are not available in 30K model. All other functions
are similar as 10K and 20K models.
10: Reserved
Interface
Setting
Reserve for future options.
11: Reserved
Interface
Setting
Reserve for future options.