Rack-Mounted Server
Installation Guide
V1.0
Warnings!
Please keep this document for future reference.
15kg
30kg
50kg
Watch out for the scratches that may be caused by the cabinet, chassis or rails.
Be aware of electric shock when installing servers into the cabinet in use.
●
At least 4 people are needed when installing a 4U server or a server of larger form factor.
●
DO NOT block the vents on the server during installation, especially the vents on the front
and rear of the server.
●
Remove the protective film from the chassis before installing servers into the rack.
●
For proper ventilation, leave a minimum space of 15 cm between two servers.
●
Always keep the air ducts in place to ensure proper air flow and avoid air turbulence in the
server room.
●
Servers can only be deployed in dedicated cabinets with ventilation holes or specialized
cooling cabinets to avoid server failure from overheating as they are high power appliances.
●
In case of multiple-server deployment, always load from bottom to top and place the
heavier server on the lower bay.
●
DO NOT install devices beyond the cabinet’s load-bearing capacity, power supply capacity
and heat dissipation capacity.
●
For easy access of the front and rear ports and cabling, leave a minimum space of 70 mm
between the front side of the server and the inner side of the cabinet’s front door, and 150
mm between the rear side of the server and the inner side of the cabinet’s rear door.
For devices ≥ 15kg, it requires at least 2 people.
For devices ≥ 30kg, it requires at least 3 people.
For devices ≥ 50kg, it requires at least 4 people.