![Inovonics EN4216MR Installation And Operation Manual Download Page 3](http://html.mh-extra.com/html/inovonics/en4216mr/en4216mr_installation-and-operation-manual_2064785003.webp)
2/3/20 357-05819-02 Rev A © Inovonics, 2020 - www.inovonics.com
3
3 Point Setup and Registration
Each transmitter must setup and registered to a point. Once registered, the
transmitters alarm(s) will be mapped to the appropriate alarm output(s).
Following are the transmitters supported by the EN4232MR:
Note:
Contact Inovonics for a list of other compatible devices.
3.1 Factory Configuration Defaults
The EN4232MR arrives with the outputs pre-programmed. If the default
programming is sufficient for your site, you do not need setup points.
Simply register a transmitter to one of the points.
To register a transmitter to a pre-programmed point:
1.
From the EN4232MR start screen, press the enter button to access the
receiver’s three main menu options.
2.
Use the up and down buttons to navigate to the install & service menu;
press the enter button.
3.
Enter your password to access the install & service menus.
4.
Follow the instructions in section 4.5.2 “Register Transmitter” on
page 5.
If you do need to setup points, advance to section 3.2 “Program a Point” on
page 3.
3.2 Program a Point
1.
From the EN4232MR start screen, press the enter button to access the
receiver’s three main menu options.
2.
Use the up and down buttons to navigate to the install & service menu;
press the enter button.
3.
Enter your password to access the install & service menus.
4.
Following the instructions in section 4.5.1 “Setup Point” on page 4.
4 32 Zone Multi-Condition Receiver with Relay Outputs
Operation and Point Setup Screens
4.1 Menu Tree
P
OINT
S
TATUS
, see 4.3 “Point Status” on page 4.
E
VENT
L
OG
, see 4.4 “Event Log” on page 4.
I
NSTALL
& S
ERVICE
, 4.5 “Install & Service” on page 4.
S
ETUP
P
OINT
, see 4.5.1 “Setup Point” on page 4.
P
OINT
#
S
UPERVISION
T
IME
S
ECURITY
/R
EPEATER
A
LARM
I
NPUTS
A
LARM
O
UT
A
LARM
O
UTPUT
T
YPE
I
NACTIVE
O
UT
/T
YPE
T
AMPER
O
UT
/T
YPE
L
OW
B
ATTERY
O
UT
/T
YPE
T
EXT
R
EGISTER
R
EGISTER
T
RANSMITTER
, see 4.5.2 “Register Transmitter” on
page 5.
D
ELETE
P
OINT
, see 4.5.3 “Delete Point” on page 5.
S
IGNAL
S
TRENGTH
, see 4.5.4 “Signal Strength” on page 5.
C
HANGE
P
ASSWORD
, see 4.5.5 “Change Password” on page 5.
F
ACTORY
C
ONFIG
, see 4.5.6 “Factory Config” on page 5.
4.2 EN4232MR Start Screen
The EN4232MR start screen displays alarm and fault information on the
LCD display. Points in alarm are displayed as “Alarm”, with the point
number following. If more than one point is in alarm, the display scrolls
through each point. If a point has more than one alarm, the display scrolls
through each alarm. Fault conditions are indicated by “Fault” in the LCD
display if there is no alarm already displayed, and point numbers are not
displayed.
Alarms and faults will only display briefly when the alarm or fault is first
received, and then the start screen will return to a ready condition. For
detailed alarm and fault information, see section 4.3 “Point Status” on
page 4.
Table 1: EN4232MR Supported Transmitters
Transmitter
Alarm 1
Alarm 2
Alarm 3
Alarm 4
EN1215EOL
Terminal
block
EN1215WEOL
Terminal
block
Reed
switch
EN1223D
Both
buttons
EN1235SF
Button
EN1235DF
Both
buttons
EN1242
Smoke
EN1244
Smoke
EN1245
CO
EN1249
Bill trap
EN1261HT
Motion
Table 2: Default Transmitter Programming
Alarm Output
Transmitter Points
1
1, 11, 21, 31
2
2, 12, 22, 32
3
3, 13, 23
4
4, 14, 24
5
5, 15, 25
6
6, 16, 26
7
7, 17, 27
8
8, 18, 28
9
9, 19, 29
10
10, 20, 30
Table 3: Default Trouble Condition Programming
Output/Relay
Condition
11
Tamper
12
Low Battery
12
Supervision Loss/Inactive
12
Line Power Loss