Inovonics EN4016SK Installation And Operation Manual Download Page 5

6.13.19 168-04493-01 Rev A © Inovonics, 2019 - www.inovonics.com 

5

From the main menu, highlight Point Status, and press enter to select. The 

Register Point menu displays.

 Figure 19  

The Main Menu, Point Status highlighted

6.

All registered points display. Highlight the point for the end-device that 

will be placed in this location, and press enter to select. The Point 

Status Summary screen displays.

 Figure 20  

The Point Status Summary screen

The Point Status Summary screen contains the following information:
Point # The point number you’ve selected displays here along with the 

signal level of the selected end-device. Good indicates a signal sufficient 

for EchoStream functionality; Weak indicates a signal insufficient for 

EchoStream functionality; N/S indicates no signal received.
Good displays when the signal margin is 4 decibels or more. Weak displays 

when the signal margin is less than 4 decibels. 

N/S displays when no recognizable message is received at all, no matter 

how weak.
End-device transmission symbol: The end-device transmission symbol, *, 

beats when the receiver is hearing a signal directly from a selected end-

device. When receiving a good signal, the end-device transmission symbol 

beats approximately once a second, and the receiver beeps accordingly.
High-power repeater transmission symbol: The high-power repeater 

transmission symbol, +, beats when the receiver is hearing a signal from 

the selected end-device that has been passed on by a high-power repeater. 

When receiving a good signal, the high-power repeater transmission 

symbol beats approximately once a second.
Rcv Lvl Indicates the overall strength of messages received from the 

selected end-devices and repeaters, in decibels.
Rcv Mar Indicates the signal margin of messages received from the 

selected end-devices and repeaters, in decibels.
Msg# Indicates the total number of messages received, up to 999.
Batt Indicates the battery status of the end-device as either OK or Low.

7.

Press enter for more signal information. The Point Status Message 

Count screen displays.

 Figure 21  

The Point Status Message Count screen

Act# Indicates the total number of activation messages received, up to 999. 

An activation message is defined as a message that does not fall into the 

Tmp, Res and Sup categories described below. For example, an alarm 

message on a pendant transmitter would be displayed as an Act message.
Tmp# Indicates the total number of tamper messages received, up to 999.
Res# Indicates the total number of reset and restoral messages received, 

up to 999.
Sup# Indicates the total number of supervisory messages received, up to 

999.

8.

Press enter for more signal information. The Point Status Signal 

Strength screen displays.

 Figure 22  

The Point Status Signal Strength screen

Dir Lvl Indicates the overall strength of messages received directly from the 

selected end-device, in decibels.
Dir Mar Indicates the signal margin of messages received directly from the 

selected end-device, in decibels.
1st Lvl Indicates the overall strength of first hop end-device messages 

received by high-power repeaters, in decibels.
1st Mar Indicates the signal margin of first hop end-device messages 

received by high-power repeaters, in decibels.
Lst Lvl Indicates the overall strength of last hop high-power repeater 

messages received by the survey receiver, in decibels.
Lst Mar Indicates the signal margin of last hop high-power repeater 

messages received by the survey receiver, in decibels.

9.

Repeat all steps for the next point on your site map.

10.

When the site survey is complete, press the EN1223SK and EN1210SK 

on/off buttons to stop transmission.

11.

Press the EN4016SK power button to turn off the survey receiver.

5 Perform a Site Survey without using Survey 

Transmitters

The survey receiver can be used to monitor the signal strength of any end-

device or high-power repeater in your EchoStream system.

1.

Register the end-device or high-power repeater you want to monitor.

• Refer to section 3.3, “Register End-Devices” to register an end-

device; refer to section 3.4, “Register High-Power Repeaters” to 

register a high-power repeater.

2.

Place the survey receiver where your network coordinator or receiver is 

normally located.

3.

Activate the end-device.

4.

Monitor signal strength.

• Refer to step 5 through 8 in section 4, “Perform a Site Survey using 

Survey Transmitters” to monitor signal strength.

6 Specifications

Operating frequency 915-928 MHz (Australia), 921-928 MHz (New 

Zealand) 902-928 MHz (USA)
Operating environment 0°- 60°C (32°- 140°F), 90% relative humidity, non-

condensing
Measurement ac/- 2dB @ 25°C (77°F), +/- 3dB @ 0°C - 60°C 

(32°F-140°C).
Receiver type Frequency hopping spread spectrum
Battery life and ordering info EN4016SK: Eight hours of continuous use 

with 1.5V, AA alkaline batteries.

Caution: 

Changes or modifications to this unit not expressly approved by 

Inovonics Wireless Corporation may void the installer's authority to operate 

the equipment as well as the product warranty. 

Note: 

E-mail [email protected] for a copy of the CE Declaration of 

Conformity.

Reviews: