5.25.17 05377D © Inovonics, 2017 - www.inovonics.com
2
2.5 Select Fixed/Variable Sleep Time
The sleep time jumper setting provides control for normal or high-traffic
operating environments. When set to fixed, if the EE1265 senses motion, it
will transmit an alarm, then enter sleep mode for 180 seconds; if motion is
sensed when the sleep time has expired, the EE1265 will transmit another
alarm. Fixed sleep time is recommended for normal operating
environments. When set to variable, if the EE1265 senses motion, it will
transmit an alarm, then enter sleep mode for 180 seconds; if motion is
sensed before the sleep time has expired, the EE1265 will restart the 180
second interval. Variable sleep time is recommended for high-traffic
operating environments.
8.
Place a selection jumper on the appropriate sleep countselection pins.
• Place the jumper on the left two pins to select variable sleep time.
• Place the jumper on the right two pins to select fixed sleep time.
9.
Install the battery.
10.
Press the
Reset
button.
2.6 Register the PIR
The EE1265 must be registered.
11.
Refer to receiver, network coordinator, or control panel installation
instructions to register the EE1265. Press
Reset
when prompted to
register the transmitter.
Caution:
The EE1265 should be tested after registration to ensure
operation. To test the EE1265, activate each of the conditions and ensure
an appropriate response.
2.7 Mount the EE1265
12.
Install the housing cover and housing tamper lock screw.
Note:
Ensure the housing tamper lock screw is tightened sufficiently to
depress the tamper switch. If the housing tamper lock screw is not
sufficiently tightened, the EN1265 will remain in a state of tamper.
13.
Remove the mounting bracket.
14.
Use the provided anchors and screws to mount the EE1265 housing
base to the ceiling.
• The EE1265 can be mounted to a maximum height of approximately
12 feet (3.6 meters). As mounting height increases, distance between
detection zones also increases toward the perimeter, and the effects
of factors such as floor surface temperature and intruder direction and
speed are intensified. This can contribute to reducing the speed of
detection. Every installation should include a walk test of detection
zones, including intrusion paths crossing the edges of the zones. See
Figure 3 and Figure 4 for more information.
Figure 3
EE1265 detection diameter
Note:
The ACC689 long range lens allows for an install height of up to 25
feet.
Figure 4
EE1265 lens pattern
15.
When the housing base has been attached to the ceiling, install the PIR
on the mounting bracket.
3 Test the EE1265
3.1 Walk Test
When in walk test mode the test LED will light every time the EE1265
senses motion. The unit will not transmit alarm signals during this test
period. There are two ways to initiate a walk test. Once initiated, the walk
test will last for one minute. To initiate a walk test:
1.
With the cover off the unit, pass a magnet near the walk test reed switch
for one second, or press the test button for one second.
Note:
The test LED only lights during the walk test and the transmission
test.
3.2 Transmission Test
When in transmission test mode the unit will transmit alarm and restoral
cycles at regular intervals for approximately one minute. The LED will light
every time the unit transmits. To initiate a transmission test:
1.
With the cover off the unit, hold a magnet near the walk test reed switch
for at least three seconds, or press the test button for at least three
seconds.
4 Operation
The EE1265 contains a tamper switch on the board to alert the user if the
housing cover is removed. The EE1265 also contains tamper contacts in
the mounting bracket to alert the user if the unit is removed from the wall.
5 Specifications
Dimensions: 131mm x 57mm (5.2" x 2.25").
Weight: 185g (6.52 oz.).
Detection method: 4-element PIR.
Operating temperature: 0°C to 49°C (32°F to 120°F).
Humidity: 10% to 90% non-condensing.
Battery: Inovonics BAT604 (3.0V lithium Duracell DL123A) .
Note:
Battery is supervised.
Typical battery life: 2 years in location with low to moderate activity.
Visible light protection: Stable against halogen light 8 feet (2.4m) or
reflected light.
Temperature compensation: Yes.
Pulse count: Selectable single pulse or multiple pulse.
Operating frequency: 868-869 MHz.
Output power: 25mW.
Firmware revision: 90484, v3.01.
Ceiling - 3 m (10 ft)
Effective Detection Diameter
14 m (46 ft)
0.8 M (2.6 Ft)
Floor