Figure 7
EN4201R Components
2.5 Mount the Receiver
Caution:
Mount the receiver in a location removed from metal. Metal objects (duct work, wire mesh
screens, boxes) will reduce RF range.
1.
Use the provided anchors and screws to mount the receiver in a location accessible for future
maintenance.
2.
Perform a walk test, activating each transmitter assigned to the receiver and ensuring an appopriate
response.
3 Specifications
Housing:
162 mm x 92 mm x 28 mm (6.38" x 3.60" x 1.10")
Operating environment:
0°- 60°C (32°- 140°F), 90% relative humidity, non-condensing
Power requirement:
11 - 14 VDC; 150 mA (EN4201), ~400 mA max (EN4201R with relays energized)
Current consumption:
Approx. 135 mA; approx. ~400 mA max (EN4201R with relays energized)
Output specifications:
Open collector, drive down to .4V @ 100 mA (EN4201); Form C relay 1A @ 28 VDC,
0.5A @ 30 VAC resistive load (EN4201R); N/O receiver case tamper contact closure, N/O receiver jam input
indication.
Input specifications:
A low is less than .5 V; a high is greater than 2.5 V. Reset input: Contact closure,
momentary low.
Receiver type:
Frequency hopping spread spectrum
Operating frequency:
915-928 MHz (Australia), 921-928 MHz (New Zealand) 902-928 MHz (USA)
Number of points/transmitters:
Four
Number of alarm outputs:
EN4201: one open collector output; EN4201R: one Form C relay output
Number of fault outputs:
EN4201: one open collector output; EN4201R: one Form C relay output
Figure 12
Tamper, Reset and Jam Circuits
4 Warranty/Disclaimer
Caution:
Changes or modifications to this unit not expressly approved by Inovonics Wireless Corporation
may void the installer's authority to operate the equipment as well as the product warranty.
Inovonics Wireless Corporation ("Inovonics") warrants its products ("Product" or "Products") to conform to
its own specifications and to be free of defects in materials and workmanship under normal use for a period
of twenty-four (24) months from the date of manufacture. Within the warranty period, Inovonics will repair
or replace, at its option, all or any part of the warranted Product. Inovonics will not be responsible for
dismantling and/or reinstallation charges. To exercise the warranty, the User ("User", "Installer" or
"Consumer") must work directly through their authorized distributor who will be given a Return Material
Authorization ("RMA") number by Inovonics. Details of shipment will be arranged directly through the
authorized distributor.
This warranty is void in cases of improper installation, misuse, failure to follow installation and operating
instructions, alteration, accident or tampering, and repair by anyone other than Inovonics.
This warranty is exclusive and expressly in lieu of all other warranties, obligations or liabilities, whether
written, oral, express, or implied. There is no warranty by Inovonics that Inovonics product will be
merchantable or fit for any particular purpose, nor is there any other warranty, expressed or implied, except
as such is expressly set forth herein. In no event shall Inovonics be liable for an incidental, consequential,
indirect, special, or exemplary damages, including but not limited to loss of profit, revenue, or contract,
loss of use, cost of down time, or interruption of business, nor any claim made by distributor's customers or
any other person or entity.
This warranty will not be modified or extended. Inovonics does not authorize any person to act on its behalf
to modify or extend this warranty.
This warranty will apply only to Inovonics Products. Inovonics will not be liable for any direct, incidental, or
consequential damage or loss whatsoever, caused by the malfunction of Product due to products,
accessories, or attachments of other manufacturers, including batteries, used in conjunction with Inovonics
Products.
Note:
E-mail [email protected] for a copy of the CE Declaration of Conformity.
A.
Housing release tabs
B.
Power (11-14 VDC)
C.
GND connection
D.
Output terminals
E.
Fault output
F.
Frequency selection pins
G.
Reset button
H.
Reset input
I.
Jam output
J.
Tamper output
K.
Program button
Figure 8
EN4201 Cabling Option: Open
Collector Out, Normally Open, with an EOL
Resistor
Figure 9
EN4201 Cabling Option: Open Collector
Out, Normally Closed, with an EOL Resistor
Figure 10
EN4201R Cabling Option: Relay
Out, Normally Closed, with an EOL Resistor
Figure 11
EN4201R Cabling Option: Relay
Out, Normally Open, with an EOL Resistor
NZ
AUS
ADVANCE
PROGRAM
TAMP
RESET
Delete
Out Type
Output
Sup Wind
Switch
F
Toggle
4h
Latch
96h
Follow
None
N/O
Moment
2h
N/C
1
2
3
4
A
B
C
I
J
G
H
F
K
D
E
A
A
Control
Panel
EE4201
Vs
GND
Zone 1
Return
GND
Out 1
Fault
Vs
Control
Panel
EE4201
Zone 1
Vs
GND
Zone 1
Return
GND
Out 1
Fault
Vs
Zone 1
Control
Panel
EE4201R
Control
Panel
EE4201R
Vs
GND
Zone 1
Return
GND
NC
COM 1
NO
Vs
Zone 1
NC
COM 2
NO
Vs
GND
Zone 1
Return
GND
NC
COM 1
NO
Vs
Zone 1
NC
COM 2
NO
GND
GND
GND
Tamper
Reset
Jam