 OPERATION 

5

27

IPAQ C330/R330

www.inor.com

01/2019 - 4007317401 – MA IPAQ 330 R01 en

Proper connection of the transmitters with a PC requires our USB interface which is included in 
the ICON-X configuration kit. For connection of the transmitters refer to the following connection 
diagrams during configuration.

DANGER!

Make sure the area is safe before connecting the USB interface ICON-X to the transmitter.

Figure 5-1: Connection during configuration of in-head transmitter

a = PC configuration kit; b = PC software ConSoft

1  

Input (intrinsically safe)

2  

R

Load

 (intrinsically safe)

3  

Output voltage supply (intrinsically safe terminals 6 and 7)

4  

Communication with USB interface and a PC software ConSoft

5  

Connection to USB interface and a PC software ConSoft is not permitted if Ex version of IPAQ C330 (IPAQ C330X) is 
placed in the classified hazardous area (potentially explosive area)

6  

Safe area

7  

Classified hazardous area (potentially explosive area e.g. zone 0, 1 or 2)

Summary of Contents for 70C330X010

Page 1: ...er with NFC technology IPAQ C330 R330 IPAQ C330 R330 IPAQ C330 R330 IPAQ C330 R330 INOR 01 2019 4007317401 MA IPAQ 330 R01 en The documentation is only complete when used in combination with the relev...

Page 2: ...2 www inor com 01 2019 4007317401 MA IPAQ 330 R01 en IMPRINT...

Page 3: ...itter 14 3 2 Rail mounting kit for in head transmitters 15 3 3 Rail mount transmitter 16 4 Electrical connections 17 4 1 Safety instructions 17 4 2 Electrical connections of in head transmitter 19 4 3...

Page 4: ...recycling 34 6 5 3 Disassembling and recycling of IPAQ C330 C330X 34 6 5 4 Disassembling and recycling of IPAQ R330 R330X 35 6 5 5 Packaging of IPAQ C330 C330X and R330 R330X 37 7 Technical data 38 7...

Page 5: ...osion that can result in fatal injuries DANGER Responsibility for the correct use of the devices with special regard to suitability intended use and the field of application lies solely with the opera...

Page 6: ...sically safe partno 70C330X010 C330X intrinsically safe partno 70C330X012 R330X intrinsically safe partno 70R330X010 R330X intrinsically safe partno 70R330X012 CE marking ATEX KIWA 16ATEX0038 X II 1 G...

Page 7: ...the Internet e g when communicating by e mail may involve gaps in security It is not possible to protect such data completely against access by third parties We hereby expressly prohibit the use of t...

Page 8: ...prevent any injury to the user or damage to the device it is essential that you read the information in this document and observe applicable national standards safety requirements and accident preven...

Page 9: ...device in a hazardous atmosphere DANGER These warnings must be observed without fail Even partial disregard of this warning can lead to serious health problems and even death WARNING Disregarding this...

Page 10: ...in head transmitter for temperature measurements and other measurement applications in an industrial environment For further information about the possible measurements refer to Intended use on page...

Page 11: ...ut 2 Ex relevant electrical data 3 Ex approvals North America 4 Electronic electric device waste marking 5 Control drawing number Nameplate for in head transmitter Partno 70C330X012 Figure 2 3 Example...

Page 12: ...field sensor configuration 5 Ex relevant electrical data and Ex approvals 6 Electrical data for output and input 7 Control drawing number 8 CE marking EC conformity and electronic electric device was...

Page 13: ...rical data for output and input 8 Max ambient temperature 9 CE marking EC conformity and electronic electric device waste marking Ui 30V Ii 100mA Pi 0 9W Ci 23 1nF Li 20 H Uo 6 5V Io 11 7mA Po 19 1mW...

Page 14: ...llation in potentially explosive atmospheres The intrinsically safe version must be supplied by an intrinsically safe power supply unit or Zener barrier placed outside of the potentially explosive zon...

Page 15: ...he transmitter until it is attached to the clip The rail mounting kit allows to install the in head transmitter on a rail according to EN 60715 DIN 50022 The kit does not belong to the standard scope...

Page 16: ...lower part of the transmitter against the rail 3 To remove the transmitter bend the locking device using a small screwdriver Carefully pull the transmitter in the forward direction Installation proce...

Page 17: ...y explosive area DANGER Never connect or operate a non Ex version of a transmitter in potentially explosive areas otherwise it might cause an explosion that can result in fatal injuries Before you con...

Page 18: ...tside of the hazardous area If certified ICON X interface is used a connected sensor may be located in the hazardous area If non Ex ICON interface is used a connected sensor shall not be located in th...

Page 19: ...onnection Pt100 Pt100 Pt100 Pt100 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 3 wire connection 3 wire connection 3 wire connection 3 wire connectio...

Page 20: ...grams Otherwise it can come to destruction or damage of the transmitter Note that the maximum output load always depends on the power supply If the maximum output load is exceeded then the measured va...

Page 21: ...ter intrinsically safe Figure 4 2 Connection diagram 1 Input 2 Potentially explosive area 3 Safe area 4 RLoad 5 Voltage supply 8 0 30 VDC intrinsically safe 6 Output signal 4 20mA DANGER The transmitt...

Page 22: ...000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 Pt1000 Ni100 Ni120 Cu10 3 wire connection 3 wire connection 3 wire connection 3 wire connection Pt100 Pt100 Pt100 Pt100 Pt1000 Ni10...

Page 23: ...f rail mount transmitter intrinsically safe Figure 4 3 Connection diagram 1 Input 2 RLoad 3 Voltage supply 8 36 VDC and output 4 20 mA Figure 4 4 Connection diagram 1 Input intrinsically safe 2 Classi...

Page 24: ...does not need any power or other external connection just to be close to the smartphone The app makes it possible to read write save and share settings directly in the field The logging function give...

Page 25: ...her a factory settings or configured according to customers specifications Menu Parameter Factory settings Device Root menu Sensor Type of sensor RTD Pt100 0 003850 Number of wires 3 PV Lower range va...

Page 26: ...k on Options Update USB Interface Load file type the path for the software file downloaded on your desktop or in a separate folder 4 Wait until File OK message is on the screen 5 Click on Start update...

Page 27: ...ON X to the transmitter Figure 5 1 Connection during configuration of in head transmitter a PC configuration kit b PC software ConSoft 1 Input intrinsically safe 2 RLoad intrinsically safe 3 Output vo...

Page 28: ...Communication with USB interface and a PC software ConSoft 5 Connection to USB interface and a PC software ConSoft is not permitted if Ex version of IPAQ R330 IPAQ R330X is placed in the classified ha...

Page 29: ...Overrange Measurement is over specified range Check the specified high range and sensor and sensor connection If error remains replace the sensor Transmitter Ad_short See Sensor short circuit same err...

Page 30: ...on Electronics Transmitter Sensor Out of Specification Sensor Transmitter Process Check Process Transmitter Configuration Check Configuration Transmitter Electronics Check Electronics Transmitter Sens...

Page 31: ...cation is individually configurable and is set via the configuration software 5 7 System or sensor error correction System error correction To perform a system error correction a dry block cell or a t...

Page 32: ...0ADA00015 Ex configuration kit including Ex approved modem software ConSoft and cables for USB connection 70USBIX001 Connection Head installation kit 70ADA00017 ICON BT interface 70CFGBT001 For more p...

Page 33: ...to persons or the environment through any residual media contained in the device when it is returned Date Signature Stamp LEGAL NOTICE Disposal must be carried out in accordance with legislation appl...

Page 34: ...330X is not possible The content of the IPAQ C330 C330X can be found in the following table The products do not contain dangerous gases or materials If there is contamination from the process refer to...

Page 35: ...R330 R330X can be found in the following table RoHS Polybrominated diphenyl Ethers PBDE NA 0 0 Cadmium Cd 7440 43 9 0 0 Mercury Hg 7439 97 6 0 0 Lead Pb 7440 31 7 0 0 Chrome VI Cr VI 7440 47 3 0 0 Pol...

Page 36: ...9 1 4 Polyester NA 0 2 0 3 Nickel 7723 14 0 0 3 0 5 Alumina Al2O3 1344 28 1 0 1 0 2 Gold Au 7444 57 6 0 1 0 2 Barium titanat BaTiO3 12047 27 7 0 1 0 2 RoHS Polybrominated diphenyl Ethers PBDE NA 0 0...

Page 37: ...2019 4007317401 MA IPAQ 330 R01 en 6 5 5 Packaging of IPAQ C330 C330X and R330 R330X The products are delivered to the customers in corrugated cardboard boxes which protect products against moisture a...

Page 38: ...of metals increases according to a mathematical function as the temperature rises This effect is taken advantage of by resistance temperature sensors to measure temperature The Pt100 temperature senso...

Page 39: ...red If however the measuring point and the cold junction are at the same temperature no thermoelectric voltage is generated The degree of thermoelectric voltage also known as electromotive force EMF d...

Page 40: ...r installation in potentially explosive atmospheres Features Features Features Features NFC NFC enables wireless communication and configuration between transmitter and a portable device such a smartp...

Page 41: ...ead transmitter Housing IP65 Terminals IP00 Rail mount transmitter Housing IP20 Terminals IP20 Installation conditions Mounting In head transmitter DIN B head or larger DIN rail with adapter Rail moun...

Page 42: ...ouples Input thermocouples Input thermocouples Input thermocouples T C type B Pt30Rh Pt6Rh IEC 60584 400 1800 C 752 3272 F T C type C W5Re W26Re ASTM E 988 0 2315 C 32 4199 F T C type D W3Re W25Re AST...

Page 43: ...wireless configuration through Bluetooth or NFC technology Communication via Bluetooth requires the Bluetooth interface ICON BT which can be ordered from the manufacturer Approvals and certifications...

Page 44: ...o 70C330X012 C330X intrinsically safe partno 70C330X012 ATEX KIWA 16ATEX0038 X II 1 G Ex ia IIC T6 T4 Ga IECEx IECEx KIWA 16 0016X Ex ia IIC T6 T4 Ga R330X intrinsically safe partno 70R330X010 R330X i...

Page 45: ...n head transmitter In head transmitter In head transmitter In head transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Dimensions mm inch a 33 0 1 3...

Page 46: ...ansmitter Intrinsically safe transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Rail mount transmitter Intrinsically safe transmitter Temperature class Ambient temperatur...

Page 47: ...ermissible output load permissible RLoad U 8 0 0 022 Formula for the maximum permissible output load permissible RLoad U 8 0 0 022 Standard transmitter Figure 7 3 Output load diagram X Power supply U...

Page 48: ...itter R330X Part number 70R330X012 Output terminals 6 7 Input terminals 1 2 3 4 Ui Vmax 30 VDC U0 U0C 30 VDC Ii Imax 100 mA I0 ISC 54 mA Pi Pmax 900 mW P0 405 mW Li 20 H L0 11 mH Ci 23 1 nF C0 38 1 nF...

Page 49: ...span per C RTD Cu10 50 260 83 1 5 C or 0 2 of span 0 02 of span per C T C type B 400 1800 700 1 0 C or 0 2 of span 2 0 01 of span per C T C type C 0 2315 200 1 0 C or 0 2 of span 2 0 01 of span per C...

Page 50: ...0 1 of span 2 0 006 of span per F T C type C 32 4199 360 1 8 F or 0 1 of span 2 0 006 of span per F T C type D 32 4199 360 1 8 F or 0 1 of span 2 0 006 of span per F T C type E 454 1832 90 0 9 F or 0...

Page 51: ...01 MA IPAQ 330 R01 en 8 1 Installation and control drawings IPAQ Part Number Control drawing C330X 1 70C330X010 4005488501 C330X 2 70C330X012 4005488502 R330X 1 70R330X010 4005499601 R330X 2 70R330X01...

Page 52: ...then the resistance between the terminal on the safety barrier and the earth ground shall be less than 1 ohm 5 Do not connect any communication equipment to the communication port of the transmitter...

Page 53: ...nication equipment to the communication port of the transmitter unless area is known to be non hazardous Associated apparatus The control equipment connected must not use or generate over 250 V rms or...

Page 54: ...70 Article 500 to 510 Canadian Electrical Code CEC Section 18 and ANSI ISA RP12 06 01 4 If the cable parameters are unknown the following values shall be used Capacitance 200 pF m 60pF feet Inductance...

Page 55: ...al Electrical Code NFPA 70 Article 500 to 510 Canadian Electrical Code CEC Section 18 and ANSI ISA RP12 06 01 4 If the cable parameters are unknown the following values shall be used Capacitance 200 p...

Page 56: ...9 NOTES 56 IPAQ C330 R330 www inor com 01 2019 4007317401 MA IPAQ 330 R01 en...

Page 57: ...NOTES 9 57 IPAQ C330 R330 www inor com 01 2019 4007317401 MA IPAQ 330 R01 en...

Page 58: ...9 NOTES 58 IPAQ C330 R330 www inor com 01 2019 4007317401 MA IPAQ 330 R01 en...

Page 59: ...ished by INOR 2 is connected to a proper power supply 3 is not misused or abused and 4 there is no evidence of tampering mishandling neglect accidental damage modification or repair without the approv...

Page 60: ...82 762 2 E mail info inor gmbh de Web www inor gmbh de The current list of all INOR contacts and addresses can be found at www inor com Inor Process AB PO Box 9125 SE 200 39 Malm Sweden Phone 46 0 40...

Reviews: