PSU = power supply unit 

BCT = battery condition test 

ECB = electronic circuit breaker 

ELVD = electronic low voltage disconnect  RPP = reverse polarity protection 

EMI = electromagnetic interference 

Glossary of terms used in our user manuals

 

SNMP = Simple Network Management 
Protocol   

LAN = local area network 

 

Safety  

The user is responsible for ensuring that input and output wiring segregation complies with local standards and that in 
the use of the equipment, access is confined to operators and service personnel.   A low resistance earth connection is 
essential to ensure safety and additionally, satisfactory EMI suppression (see below).

 

 
 

HAZARDOUS VOLTAGES EXIST WITHIN A POWER SUPPLY ENCLOSURE AND ANY REPAIRS MUST 

BE CARRIED OUT BY A QUALIFIED SERVICEPERSON. 

 

 

Electrical Strength Tests

 

Components within the power supply responsible for providing the safety barrier between input and output are con-
structed to provide electrical isolation as required by the relevant standard. However EMI filtering components could be 
damaged as result of excessively long high voltage tests between input, output and ground. Please contact our techni-
cians for advice regarding electric strength tests. 

 

Earth Leakage

 

The EMI suppression circuits causes earth leakage currents which may be to the maximum allowable of 3.5mA. 

 

 

Ventilation

 

 

High operating temperature is a major cause of power supply failures,  for example it has been well documented that a 
10

o

C rise in the operating temperature of a component will halve its expected life.   Therefore always ensure that there is 

adequate ventilation for the equipment.   Batteries and cooling fans also suffer shortened lifetimes if subjected to high 
ambient temperatures - both should be included in a routine maintenance schedule to check for signs of  reduced effi-
ciency. 

 

Water / Dust  

Every effort must be made in the installation to minimise the risk of ingress of water or dust. Water will almost always  
cause instant failure.   The effects of dust are slower in causing failure of electronic equipment but all electrical equip-
ment should be cleaned free of any dust accumulation at regular intervals.   This is particularly important where internal 
fans are fitted. 

 

Electromagnetic Interference (EMI) 

Switching power supplies and converters inherently generate electrical noise.  All wiring should be as short as practica-
ble and segregated from  all equipment wiring which is sensitive to EMI.   Residual noise can be reduced by looping DC 
wiring through ferrite cable sleeves. These are most effective as close to the power supply as possible and as many 
turns of the wire taken through the core (+ and - in the same direction) as the core will accommodate.  
 

Fuse ratings 

Check that the wiring and fuses or MCBs match the rating of the PSU or converter.   Adequate fuse protection of battery 
circuits is very important owing to the large potential currents available from batteries.   Our No-Break DC series has an 
internal ECB for protection of the battery circuit but for all other charging situations should have an external fuse or cir-
cuit breaker fitted in the battery circuit. 
 

Connection polarity 

It is critical to check the polarity carefully when connecting batteries and equipment to DC power supplies and chargers.   
Boost chargers (and some float chargers)  made by Innovative Energies have reverse polarity protection,  which can be 
by an electronic switch  (non-destructive) or an internal fuse which needs to be replaced if a battery is connected in re-
verse.    