background image

Oasis 

TROUBLESHOOTING GUIDE

©2015 Innovair Corporation.  All Rights Reserved.

www.innovair.com

WOE

36C2DB1 / HOE36C2MR1

 

MINI SPLIT SYSTEM

 

Summary of Contents for Oasis WOE36C2DB1

Page 1: ...Oasis TROUBLESHOOTING GUIDE 2015 Innovair Corporation All Rights Reserved www innovair com WOE36C2DB1 HOE36C2MR1 MINI SPLIT SYSTEM E 1 ...

Page 2: ...on lamp Auto lamp Timer lamp Failure Over current protection occurs 4 times X EEPROM error X X The T1 sensor is open circuit or short circuit X X The T2 sensor is open circuit or short circuit X X Indoor outdoor units communication error O light X off flash ...

Page 3: ...ion temperature too high Does the outdoor unit has bad air circulation Yes No Check if the outdoor fan can run properly No Correct the connection of fan motor or replace the fan motor Yes Yes Check if the compressor is normal running No Replace the compressor Yes Replace the capillary Evacuate the system and recharge refrigerant Disconnect with the power and replace the main PCB Turn on the units ...

Page 4: ...the connections No Yes Yes Replace indoor or outdoor PCB Replace the sensor and c h e c k i f t h e p r o b l e m happen again 9 2 3 EEPROM parameter error diagnosis and solution Is the EEPROM chip plugged in PCB well Yes No Yes Correct the connection Replace the indoor PCB Shut off the power supply and turn it on 5 seconds later Is it still displaying the error code ...

Page 5: ... wire Is the error still displaying after several minutes No Yes Change the outdoor Main PCB Power on Is the error extinguished Check all the wirings between indoor and outdoor indoor PCB and outdoor PCB following the wiring diagram Are all the wirings connected correctly Is the wiring to the indoor PCB connected correctly Change the indoor PCB Yes Change the outdoor main PCB No Is the wiring to t...

Reviews: